[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-110-1-fire-law-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-038","fire-110-1-fire-law-038",110,1,38,"依建築技術規則建築設計施工編規定，有關防火門構造等相關規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"防火門周邊 10 公分範圍內之牆壁應以不燃材料建造","防火門之門扇寬度應在 100 公分以上，高度應在 200 公分以上","常時關閉式之防火門應用鑰匙開啟，並應裝設經開啟後可自行關閉之裝置","防火門應朝避難方向開啟。但供住宅使用及宿舍寢室、旅館客房、醫院病房等連接走廊者，不在此限","D",null,[],false,"本題考點：建築技術規則建築設計施工編關於防火門窗構造之四項要件——周邊不燃範圍、門扇尺寸、開啟方式與開啟方向。\n【正解理由】依建築技術規則建築設計施工編防火門窗之規定，防火門應朝避難方向開啟，但供住宅使用及宿舍寢室、旅館客房、醫院病房等連接走廊者，不在此限。(D) 之敘述與該規定及其但書相符，故選 D。\n【逐項排除】\n(A) 周邊應以不燃材料建造之範圍為十五公分，並非十公分；該範圍在防止火勢由門框周邊之可燃牆體繞過門扇延燒，縮短為十公分不符規定。\n(B) 門扇尺寸下限為寬七十五公分以上、高一百八十公分以上，係以人員通行需求反推;(B) 誤植為寬一百公分、高二百公分，並非法定數值。\n(C) 常時關閉式防火門應免用鑰匙即可開啟，並裝設經開啟後可自行關閉之裝置;(C) 寫成應用鑰匙開啟，與規定完全相反，火災時將使避難者受阻於門後。\n(D) 朝避難方向開啟，及住宅、宿舍寢室、旅館客房、醫院病房連接走廊者之除外，均與規定一致，為本題應選者。\n【記憶點】防火門：十五公分不燃、七十五乘一百八十、免鑰匙且自行關閉、朝避難方向開。","防火門的要件可拆成「範圍、尺寸、開啟方式、開啟方向」四面向理解。周邊十五公分範圍內之牆壁須以不燃材料建造，是因為門扇本身雖具防火時效，若門框周邊為可燃裝修，火勢會繞過門扇由牆體延燒，使防火門形同虛設。門扇寬七十五公分以上、高一百八十公分以上，則以人員攜物、擔架通行及消防人員著裝進入的最小斷面反推；寬度不足會在避難路徑上形成瓶頸，使通過時間急遽拉長。\n常時關閉式防火門要求「免用鑰匙即可開啟」並裝設開啟後可自行關閉之裝置，是歷次重大火災的教訓：上鎖的防火門會把避難路徑變成死巷，而自行關閉裝置確保人員通過後門扇復歸，維持區劃完整。與之對照的是常時開放式防火門，平時開啟、由探測器或閉門器連動於火災時關閉，兩者在題目中常互換敘述設陷阱。\n開啟方向的但書涉及避難流線：一般場所防火門朝避難方向開啟，人流推擠時仍可推開；但住宅、宿舍寢室、旅館客房、醫院病房等連接走廊者，門扇外開會侵占走廊有效寬度，反而阻礙走廊上的避難人流，故予排除。\n延伸考點：防火門窗屬防火設備，常與《設置標準》併同命題，例如第 49 條免裝撒水頭處所中「主要構造為防火構造，且開口設有具一小時以上防火時效之防火門之金庫」,以及第 188 條排煙風管貫穿防火區劃時應在貫穿處設防火閘門；辨明「防火門窗」與「防火閘門」各自的適用對象，是這一組題目的關鍵。防火時效之等級(半小時、一小時、二小時)則隨所在區劃之重要性遞增,《設置標準》第 190 條免設排煙設備之條件即分別要求半小時以上阻熱性與一小時以上阻熱性之防火門窗等防火設備，數值層級與本題的門扇構造要件宜分開記憶，避免互相污染。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-037","有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-039","依建築技術規則建築設計施工編規定，有關建築技術用語之定義，下列敘述何者正確？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-036","依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-040","依建築技術規則建築設計施工編規定，下列何者屬無窗戶居室？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-035","某幼兒園經當地消防機關會勘通過依法取得使用執照，依消防安全設備檢修及申報辦法規定，自該使用執照證明文件核發之日期起算，距申報期限在幾個月內，免辦理當次檢修及申報備查？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-111-1-fire-law-001","依消防法及消防法施行細則之規定，下列那一個場所應由管理權人，遴用防火管理人並責其製定消防防護計畫報請消防機關核備？",111,[53,57,61,65,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-038",114,"依消防法規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-038",113,"有關六類公共危險物品製造、儲存及處理場所之安全管理，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-038",112,"依建築技術規則建築設計施工編之規定，下列何者屬耐燃二級裝修材料？",{"webId":66,"year":51,"stem":67,"number":13},"fire-111-1-fire-law-038","有關加壓送水裝置之電動機，其種類、構造及機能等之敘述，何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-fire-law-038",109,"依建築技術規則建築設計施工編之定義，經主管機關認可後，下列何者屬「防火設備」？",1785129969868]