[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-022":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-022","fire-109-1-water-chemical-022",109,1,22,"室內消防栓之箱面字樣，每字不得小於多少平方公分？",{"A":16,"B":17,"C":18,"D":19},"15","20","25","30","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 35 條室內消防栓箱之箱面字樣大小下限。\n【正解理由】依《各類場所消防安全設備設置標準》第 35 條第三款，室內消防栓箱應「箱面有明顯而不易脫落之消防栓字樣，每字在二十平方公分以上」。題目問「每字不得小於多少平方公分」，即該款所定之下限二十平方公分，故選 B。\n【逐項排除】\n(A) 15 平方公分低於第 35 條所定之下限，字體過小將不符「明顯」之要求，屬不合格。\n(B) 20 平方公分與條文「每字在二十平方公分以上」完全一致，為應選者。\n(C) 25 平方公分並非本款數值，易與第 191 條緊急電源插座保護箱長邊二十五公分以上之尺寸規定混淆。\n(D) 30 平方公分同樣未見於條文，屬加碼推測；標示規定為「以上」的下限值，記憶時不可自行放大。\n【記憶點】消防標示字樣「每字 20 平方公分以上」是通則，僅緊急電源插座保護箱蓋為每字 2 平方公分以上。","「每字二十平方公分以上」是《各類場所消防安全設備設置標準》橫跨多條的通用標示規格，可整批記憶：第 35 條室內消防栓箱之消防栓字樣、第 40 條第四款室外消防栓水帶箱之水帶箱字樣、第 180 條第二款連結送水管出水口箱之出水口字樣、第 182 條十一層以上樓層水帶箱之水帶箱字樣，皆為每字在二十平方公分以上。唯一的明顯例外是第 191 條緊急電源插座保護箱蓋之緊急電源插座字樣，每字在二平方公分以上——因為保護箱長短邊僅二十五公分及二十公分以上，箱體本身就小。差一個數量級，正是命題最愛的對照組。\n連帶把箱體規格一併整理：室內消防栓箱箱身為厚度一點六毫米以上之鋼板或具同等性能以上之不燃材料，箱面表面積在零點七平方公尺以上（第 35 條）；室外消防栓水帶箱箱面表面積在零點八平方公尺以上，且箱底二側設排水孔（第 40 條）；連結送水管出水口箱為厚度一點六毫米以上鋼板，箱面短邊四十公分以上、長邊五十公分以上（第 180 條）；十一層以上樓層之水帶箱表面積零點八平方公尺以上、材質為厚度一點六毫米以上鋼板（第 182 條）；緊急電源插座保護箱亦為厚度一點六毫米以上鋼板，須接地、箱蓋為易於開閉之構造，與室內消防栓箱等併設時須設於上方且箱蓋須能另外開啟（第 191 條）。\n記憶法：鋼板厚度一律 1.6 毫米、標示字樣一律 20 平方公分（緊急電源插座 2 平方公分例外）、箱面表面積室內 0.7、室外與十一層以上水帶箱 0.8。把「厚度、面積、字樣」三個維度排成表，數值題就不會互相串線。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-021","室內消防栓中之減水警報裝置，應於水量減至多少時發出警報？",21,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-023","下列有關室內消防栓箱之敘述，何者正確？",23,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-020","用於防護電氣設施之水霧滅火設備進行放水試驗時，最末端放射區域全部水霧噴頭之放水壓力均應能達到多少壓力以上？",20,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-024","室外消防栓設備之水帶箱設置，箱內應配置口徑 63 毫米及長多少公尺之水帶 2 條？",24,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-019","某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",19,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-025","高架倉庫內所設置之撒水頭，其放水量每分鐘應在多少公升以上？",25,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-022",113,"下列場所何者得設置水霧滅火設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-022",112,"依各類場所消防安全設備設置標準規定，一般場所設置滅火器，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-022",111,"有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-022",110,"同一建築基地內有二棟以上建築物時，建築物間外牆與中心線水平距離第一層在 X 公尺以下，第二層在 Y 公尺以下，且合計各棟該第一層及第二層樓地板面積在 Z 平方公尺以上者，應設置消防專用蓄水池。X、Y、Z 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-022",108,"有關潔淨藥劑氣體滅火設備滅火藥劑主要成分之敘述，下列何者正確？",1785129972711]