[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-034","fire-110-1-fire-law-034",110,1,34,"依消防安全設備及必要檢修項目檢修基準規定，室內消防栓設備水帶製造年份超過 10 年應使用耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。X＋Y 為多少？",{"A":16,"B":17,"C":18,"D":19},"10","12","16","17","B",null,[],false,"本題考點：室內消防栓設備水帶之耐水壓試驗數值，依《消防安全設備及必要檢修項目檢修基準》第二章室內消防栓設備之性能檢查。\n【正解理由】該章消防栓箱等之檢查方法就第一種消防栓明定，製造年份超過十年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，並利用相關器具夾住水帶兩末端處，確認快速接頭已確實連接及水帶內無殘留之空氣後，「施以 7kgf\u002Fcm² 以上水壓試驗 5 分鐘合格，始得繼續使用。但已經水壓試驗合格未達 3 年者，不在此限」。X 為七、Y 為五，X＋Y 等於十二，故選 B。\n【逐項排除】\n(A) 十：與基準所定之七與五之和不符；此值多半來自把題幹「製造年份超過十年」的年數直接當成答案。\n(B) 十二：七加五即為十二，與原文相符，為本題應選者。\n(C) 十六：若把壓力誤用室外消防栓設備與射水設備水帶的六，再把時間誤記為十分鐘，即得此值。\n(D) 十七：壓力七是對的，但時間被誤記為十分鐘；基準所定之試驗時間一律為五分鐘。\n【記憶點】水帶耐壓：室內消防栓、泡沫消防栓箱、連結送水管為七，室外消防栓與射水設備為六，時間一律五分鐘，合格未滿三年免再試。","同一項檢查散落在五個章節，只有壓力值不同，值得一次背完：第二章室內消防栓設備（第一種）、第七章泡沫滅火設備之泡沫消防栓箱、第二十章連結送水管之水帶箱，均為 7kgf\u002Fcm² 以上、5 分鐘；第三章室外消防栓設備與第二十六章射水設備之室外消防栓箱，則為 6kgf\u002Fcm² 以上、5 分鐘。各章的但書一致：已經水壓試驗合格未達 3 年者，不在此限；適用對象也一致：製造年份超過 10 年或無法辨識製造年份之水帶。第二種消防栓因採瞄子開閉裝置操作、平時不必拆接水帶，其檢查方法只以目視確認有無腐蝕、損傷及瞄子開閉裝置操作是否容易，不做水壓試驗。\n最容易與此混淆的是「配管的加壓試驗」，兩者單位與時間都不同：《各類場所消防安全設備設置標準》第三十三條規定室內消防栓設備之消防立管管系竣工時應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓，並以繼續維持二小時無漏水現象為合格。一個是「倍數＋小時」，一個是「kgf\u002Fcm²＋分鐘」，命題者常故意互換。\n室內消防栓設備的其他常考數值可一併整理：第三十六條規定水源容量應在裝置室內消防栓最多樓層之全部消防栓繼續放水二十分鐘之水量以上，該樓層內全部消防栓數量超過二支時以二支計算；第三十八條規定緊急電源應使用發電機設備或蓄電池設備，其供電容量應供其有效動作三十分鐘以上，供第十二條第四款所列丁類工作場所使用者，得使用具有相同效果之引擎動力系統。檢修基準第二章之性能檢查另就減壓措施規定，放水壓力應在 1.7kgf\u002Fcm² 以上 7kgf\u002Fcm² 以下，但公共危險物品等場所達顯著滅火困難者所設第一種滅火設備之消防栓，放水壓力應在 3.5kgf\u002Fcm² 以上 7kgf\u002Fcm² 以下。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-033","依消防安全設備及必要檢修項目檢修基準規定，有關固定式泡沫滅火設備（低發泡）綜合檢查之檢查方法，下列敘述何者正確？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-035","某幼兒園經當地消防機關會勘通過依法取得使用執照，依消防安全設備檢修及申報辦法規定，自該使用執照證明文件核發之日期起算，距申報期限在幾個月內，免辦理當次檢修及申報備查？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-032","裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-036","依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-031","有關標示設備之規定，下列敘述何者正確？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-037","有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-034",114,"依消防法施行細則規定，下列何者非屬消防防災計畫應包括事項？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-034",113,"有關防火牆及防火水幕設置基準規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-034",112,"避難器具支固器具以直接裝置在建築物主要構造部之施工方法，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-034",111,"依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-034",109,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，幫浦所消耗之動力，在額定出水量 150%時，其軸動力不得超過馬達額定輸出馬力之多少以下？",1785129969838]