[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-018","fire-110-1-alarm-evacuation-018",110,1,18,"下列避難器具架設完成後，進行綜合檢查時，何者應判定不合格？",{"A":16,"B":17,"C":18,"D":19},"懸吊型避難梯突起向牆壁方向，牆壁與橫桿之間隔在 15 公分","緩降機下降距離及下降時間分別測量為 1800 公分及 20 秒","斜降式救助袋本體下部出口離地面 95 公分","避難繩下端距離地面 60 公分","D",null,[],false,"本題考點：避難器具架設完成後綜合檢查之判定值，涵蓋避難梯間隔、緩降機下降速度、救助袋出口高度與避難繩索繩端位置。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十八章避難器具之綜合檢查，繩索類避難器具之下降準備判定明定「把繩子展開時，應無纏繞等，而能成直線垂下，繩子之長端應能到達地面上」，繩端確實到達地面是合格要件。避難繩索下端距離地面 60 公分，繩端並未到達地面，避難者最後一段須跳落，應判定不合格，故選 D。\n【逐項排除】\n(A) 懸吊型避難梯之判定為梯子全長應能順利伸長，突起向牆壁方向時，牆壁與橫桿之間隔應有十公分以上；題示 15 公分已符合。\n(B) 下降速度為 1800 公分除以 20 秒，等於每秒 90 公分，落在平均降落速度每秒 80 至 100 公分之範圍內，且未逾最大下降速度每秒 150 公分，應判定合格。\n(C) 斜降式救助袋之下部出口，依綜合檢查程序係將張設繩索充分拉緊，使其大約離地面 50 公分至 100 公分；題示 95 公分在此範圍內。\n(D) 避難繩索下端距離地面 60 公分，繩端未到達地面，不符合繩子長端應能到達地面之判定，為本題應選者。\n【記憶點】繩端一定要落地；緩降機每秒八十至一百公分。","綜合檢查是在完成外觀檢查及性能檢查之後實施，檢查時應使避難器具成使用狀態，確認其性能是否正常，所以它量的都是「真的架起來用一次」才會出現的值。緩降機部分分為下降準備、下降、收藏三段：下降準備要求拴緊緩降機連結部（掛鉤等）之環扣，應能完全地安裝在支固器具，把繩子展開時應無纏繞而能成直線垂下、繩子之長端應能到達地面上；下降則測量下降距離及下降時間，計算出下降速度，應在規定的下降速度範圍內，即平均的降落速度應在每秒 80 至 100cm，最大下降速度應在每秒 150cm 以內，下降後再實施性能檢查，器具本體、支固器具等應無異常；收藏則要求各部份應無變形且能順暢地恢復原狀，捲取繩子時應使輪盤本身轉動，以避免繩子扭曲。\n避難梯依型式分別判定。懸吊型者，梯子之全長應能順利伸長，突起向牆壁方向，牆壁與橫桿之間隔應有十公分以上，梯柱成垂直、橫桿成水平，下降時亦同；固定收藏型者，被收藏之梯柱應能順利展開，下端碰到堅固的地面，梯柱成垂直、橫桿成水平，下降時梯柱及橫桿應無明顯地搖動。避難橋則確認各部份應無翹曲、明顯變形、損傷等，搭架長度不得有變化；移動型者應具有充份之搭架長度，與固定部或支持部之連接處不得妨礙避難。\n紀錄面也常入題：避難器具檢查表於檢查合格者在判定欄打圈，有不良情形時打叉並填載不良狀況與處置措施；避難器具為緩降機者，應加填附表，逐具填寫樓層別、設置位置、下降距離（公分）、下降時間（秒）與下降速度（公分／秒），本題 (B) 的數據正是這張附表的三個欄位。另依第 164 條，緩降機之下降空間為以器具中心半徑零點五公尺圓柱形範圍內，避難梯為自避難梯二側豎桿中心線向外二十公分以上及其前方六十五公分以上之範圍內。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-017","下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-019","對於設置在地下建築物、地下層及地上層三者之居室的緊急照明燈進行性能檢查，依照消防安全設備及必要檢修項目檢修基準之規定，使用低照度測定用光電管照度計測試，在地面之水平面照度應分別達多少勒克斯（lux）以上？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-016","建築物之避難器具設置緩降機時，對其開口部進行外觀檢查之判定，下列何者合格？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-020","有關辦公大樓排煙設備之啟動裝置在消防安全設備及必要檢修項目檢修基準之性能及綜合檢查的檢查及判定方法，下列敘述何者錯誤？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-015","對空氣管式之差動式分布型探測器進行空氣注入之性能檢查時，下列何種試驗無須量測探測器導通與否？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-021","下列有關免設火警探測器之場所，何者錯誤？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-018",113,"探測器容易因設置環境影響其探測能力，因此需考慮設置處所環境，根據各類場所消防安全設備設置標準之要求，補償式局限型二種探測器不適合安裝在下列場所？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-018",112,"消防安全設備及必要檢修項目檢修基準的緊急照明設備於性能檢查時，判定方法下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-018",111,"局限型偵煙探測器光電式的偵測原理若設計為散亂光式，其對火場中何種信號較不敏感？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-018",109,"依住宅用火災警報器認可基準之規定，住宅用火災警報器以警報音發出火災警報，於無響室中距離警報器中心前方 1 公尺處，音壓應有多少分貝以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-018",108,"利用加瓦斯試驗器對瓦斯漏氣檢知器進行檢測，其性能判定方法下列何者錯誤？",1785129963950]