[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-027","fire-110-1-fire-law-027",110,1,27,"依各類場所消防安全設備設置標準規定，自動撒水設備得依實際情況需要選擇適當型式設置。但下列何種場所應設開放式？",{"A":16,"B":17,"C":18,"D":19},"集會堂使用之舞臺","旅館","車站","醫院","A",null,[],false,"本題考點：自動撒水設備型式之選設自由，以及「應設開放式」的強制例外，依《各類場所消防安全設備設置標準》第四十三條但書。\n【正解理由】第四十三條本文規定自動撒水設備得依實際情況需要就密閉濕式、密閉乾式、開放式、預動式等款擇一設置，但書則明定「供第十二條第一款第一目所列場所及第二目之集會堂使用之舞臺，應設開放式」；集會堂列於第十二條第一款第二目，其舞臺正是但書所點名者，故選 A。\n【逐項排除】\n(A) 集會堂使用之舞臺為第四十三條但書明文列舉者，舞臺布幕與道具等可燃物集中、裝置面挑高，密閉型撒水頭受熱動作慢，須以一齊開放閥使全區同時撒水，為本題應選者。\n(B) 旅館列於第十二條第一款第三目（觀光旅館、飯店、旅館、招待所），不在但書射程內，仍得於四種型式間擇一設置。\n(C) 車站列於第十二條第二款第一目，屬乙類場所，更不受該但書拘束。\n(D) 醫院列於第十二條第一款第六目，雖同屬甲類，但但書只點名第一目所列場所與第二目之集會堂舞臺，醫院不在其中。\n【記憶點】強制開放式只有兩種：第一款第一目所列場所，以及集會堂的舞臺。","第四十三條五款是按「管內平時有什麼」在分類：密閉濕式平時管內貯滿高壓水，撒水頭動作時即撒水；密閉乾式平時管內貯滿高壓空氣，撒水頭動作時先排空氣繼而撒水；開放式平時管內無水，啟動一齊開放閥使水流入管系撒水；預動式平時管內貯滿低壓空氣，以感知裝置啟動流水檢知裝置，且撒水頭動作時即撒水。舞臺被強制指定開放式的關鍵，在於開放式撒水頭沒有感熱元件，一經一齊開放閥動作即全區放水，不必等每一顆撒水頭各自受熱動作。\n開放式的配套規定要一起記：第五十四條規定每一舞臺之放水區域在四個以下，放水區域在二個以上時，每一放水區域樓地板面積在一百平方公尺以上，且鄰接之放水區域相互重疊，使有效滅火；第五十七條第二款規定水源容量，供第十二條第一款第一目使用場所及第二目集會堂之舞臺，在十層以下建築物之樓層時，應在最大放水區域全部撒水頭繼續放水二十分鐘之水量以上，在十一層以上建築物之樓層則以最大樓層全部撒水頭計算。相對地，密閉式是按第五十七條第一款的撒水頭個數表計算，十一樓以上建築物與地下建築物為快速反應型十二個、一般反應型十五個。\n易混淆對照：同樣是集會堂，舞臺應設開放式，觀眾席反而可能免裝——第四十九條第九款規定第十二條第一款第一目所列場所及第二目集會堂使用之觀眾席，設有固定座椅部分且撒水頭裝置面高度在八公尺以上者，得免裝撒水頭。另第十九條第二項規定已依本標準設置自動撒水設備（限使用標示攝氏溫度七十五度以下、動作時間六十秒以內之密閉型撒水頭）者，在該有效範圍內得免設火警自動警報設備，但供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所不適用，這也是「設了撒水就能免設警報」不可無限上綱的界線。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-026","依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-028","依各類場所消防安全設備設置標準規定，下列場所何者屬於乙類場所？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-025","某場所室內高度為 16 公尺，依各類場所消防安全設備設置標準規定，下列何者為可選擇之探測器種類？①定溫式特種 ②差動式分布型 ③光電式局限型一種 ④火焰式",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-029","有一室外儲槽，其容量為 9000 公秉，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，設有防火水幕，下列敘述何者正確？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-024","依各類場所消防安全設備設置標準規定，有關連結送水管之送水設計壓力規定計算，下列敘述何者錯誤？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-030","可燃性高壓氣體儲存場所防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，強度應能承受可能預料之氣體爆炸衝擊，有關混凝土空心磚製防爆牆之規定，下列敘述何者正確？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-027",114,"依各類場所消防安全設備設置標準，針對滅火設備水源容量之規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-027",113,"依消防設備人員法規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-027",112,"依各類場所消防安全設備設置標準之規定，建築物總樓地板面積在多少平方公尺以上應設置防災監控系統綜合操作裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-027",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，儲存第五類公共危險物品分級屬 A 型，其儲存量達管制量 5 倍以上未達 10 倍者且周圍設有圍牆之室內儲存場所，其應保留空地寬度應為多少公尺以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-027",109,"有一 500 平方公尺地下停車場，採水霧滅火設備，依各類場所消防安全設備設置標準，其水源容量應保持多少立方公尺以上？",1785129969784]