[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-020":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-020","fire-110-1-alarm-evacuation-020",110,1,20,"有關辦公大樓排煙設備之啟動裝置在消防安全設備及必要檢修項目檢修基準之性能及綜合檢查的檢查及判定方法，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"性能檢查時，須針對自動及手動啟動裝置進行檢查及判定","探測器動作後，能連動排煙機啟動","綜合檢查時，勿切換成緊急電源之狀態","綜合檢查時，須記錄運轉電流","C",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》第二十二章排煙設備，性能檢查與綜合檢查的檢查方法及判定方法。\n【正解理由】依該章綜合檢查之檢查方法，明定「切換成緊急電源的狀態，使偵煙式探測器動作及操作手動啟動裝置，以確認各部分之性能」，可見綜合檢查本來就是要在緊急電源供電狀態下驗證整套連動；只有醫院等切換成緊急電源進行檢查有困難之場所，才依注意事項改用常用電源進行檢查。本題問敘述錯誤者，(C) 稱綜合檢查時勿切換成緊急電源，與該明文相反，故選 C。\n【逐項排除】\n(A) 性能檢查之「啟動裝置」分列「自動啟動裝置」與「手動啟動方式」兩項，各有檢查方法與判定方法，兩者都在檢查範圍內，敘述正確。\n(B) 自動啟動裝置之檢查方法為「確認探測器動作後，能否連動排煙機啟動」，判定方法為「排煙機應能確實啟動」，敘述正確。\n(C) 綜合檢查以切換成緊急電源為前提，敘述與基準相反，為本題應選者。\n(D) 綜合檢查判定方法第二點為「運轉電流在所規定的範圍內」，須量測並記載運轉電流始能判定，敘述正確。\n【記憶點】排煙設備綜合檢查＝切到緊急電源，探測器與手動啟動各動一次，看排煙機是否連動、運轉電流是否在範圍內。","排煙設備的檢修分外觀檢查、性能檢查、綜合檢查三個階段，層次是遞進的：外觀看有無變形、損傷；性能拆成「電動機之控制裝置」「啟動裝置」「排煙機」逐項確認；綜合檢查則是把整套系統放在最接近火災的條件下跑一次。所謂最接近火災的條件，關鍵就在電源狀態——火災時常用電源可能已經跳脫，設備必須靠緊急電源運轉，因此基準把「切換成緊急電源的狀態」直接寫進綜合檢查的檢查方法，並在注意事項留下唯一例外：醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查。命題者把這個例外倒過來寫成通則，就是本題的陷阱所在。\n綜合檢查的四項判定值得整組背：一、吸煙口及排煙閘門打開後，能連動自動排煙機啟動；二、運轉電流在所規定的範圍內；三、排煙機在運轉中應無異常聲音及振動，風道應無異常振動；四、排煙機回轉葉片的回轉方向應正常。前兩項問「會不會動、動得對不對」，後兩項問「動得順不順」。\n性能檢查則要分辨檢查對象。電動機之控制裝置查各開關、保險絲、繼電器、表示燈、結線接續、接地共六項，判定重點分別是端子無鬆動發熱、依回路圖所定種類及容量、繼電器無接點燒損且動作正常、表示燈能正常亮燈、結線無斷線脫落、接地無顯著腐蝕。啟動裝置分兩型：自動啟動裝置之偵煙式探測器依照火警自動警報設備之檢查要領進行，並確認探測器動作後能否連動排煙機啟動；手動啟動方式則確認操作箱把手及操作桿之轉動與打開動作，判定為把手應能容易轉動、操作桿無破損、鋼索無斷落或生鏽。排煙機再分電動機與回轉葉片，兩者都查回轉軸與軸承部，電動機另查動力傳達裝置的皮帶輪與Ｖ型皮帶。\n易混淆之處在於「連動」在兩個階段都出現：性能檢查的自動啟動裝置只確認探測器動作後排煙機能否啟動；綜合檢查則再加上吸煙口與排煙閘門開啟後的連動，以及運轉電流、聲音振動、回轉方向等整體表現。此外性能檢查電動機時另有注意事項：測試會影響所連動之空調機械，且除運轉的性能檢查外必須將電源切斷。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-019","對於設置在地下建築物、地下層及地上層三者之居室的緊急照明燈進行性能檢查，依照消防安全設備及必要檢修項目檢修基準之規定，使用低照度測定用光電管照度計測試，在地面之水平面照度應分別達多少勒克斯（lux）以上？",19,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-021","下列有關免設火警探測器之場所，何者錯誤？",21,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-018","下列避難器具架設完成後，進行綜合檢查時，何者應判定不合格？",18,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-022","有一地下 3 層、地上 7 層之建築物，各層樓地板面積為 600 平方公尺，若地下 1 樓發生火警，則火警自動警報設備之鳴動樓層，下列何者正確？",22,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-017","下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",17,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-023","依各類場所消防安全設備設置標準，火警探測器之探測區域係指裝置面之四周以淨高 X 公分以上之樑或類似構造體區劃包圍者。偵煙式探測器，其裝置面之四周淨高應為 Y 公分，其中 X 及 Y 分別為：",23,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-020",113,"一棟建築物擁有地下 2 層以及地上 8 層，B1F, B2F 各層面積均為 400 平方公尺，1F, 2F 面積皆為 350 平方公尺，3~8F 皆為 280 平方公尺，依據各類場所消防安全設備設置標準之規定，下列何者正確？（1F 為地面層，BF 代表地下層，B1F 為地下 1 層，依此類推）",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-020",112,"依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-020",111,"依消防安全設備及必要檢修項目檢修基準，實施緊急照明設備性能檢查，檢查數量下列之敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-020",109,"B 級出口標示燈且有顯示避難方向符號者，其有效距離係指步行至該燈多少公尺之距離？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-020",108,"依消防法令規定，觀光旅館、飯店、旅館、招待所（限有寢室客房者）等場所，採膠囊式經營時，須設置火警自動警報設備者，下列何者錯誤？",1785129963978]