[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-019","fire-110-1-alarm-evacuation-019",110,1,19,"對於設置在地下建築物、地下層及地上層三者之居室的緊急照明燈進行性能檢查，依照消防安全設備及必要檢修項目檢修基準之規定，使用低照度測定用光電管照度計測試，在地面之水平面照度應分別達多少勒克斯（lux）以上？",{"A":16,"B":17,"C":18,"D":19},"10、10、10","10、10、2","10、2、2","2、2、2","D",null,[],false,"本題考點：緊急照明燈之照度判定值，十勒克斯只適用於地下建築物之地下通道。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十九章緊急照明設備之性能檢查，使用低照度測定用光電管照度計測試，其判定方法為「於地下建築物之地下通道，緊急照明燈在地面之水平面照度應達十勒克斯（lux）以上；其它場所應達到二勒克斯（lux）以上」；《各類場所消防安全設備設置標準》第 178 條同此意旨。本題所問三處均為居室而非地下通道，故地下建築物、地下層與地上層之居室一律適用二勒克斯，故選 D。\n【逐項排除】\n(A) 10、10、10 係把十勒克斯全面套用於居室，惟十勒克斯之適用對象限於地下建築物之地下通道。\n(B) 10、10、2 把地下建築物與地下層之居室都當成地下通道，地下層之居室並無十勒克斯之規定。\n(C) 10、2、2 僅將地下建築物之居室誤列為十勒克斯，該居室仍非地下通道，應為二勒克斯。\n(D) 三者均為居室，皆屬「其它場所」，水平面照度均為二勒克斯以上，為本題應選者。\n【記憶點】只有地下建築物的地下通道要十勒克斯，居室一律二勒克斯。","本題的陷阱在「地下建築物」與「地下通道」不是同一件事。第 178 條的文字是「在地下建築物之地下通道，其地板面應在十勒克司（Lux）以上，其他場所應在二勒克司（Lux）以上」，主詞是地下通道，不是整個地下建築物；同條另有但書：在走廊曲折點處，應增設緊急照明燈。地下建築物內的居室既然不是地下通道，就回到二勒克斯這一級。\n第十九章的性能檢查不是只量照度。檢查項目還包括：檢查開關，以目視確認有無變形或端子有無鬆動，並由檢查開關進行常用電源之切斷及復舊操作，切斷常用電源時應能自動切換至緊急電源即時亮燈，復舊時亦能自動切換回常用電源；保險絲類應無損傷或熔斷，且為規定之種類及容量；結線接續應無斷線、端子鬆動、脫落、損傷；緊急電源於切換狀態時應無不亮燈或閃爍之情形，且電源容量應能持續三十分鐘以上。\n緊急電源容量的檢查數量是級距表，不是比例式，逐格為：建築物總樓地板面積 1000m2 以下者 5 個以上、3000m2 以下者 10 個以上、6000m2 以下者 15 個以上、10000m2 以下者 20 個以上、超過 10000m2 者為 20 個加上每增加 5000m2 增加 5 個。另可一併記住兩件事：依第 13 條，各類場所增建、改建或變更用途時原則適用變更前之標準，但消防安全設備為滅火器、火警自動警報設備、手動報警設備、緊急廣播設備、標示設備、避難器具及緊急照明設備者，適用變更後之標準；以及第 146-6 條所定觀眾席引導燈之照度，在觀眾席通道地面之水平面上測得之值在零點二勒克司（lx）以上，屬另一種設備的照度規定。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-018","下列避難器具架設完成後，進行綜合檢查時，何者應判定不合格？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-020","有關辦公大樓排煙設備之啟動裝置在消防安全設備及必要檢修項目檢修基準之性能及綜合檢查的檢查及判定方法，下列敘述何者錯誤？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-017","下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-021","下列有關免設火警探測器之場所，何者錯誤？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-016","建築物之避難器具設置緩降機時，對其開口部進行外觀檢查之判定，下列何者合格？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-022","有一地下 3 層、地上 7 層之建築物，各層樓地板面積為 600 平方公尺，若地下 1 樓發生火警，則火警自動警報設備之鳴動樓層，下列何者正確？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-019",113,"某百貨公司設計有一挑高中庭，其高度為 14 公尺，依據各類場所消防安全設備設置標準之規定，請問下列探測器何者不適合？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-019",112,"消防安全設備及必要檢修項目檢修基準的火警自動警報設備的探測器性能檢查中，使用火焰探測器用動作試驗器，在確認火焰探測器之動作及火警分區之表示是否正常時，火焰探測器之動作時間應在幾秒內動作？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-019",111,"有關緊急照明燈的緊急電源及配線之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-019",109,"具閃滅或音聲引導功能之出口標示燈設置規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-019",108,"應設排煙設備場所之樑為裸露式者，交錯之樑形成之各防煙區劃皆應設置排煙口。但其樓地板面積每 500 平方公尺防煙區劃內，防煙壁及排煙口之設置，符合各類場所消防安全設備設置標準第 188 條第 1 項第 3 款規定，並符合下列何者，不在此限？〔A：大樑深度（cm）；B：中樑深度（cm）；X：大樑下加設之垂壁高度（cm），其值得為 0；A＋X：防煙壁下垂高度（cm）。〕",1785129963972]