[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-028","fire-109-1-water-chemical-028",109,1,28,"水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",{"A":16,"B":17,"C":18,"D":19},"65","85","95","100","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 63 條水霧滅火設備放射區域數與主管管徑的連動規定。\n【正解理由】第 63 條第一項先界定「放射區域，指一只一齊開放閥啟動放射之區域，每一區域以五十平方公尺為原則」，第二項接著規定「前項放射區域有二區域以上者，其主管管徑應在一百毫米以上」。題幹問的正是二區域以上時主管管徑的下限，條文明列一百毫米，故選 D。\n【逐項排除】\n(A) 65：第 63 條第二項只出現一百毫米這一個管徑。六十五之所以常被誤填，是因為第 32 條立管管徑規定第一種消防栓在六十三毫米以上，條號、設備與數值都與本題無關。\n(B) 85：水霧滅火設備的第 62 條至第 64 條並無八十五毫米之管徑規定，屬憑印象填入的中間值。\n(C) 95：第 63 條同樣未出現九十五毫米；候選條文中與之相近的一百毫米，見於第 32 條立管與連結送水管共用時之管徑及第 63 條第二項，兩處都是一百而非九十五。\n(D) 100：與第 63 條第二項「其主管管徑應在一百毫米以上」逐字相符，為正確答案。二區域以上代表可能同時放射，主管須承擔加倍流量。\n【記憶點】水霧記「一區五十平方公尺、二區以上主管一百毫米、水源二十變四十立方公尺」，三個數字一起背。","水霧滅火設備的放射區域是整組計算的起點。第 63 條第一項把放射區域定義為一只一齊開放閥啟動放射之區域，並以五十平方公尺為原則，第二項才接著規定二區域以上時主管管徑一百毫米以上——放大主管的理由是：兩區以上代表最不利情況下可能同時放射，主管必須承擔加倍流量，管徑不放大則摩擦損失暴增、末端放射壓力不足。水源容量的規定與此完全對應：第 64 條規定水霧滅火設備之水源容量應保持二十立方公尺以上，但放射區域在二區域以上者應保持四十立方公尺以上，同樣是一比二的關係。五十平方公尺、一百毫米、二十與四十立方公尺這三組數字建議綁在一起記，考題經常交叉抽換其中一個。另有一個高頻陷阱：第 212 條也在談水霧滅火設備，卻規定放射區域每一區域在一百五十平方公尺以上、防護對象面積未滿一百五十平方公尺者以實際面積計算、水源容量以最大放射區域全部水霧噴頭繼續放水三十分鐘、每平方公尺每分鐘放水量二十公升以上、放射壓力每平方公分三點五公斤以上或 0.35MPa 以上，且緊急電源供電容量四十五分鐘以上。那是《設置標準》第四編公共危險物品等場所的專屬規定，只適用於公共危險物品或可燃性高壓氣體場所；遇到地下停車場、百貨、辦公室等一般場所，一律回到第二編、第三編，兩套數值不得互套，看到「一百五十平方公尺」就要先確認題幹場所屬於哪一編。至於水霧設備其他配管相關規定的來源，第 62 條把緊急電源、配管、配件、屋頂水箱、竣工時之加壓送水試驗、流水檢知裝置、啟動裝置及一齊開放閥準用第三十八條、第四十四條、第四十五條與第五十一條至第五十三條，因此讀水霧設備必須連著自動撒水設備一起讀。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-027","中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-029","泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-026","密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-030","泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-025","高架倉庫內所設置之撒水頭，其放水量每分鐘應在多少公升以上？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-031","使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-028",113,"下列場所之消防安全設備設置何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-028",112,"有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-028",111,"依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-028",110,"消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-028",108,"依法令規定在應設水霧、泡沫、乾粉、二氧化碳滅火設備之場所，但外牆開口面積（常時開放部分）達該層樓地板面積百分之多少以上者，上列滅火設備得採移動式設置？",1785129972751]