[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-037","fire-110-1-fire-law-037",110,1,37,"有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"手動啟動裝置標示係紅底白字，長 300 mm 以上","放射表示燈規格，點燈時紅底白字，長 280 mm 以上","移動放射方式標示係紅底白字，長 100 mm 以上","音響警報裝置標示係紅底白字，每字大小為 25 mm×25 mm 以上","A",null,[],false,"本題考點：二氧化碳滅火設備各種標示規格之法源與尺寸;《各類場所消防安全設備設置標準》第 97 條明定「二氧化碳滅火設備使用之各種標示規格，由中央消防機關另定之」。\n【正解理由】依第 97 條之授權，細部尺寸另定於中央消防機關訂頒之二氧化碳滅火設備各種標示規格。其中手動啟動裝置之標示為紅底白字、長三百毫米以上，與 (A) 所述完全一致，故選 A。\n【逐項排除】\n(A) 手動啟動裝置標示紅底白字、長 300 mm 以上，與該標示規格所定尺寸相符，為本題應選者。\n(B) 放射表示燈依第 93 條設於防護區域出入口等易於辨認處所，點燈時雖為紅底白字，惟長度並非 280 mm,尺寸數值與規格不符。\n(C) 移動放射方式依第 96 條，於儲存容器近旁設紅色標示燈並標明移動式二氧化碳滅火設備字樣，該標示長度非 100 mm。\n(D) 音響警報裝置依第 92 條設置，全區放射方式並採人語發音，其標示每字大小非 25 mm×25 mm。\n【記憶點】標示規格的授權在第 97 條，手動啟動裝置紅底白字、長 300 mm 以上。","二氧化碳滅火設備的標示與警報體系，在《設置標準》中是分條佈建、再由第 97 條把「規格」統一授權給中央消防機關：第 92 條規定音響警報裝置，手動或自動裝置動作後應自動發出警報，且藥劑未全部放射前不得中斷，設於全區放射方式者採人語發音(平時無人駐守者除外);第 93 條規定全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有二十秒以上之遲延裝置，並於防護區域出入口等易於辨認處所設置放射表示燈；第 96 條移動式則要求儲存容器近旁設紅色標示燈及標明移動式二氧化碳滅火設備字樣，每一瞄子之藥劑放射量在溫度攝氏二十度時應在每分鐘六十公斤以上。第 98 條又規定乾粉滅火設備之各種標示規格準用第 97 條，同一套規格橫跨兩種設備，是高頻命題點。\n標示為何要用紅底白字並限定尺寸與字級？因為二氧化碳屬窒息性藥劑，放射後防護區劃內含氧量驟降，遲延裝置、音響警報與放射表示燈是避免人員誤入的最後防線；標示看不清等同保護失效，故連長度與字級都入法。\n可併記的鄰近數值：第 82 條三種放射方式中，移動放射方式之皮管接頭至防護對象任一部分之水平距離在十五公尺以下；第 88 條啟動用氣體容器能耐每平方公分二百五十公斤或 25 MPa 之壓力，內容積一公升以上，所儲存二氧化碳重量在零點六公斤以上，充填比在一點五以上。這些數值與標示規格常在同一題組交錯出現，宜整組記憶。條號串記上可用「九二音響警報、九三遲延裝置與放射表示燈、九六移動式紅色標示燈、九七標示規格授權、九八乾粉準用」拉成一條線，遇到標示題先回到第 97 條這個授權條，再往細部規格找數值，就不會把設置規定與規格尺寸混為一談。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-036","依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-038","依建築技術規則建築設計施工編規定，有關防火門構造等相關規定，下列敘述何者正確？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-035","某幼兒園經當地消防機關會勘通過依法取得使用執照，依消防安全設備檢修及申報辦法規定，自該使用執照證明文件核發之日期起算，距申報期限在幾個月內，免辦理當次檢修及申報備查？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-039","依建築技術規則建築設計施工編規定，有關建築技術用語之定義，下列敘述何者正確？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-034","依消防安全設備及必要檢修項目檢修基準規定，室內消防栓設備水帶製造年份超過 10 年應使用耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。X＋Y 為多少？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-040","依建築技術規則建築設計施工編規定，下列何者屬無窗戶居室？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-037",114,"依建築技術規則建築設計施工編規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-037",113,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，六類物品製造場所及一般處理場所，其外牆或相當於該外牆之設施外側，與廠區外鄰近公共危險物品及可燃性高壓氣體製造、儲存或處理場所、加油站、加氣站、天然氣儲槽、可燃性高壓氣體儲槽、爆竹煙火製造、儲存、販賣場所及其他危險性類似場所之安全距離，應在多少公尺以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-037",112,"依建築技術規則建築設計施工編之規定，有關建築技術用語之定義，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-037",111,"依據乾粉滅火設備各種標示規格規定，其標示規格為長 480 mm 以上，寬 270 mm 以上，黃底黑字，每字大小為 25 mm×25 mm 以上，係屬下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-037",109,"依建築技術規則建築設計施工編之定義，每層陽臺面積之和，以不超過建築面積多少為限？其未達 8 平方公尺者，得建築 8 平方公尺。",1785129969863]