[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-013":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-013","fire-110-1-alarm-evacuation-013",110,1,13,"容易受風影響之場所（如大廳、禮拜堂、大樓頂上之機械室等），依消防安全設備及必要檢修項目檢修基準之規定，可在下列何種探測器中進行選設？",{"A":16,"B":17,"C":18,"D":19},"定溫式局限型","光電式局限型","差動式局限型","離子式局限型","B",null,[],false,"本題考點：容易受風影響之場所應選設何種探測器，屬檢修基準外觀檢查之適應性判定。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十三章火警自動警報設備之外觀檢查，探測器之注意事項明定「有發生誤報或延遲感知之虞處，應依表 13-2 選設」，大廳、禮拜堂、大樓頂上之機械室等容易受風影響之場所即屬之，該表於此類場所列為可選設者為光電式局限型，故選 B。此類場所亦不在《各類場所消防安全設備設置標準》第 117 條所列偵煙式局限型不得設置之處所（塵埃粉末或水蒸氣大量滯留、腐蝕性氣體、廚房、顯著高溫、廢氣或煙大量滯留流入、結露、火焰外露等）之內。\n【逐項排除】\n(A) 定溫式局限型須待周圍溫度到達標稱動作溫度才動作，氣流持續帶走熱氣流時有延遲感知之虞。\n(B) 光電式局限型以煙粒子對光的散射變化偵測，於氣流大的挑高空間仍能維持感知能力，為該表所列可選設者。\n(C) 差動式局限型靠感熱室內之溫升速率動作，受風場所熱氣流被吹散，溫升速率不易達到動作條件。\n(D) 離子式局限型以離子電流變化偵測，氣流擾動會直接影響離子室內電流，於受風場所易生誤報或失報。\n【記憶點】受風影響大的場所挑光電式局限型。","受風影響的場所通常同時是挑高場所，所以選型還要回到裝置場所高度這一關。第 114 條規定探測器應依裝置場所高度就表選擇種類裝設，同一室內天花板或屋頂板高度不同時以平均高度計：未滿四公尺者可用差動式局限型、差動式分布型、補償式局限型、定溫式、離子式局限型、光電式局限型、光電式分離型、火焰式；四公尺以上未滿八公尺者為差動式局限型、差動式分布型、補償式局限型、定溫式特種或一種、離子式局限型一種或二種、光電式局限型一種或二種、光電式分離型、火焰式；八公尺以上未滿十五公尺者為差動式分佈型、離子式局限型一種或二種、光電式局限型一種或二種、光電式分離型、火焰式；十五公尺以上未滿二十公尺者為離子式局限型一種、光電式局限型一種、光電式分離型一種、火焰式。大樓頂上之機械室或禮拜堂常落在後兩級，可用的種類本來就被限縮。\n氣流的另一個影響是安裝位置。第 115 條規定：天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；牆上設有出風口時，應距離該出風口一點五公尺以上，但該出風口距天花板在一公尺以上時不在此限；天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內；局限型探測器以裝置在探測區域中心附近為原則，其裝置不得傾斜四十五度以上，但火焰式探測器不在此限。至於探測區域，第 119 條規定係以裝置面四周淨高四十公分以上之樑或類似構造體區劃包圍者，但差動式分布型及偵煙式探測器之裝置面四周淨高應為六十公分以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-012","建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",12,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-014","對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",14,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-011","特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",11,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-015","對空氣管式之差動式分布型探測器進行空氣注入之性能檢查時，下列何種試驗無須量測探測器導通與否？",15,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-010","各型探測器在性能試驗中，下列有關其動作試驗的動作時間，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",10,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-016","建築物之避難器具設置緩降機時，對其開口部進行外觀檢查之判定，下列何者合格？",16,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-013",113,"下列緊急廣播設備之配線規定，除依用戶用電設備裝置規則外，依下列規定設置，何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-013",112,"有關避難器具設置規定，依據各類場所消防安全設備設置標準，下列何種避難器具不能裝置在使用場所之樑？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-013",111,"設有避難器具之場所，進行外觀檢查時，下列判定方法何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-013",109,"無線電通信輔助設備設置之規定，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-013",108,"有關避難器具之外觀試驗，下列何者不屬於外觀試驗？",1785129963911]