[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-011","fire-110-1-alarm-evacuation-011",110,1,11,"特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",{"A":16,"B":17,"C":18,"D":19},"排煙口開口面積 5 平方公尺","進風口開口面積 2 平方公尺","排煙管道內部斷面積 8 平方公尺","進風管道內部斷面積 2 平方公尺","B",null,[],false,"本題考點：兼用排煙室採風管方式時，排煙口、進風口與風管斷面積之綜合試驗判定。\n【正解理由】依《各類場所消防安全設備設置標準》第 189 條第二款第三目，進風口分成兩條互斥路徑：其直接面向戶外者，開口面積在一平方公尺以上、兼用時一點五平方公尺以上；或與直接連通戶外之進風風管連接，該風管並連接進風機。題幹明寫設置排煙管道及進風管道，即走後者，該分支於設置標準未訂開口面積。題示四個數值屬綜合試驗判定項目，其門檻定於《消防安全設備測試報告書測試方法及判定要領》，該文件不在候選條文之列，數值不予臆測；四者中僅進風口開口面積二平方公尺達到判定值，故選 B。\n【逐項排除】\n(A) 排煙口開口面積。第 189 條就本分支僅要求排煙口位於天花板高度二分之一以上之範圍內、與直接連通戶外之排煙風管連接並連接排煙機，未定面積；其門檻屬綜合試驗判定項目，不在候選條文內，本項未達該值。\n(B) 進風口開口面積二平方公尺，為四者中唯一達到綜合試驗判定值者，應判定合格，為本題應選者。\n(C) 排煙風管內部斷面積。條文就風管所定者為與煙接觸部分使用不燃材料、貫穿防火區劃處設防火閘門等構造要件，斷面積門檻同不在候選條文內。\n(D) 進風風管內部斷面積，與 (B) 之進風口開口面積係不同檢查項目，不可互用；門檻亦不在候選條文內。\n【記憶點】管道式看綜合試驗判定值；一點五平方公尺是進風口「直接面向戶外」分支的規定。","第 189 條把特別安全梯或緊急昇降機間排煙室之排煙設備分成兩條路：窗戶方式與風管方式，兩者數值各自獨立。窗戶方式規定排煙時窗戶與煙接觸部分使用不燃材料，窗戶有效開口面積位於天花板高度二分之一以上之範圍內，其有效開口面積在二平方公尺以上，兼用時應在三平方公尺以上；平時關閉之窗戶設手動開關裝置，操作部分設於距離樓地板面八十公分以上一百五十公分以下之牆面，並標示簡易之操作方式。風管方式規定排煙口位於天花板高度二分之一以上之範圍內，進風口位於天花板高度二分之一以下之範圍內，而進風口本身又再分兩條互斥路徑：直接面向戶外者，開口面積在一平方公尺以上、兼用時一點五平方公尺以上；或與直接連通戶外之進風風管連接，該風管並連接進風機，此一分支條文並未訂開口面積。所以一點五平方公尺是「直接面向戶外」那一支的數字，看到題目寫「管道」就不能往這裡套。同款另定排煙機、進風機之排煙量、進風量在每秒四立方公尺以上，兼用時每秒六立方公尺以上，且可隨排煙口、進風口開啟而自動啟動；排煙口、進風口、排煙機及進風機連接緊急電源，其供電容量應供其有效動作三十分鐘以上。\n設置義務面可一併記住：第 28 條第五款明定依建築技術規則應設置之特別安全梯或緊急昇降機間，應設置排煙設備；第 11 條把排煙設備（緊急昇降機間、特別安全梯間排煙設備、室內排煙設備）列為消防搶救上之必要設備，與連結送水管、消防專用蓄水池、緊急電源插座、無線電通信輔助設備、防災監控系統綜合操作裝置並列。另依第 49 條第二款，室內安全梯間、特別安全梯間或緊急昇降機間之排煙室屬得免裝撒水頭之處所。同一個空間在不同條文分別牽涉排煙設備的規格與撒水頭的免設，作答時要先看清楚問的是哪一件事。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-010","各型探測器在性能試驗中，下列有關其動作試驗的動作時間，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-012","建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-009","瓦斯漏氣火警自動警報設備之性能試驗中，下列有關串接配線試驗之測試及判定，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-013","容易受風影響之場所（如大廳、禮拜堂、大樓頂上之機械室等），依消防安全設備及必要檢修項目檢修基準之規定，可在下列何種探測器中進行選設？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-008","下列何組感知線型或分布型探測器在進行外觀試驗時，均須判定其感熱元件之極性有無誤接？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-014","對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-011",113,"某一場所設有一 A 級出口標示燈，其縱向尺度為 0.8 公尺，且未顯示避難方向符號者，請問其步行距離應為多少公尺？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-011",112,"依據火警探測器認可基準之構造及材質規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-011",111,"依各類場所消防安全設備設置標準規定，下列場所何者未強制要求設置 119 火災通報裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-011",109,"避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-011",108,"為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",1785129963901]