[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-038","fire-110-1-alarm-evacuation-038",110,1,38,"特別安全梯排煙室設置直接面向戶外之窗戶時，窗戶之有效開口面積應在多少平方公尺以上？",{"A":16,"B":17,"C":18,"D":19},"2","4","3","6","A",null,[],false,"本題考點：特別安全梯排煙室採直接面向戶外之窗戶排煙時，窗戶有效開口面積之下限，見《各類場所消防安全設備設置標準》第 189 條第一款。\n【正解理由】第 189 條第一款第三目明定「窗戶之有效開口面積在二平方公尺以上。但特別安全梯排煙室與緊急昇降機間兼用時（以下簡稱兼用），應在三平方公尺以上」。題幹只提特別安全梯排煙室、未述及兼用，適用本文所定二平方公尺以上，故選 A。\n【逐項排除】\n(A) 即第一款第三目本文所定二平方公尺以上，為正確選項。\n(B) 四平方公尺在本款查無對應；同條第二款第四目出現的「四」是排煙機、進風機每秒四立方公尺之風量，計量單位為立方公尺每秒而非開口面積。\n(C) 三平方公尺是同一目但書所定「兼用時」之值，題幹未述及與緊急昇降機間兼用，不能逕用但書。\n(D) 六平方公尺在本款亦無對應；同條第二款第四目兼用時之每秒六立方公尺是風量，與窗戶有效開口面積無關。\n【記憶點】特別安全梯排煙室自然排煙：窗戶有效開口二平方公尺以上，與緊急昇降機間兼用時為三平方公尺以上。","特別安全梯或緊急昇降機間排煙室之排煙設備規定在《各類場所消防安全設備設置標準》第 189 條，其應設依據則是第 28 條第一項第五款「依建築技術規則應設置之特別安全梯或緊急昇降機間」。第 189 條的體例是「依下列規定選擇設置」，也就是自然排煙（直接面向戶外之窗戶）與機械排煙（排煙、進風風管）二擇一，本題問的是前者。\n自然排煙的四目要件依序為：在排煙時窗戶與煙接觸部分使用不燃材料；窗戶有效開口面積位於天花板高度二分之一以上之範圍內；窗戶之有效開口面積在二平方公尺以上，但兼用時應在三平方公尺以上；平時關閉之窗戶設手動開關裝置，其操作部分設於距離樓地板面八十公分以上一百五十公分以下之牆面，並標示簡易之操作方式。條文把「特別安全梯排煙室與緊急昇降機間兼用」簡稱為兼用，凡出現兼用字樣就是另一組數值，讀題時務必先確認題幹有無兼用之敘述。\n機械排煙的對照數值同樣成組出現：排煙口位於天花板高度二分之一以上之範圍內，與直接連通戶外之排煙風管連接，該風管並連接排煙機；進風口位於天花板高度二分之一以下之範圍內，其直接面向戶外者開口面積在一平方公尺以上，兼用時為一點五平方公尺以上；排煙機、進風機之排煙量、進風量在每秒四立方公尺以上，兼用時每秒六立方公尺以上，且可隨排煙口、進風口開啟而自動啟動；排煙口、進風口設手動開關裝置及探測器連動自動開關裝置，平時保持關閉狀態；排煙口、進風口、排煙機及進風機連接緊急電源，供電容量應供其有效動作三十分鐘以上。此外可一併記第 49 條第二款，室內安全梯間、特別安全梯間或緊急昇降機間之排煙室得免裝撒水頭，同樣是排煙室的常考條文。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-037","下列有關緊急電源插座之設置，何者錯誤？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-039","依消防安全設備及必要檢修項目檢修基準，火焰式探測器進行性能檢查時，使用火焰探測器用動作試驗器，探測器應在多少時間內動作？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-036","某場所第五層需設置排煙設備，樓地板面積為 1200 平方公尺並區分為 450、400 及 350 平方公尺等三個防煙區劃，試問該層排煙機之排煙量最少應為每分鐘多少立方公尺？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-040","避難器具之裝設規定，下列何者正確？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-035","依各類場所消防安全設備設置標準規定，避難指標設於走廊或通道時，自走廊或通道任一點至指標之步行距離在多少公尺以下？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-111-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",111,[53,57,61,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-038",113,"針對差動式分布型空氣管式探測器進行接點水高試驗，其試驗之目的為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-038",112,"有關通報試驗蓄積語音訊息之性能試驗，依據一一九火災通報裝置測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":51,"stem":63,"number":13},"fire-111-1-alarm-evacuation-038","依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-alarm-evacuation-038",109,"有關應設置緊急照明設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-alarm-evacuation-038",108,"依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",1785129964158]