[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-008","fire-110-1-alarm-evacuation-008",110,1,8,"下列何組感知線型或分布型探測器在進行外觀試驗時，均須判定其感熱元件之極性有無誤接？",{"A":16,"B":17,"C":18,"D":19},"定溫式線型及空氣管式","熱電偶式及熱半導體式","定溫式線型及熱半導體式","熱電偶式及空氣管式","B",null,[],false,"本題考點：分布型探測器中，熱電偶式與熱半導體式以熱電動勢動作，感熱元件有極性，外觀試驗須判定有無誤接。\n【正解理由】依《各類場所消防安全設備設置標準》第 121 條，差動式分布型探測器分為空氣管式、熱電偶式與熱半導體式三種型式：空氣管式係以空氣管內空氣受熱膨脹推動檢出器動作，屬氣壓系統，管路本身不生正負之別；熱電偶式與熱半導體式則以感熱元件產生之熱電動勢送回檢出器，元件兩端有固定極性，接反即無法正確傳遞信號，故外觀試驗均須判定其感熱元件之極性有無誤接，故選 B。\n【逐項排除】\n(A) 定溫式線型及空氣管式：定溫式線型（感知線型）以線內可熔絕緣物受熱熔化使導體短路而動作，空氣管式為氣壓動作，二者均無感熱元件之極性可判。\n(B) 熱電偶式及熱半導體式：同屬第 121 條差動式分布型之型式，感知元件均輸出熱電動勢，皆須判定極性，為本題應選者。\n(C) 定溫式線型及熱半導體式：熱半導體式須判定極性，定溫式線型則否，組合不成立。\n(D) 熱電偶式及空氣管式：熱電偶式須判定極性，空氣管式屬氣壓式，不生極性問題，組合不成立。\n【記憶點】會產生電動勢的才有正負——熱電偶式與熱半導體式要看極性。","第 121 條把差動式分布型拆成三種型式，各有一套設置規定，也各有一套檢查重點。空氣管式：每一探測區域內之空氣管長度，露出部分在二十公尺以上；裝接於一個檢出器之空氣管長度在一百公尺以下；空氣管裝置在裝置面下方三十公分範圍內；並裝置在自裝置面任一邊起一點五公尺以內之位置，其間距在防火構造建築物為九公尺以下、其他建築物為六公尺以下（依探測區域規模及形狀能有效探測火災發生者不在此限）。由於是靠空氣受熱膨脹推動檢出器膜片動作，其檢查重點落在管路之漏氣與流通，接線無正負可言。熱電偶式：熱電偶應裝置在裝置面下方三十公分範圍內；應設個數依建築物構造分兩層——防火構造建築物在八十八平方公尺以下者至少四個，超過八十八平方公尺者應設四個並每增加二十二平方公尺（包括未滿）增設一個；其他建築物在七十二平方公尺以下者至少四個，超過七十二平方公尺者應設四個並每增加十八平方公尺（包括未滿）增設一個；裝接於一個檢出器之熱電偶數在二十個以下。熱半導體式：探測器下端裝設在裝置面下方三十公分範圍內；各探測區域依探測器種類及裝置面高度，在每一有效探測範圍至少設置二個，但裝置面高度未滿八公尺時至少設置一個。熱電偶與熱半導體都是把溫升轉成電動勢送回檢出器，元件與回路有固定極性，這正是外觀試驗要判定極性有無誤接的由來。裝置位置面另見第 115 條：天花板設有出風口時，應距該出風口一點五公尺以上，惟火焰式、差動式分布型及光電式分離型探測器列於該款除外之列；牆上設有出風口時亦為一點五公尺以上，但該出風口距天花板在一公尺以上者不在此限。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-007","下列何種火警探測器在認可作業中須進行粉塵試驗？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-009","瓦斯漏氣火警自動警報設備之性能試驗中，下列有關串接配線試驗之測試及判定，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-006","緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-010","各型探測器在性能試驗中，下列有關其動作試驗的動作時間，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-005","避難方向指示燈之認可作業中，其引導燈具不包括下列何種附加功能？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-011","特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-008",113,"某醫學中心的 7 樓在考量避難器具選設的種類中，下列避難器具不適合？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-008",112,"有關警報裝置設置場所之外觀試驗判定要領，依據瓦斯漏氣火警自動警報設備測試報告書，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-008",111,"一場所設置定溫式局限型 1 種探測器（非再用型）共有 32 個，今進行動作試驗時，應抽取 X 個探測器以加熱試驗器加熱，測定至探測器動作時間為 Y 秒內合格，則 X、Y 為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-008",109,"緊急照明燈在地面之水平面照度，使用低照度測定用光電管照度計測得之值，在地下建築物之地下通道，其地板面應在 X 勒克司（Lux）以上，其他場所應在 Y 勒克司（Lux）以上。其中 X， Y 值為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-008",108,"感熱式局限型探測器使用加熱試驗器對探測器加熱，依動作時間方法判斷，下列何者符合動作時間之規定？（標稱動作溫度與周圍溫度之差低於 50 度）",1785129963864]