[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-026","fire-109-1-water-chemical-026",109,1,26,"密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"距地板面高度 2.1 公尺以上","管徑在 25 毫米以上","附排水管裝置","配置於最遠支管末端","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 56 條密閉式撒水頭末端查驗閥的四款要件，題目要挑出敘述錯誤者。\n【正解理由】第 56 條第四款規定「距離地板面之高度在二點一公尺以下，並附有排水管裝置，並標明末端查驗閥字樣」，二點一公尺是高度上限。選項 (A) 把「以下」寫成「以上」，方向完全相反，即為錯誤敘述，故選 A。\n【逐項排除】\n(A) 距地板面高度 2.1 公尺以上：與第 56 條第四款「在二點一公尺以下」相牴觸。查驗閥須由人員在地面即可開啟放水，條文限制的是它不得裝得太高，為本題應選者。\n(B) 管徑在 25 毫米以上：與第 56 條第一款「管徑在二十五毫米以上」相符，敘述正確，管徑過小會使查驗管本身成為節流點。\n(C) 附排水管裝置：第四款後段明定應附有排水管裝置並標明字樣，敘述正確。\n(D) 配置於最遠支管末端：第二款規定查驗閥依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端，敘述正確。\n【記憶點】末端查驗閥四要件：管徑 25 毫米、接最遠支管末端、一次側壓力表配二次側限流孔、離地二點一公尺以「下」。","末端查驗閥的每一項要件，都能從「它要模擬什麼」推得出來。它模擬的是全系統條件最差的那一個撒水頭：第 56 條第二款要求接在各層放水壓力最低之最遠支管末端，因為配管摩擦損失在最遠端最大，該點壓力若合格，其餘位置必然更寬裕；第三款要求一次側設壓力表、二次側設有與撒水頭同等放水性能之限流孔，限流孔等於一個「假撒水頭」，讓測試時的流量與真正動作時相當，量到的壓力才有意義；第一款的二十五毫米管徑，是避免查驗管自身造成額外壓損；第四款把高度壓在二點一公尺以下並要求附排水管與標示，則是讓檢查人員在地面即可操作，放出來的水也有去處。合格壓力的上下限並非憑空而來：第 50 條第一項規定撒水頭放水壓力應在每平方公分一公斤以上或 0.1MPa 以上，第 58 條第二項規定加壓送水裝置之撒水頭放水壓力應在每平方公分十公斤以下或 1MPa 以下，一下一上夾出區間。這也正是《各類場所消防安全設備檢修及申報作業基準》自動撒水設備之綜合檢查，在密閉式撒水設備項下要求切換成緊急電源供電後打開末端查驗閥，並對距加壓送水裝置最近與最遠之末端查驗閥分別進行放水試驗的道理——測兩端才能同時驗證最不利點與最有利點都落在區間內。另一組易混淆規定在第 211 條：該條屬第四編公共危險物品等場所，雖然把末端查驗閥準用第 56 條，但水源容量改為設置三十個撒水頭繼續放水三十分鐘以上，且使用密閉乾式或預動式流水檢知裝置時撒水頭數還要追加十個，與一般場所第 57 條的表列個數、二十分鐘放水時間完全不同，兩編數值不得互套。命題方式也很固定：不是把「以下」換成「以上」考方向，就是把二十五毫米換成其他管徑，或把「最遠支管末端」改寫成「最近支管末端」考位置，四款要件只要能講出理由，就不必硬背文字。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-025","高架倉庫內所設置之撒水頭，其放水量每分鐘應在多少公升以上？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-027","中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-024","室外消防栓設備之水帶箱設置，箱內應配置口徑 63 毫米及長多少公尺之水帶 2 條？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-028","水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-023","下列有關室內消防栓箱之敘述，何者正確？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-029","泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-026",113,"設於外浮頂式儲槽之泡沫放出口為？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-026",112,"依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-026",111,"壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-026",110,"固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-026",108,"依各類場所消防安全設備設置標準之規定，建築物高度超過 60 公尺者，連結送水管應採用濕式，其中繼幫浦設置規定之敘述何者錯誤？",1785129972735]