[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-039","fire-110-1-alarm-evacuation-039",110,1,39,"依消防安全設備及必要檢修項目檢修基準，火焰式探測器進行性能檢查時，使用火焰探測器用動作試驗器，探測器應在多少時間內動作？",{"A":16,"B":17,"C":18,"D":19},"20 秒","30 秒","50 秒","60 秒","B",null,[],false,"本題考點：火焰式探測器以動作試驗器進行性能檢查時之動作時間，見《消防安全設備及必要檢修項目檢修基準》第十三章火警自動警報設備二、性能檢查之蓄積性能判定方法。\n【正解理由】該節判定方法載明「以火焰式探測器用動作試驗器之紅外線或紫外線照射時，30 秒加上蓄積式中繼器或受信機設定之蓄積時間之合計時間（最大 20 秒）」，探測器本身的動作時間基準即三十秒，故選 B。\n【逐項排除】\n(A) 20 秒是同一句括號內所載蓄積式中繼器或受信機設定蓄積時間之合計上限，屬得加計的緩衝值，不是探測器動作時間本身。\n(B) 與判定方法所載火焰式探測器之三十秒相符，為正確選項。\n(C) 50 秒在該章判定方法之表 13-7、表 13-8 及蓄積性能各項數值中均查無此值。\n(D) 60 秒見於表 13-8 偵煙式（離子式、光電式局限型）二種之動作時間，以及偵煙式蓄積時間合計上限，均非火焰式探測器之基準。\n【記憶點】火焰式探測器照射動作三十秒，蓄積時間另行加計，感熱式與偵煙式各查表 13-7、13-8。","火焰式探測器靠感知火焰輻射之紅外線或紫外線動作，因此《各類場所消防安全設備設置標準》第 124 條的設置規定全在排除「看不到火」與「看錯光」：裝設於天花板、樓板或牆壁；距樓地板面一點二公尺範圍內之空間應在探測器標稱監視距離範圍內；探測器不得設在有障礙物妨礙探測火災發生處；探測器設在無日光照射之處，但設有遮光功能可避免探測障礙者不在此限。第 115 條的裝置位置通則也為它開了兩個例外：天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；局限型探測器之裝置不得傾斜四十五度以上，但火焰式探測器不在此限。\n檢查面看《消防安全設備及必要檢修項目檢修基準》第十三章火警自動警報設備。蓄積性能檢查依表 13-6 選定個數：火警分區數五十以下時，感熱式探測器、偵煙式探測器、火焰探測器各選定一個；五十一以上時各選定二個。判定方法把三類探測器的基準時間分開規定：感熱式加熱時依表 13-7，差動式局限型與補償式局限型之一種、二種均為三十秒，定溫式局限型特種四十秒、一種六十秒、二種一百二十秒，再加受信總機設定之蓄積時間（合計最大二十秒）；偵煙式加煙時依表 13-8，離子式局限型與光電式局限型一種三十秒、二種六十秒、三種九十秒，非蓄積型合計最大六十秒，蓄積型另加標稱蓄積時間後再加五秒；火焰式則以動作試驗器之紅外線或紫外線照射，基準三十秒加蓄積時間合計最大二十秒。同節注意事項並要求進行蓄積性能檢查選擇探測器時應輪流選取，並於圖面或檢查表上註記每次選取之位置。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-038","特別安全梯排煙室設置直接面向戶外之窗戶時，窗戶之有效開口面積應在多少平方公尺以上？",38,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-040","避難器具之裝設規定，下列何者正確？",40,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-037","下列有關緊急電源插座之設置，何者錯誤？",37,{"webId":41,"stem":42,"number":12,"year":43,"session":12},"fire-111-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",111,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-036","某場所第五層需設置排煙設備，樓地板面積為 1200 平方公尺並區分為 450、400 及 350 平方公尺等三個防煙區劃，試問該層排煙機之排煙量最少應為每分鐘多少立方公尺？",36,{"webId":49,"stem":50,"number":51,"year":43,"session":12},"fire-111-1-alarm-evacuation-002","平時有人之公共危險物品製造、儲存或處理場所，若未達應設置火警自動警報設備之規定時，其儲存、處理公共危險物品數量達幾倍管制量以上，應設置手動報警設備或具同等功能之緊急通報裝置？",2,[53,57,61,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-039",113,"某捷運高架車站，因地形環境因素致車站早晚霧氣瀰漫，為防止霧氣結露產生探測器誤動作，選設之探測器除考量防水性能外，試問下列何者探測器不適用？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-039",112,"依消防安全設備及必要檢修項目檢修基準，檢查一一九火災通報裝置性能時，有關通報裝置本體檢查，下列敘述何者錯誤？",{"webId":62,"year":43,"stem":63,"number":13},"fire-111-1-alarm-evacuation-039","民國 84 年取得使用執照之大樓，測試其火警地區音響裝置之音壓何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-alarm-evacuation-039",109,"有關緊急照明設備之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-alarm-evacuation-039",108,"依各類場所消防安全設備設置標準規定，下列何種場所不須設置緊急電源插座？",1785129964166]