[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-016","fire-109-1-water-chemical-016",109,1,16,"製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",{"A":16,"B":17,"C":18,"D":19},"3 分鐘","5 分鐘","7 分鐘","10 分鐘","B",null,[],false,"本題考點：室內消防栓水帶製造年份超過 10 年時之耐水壓試驗，其試驗壓力與加壓時間。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》室內消防栓設備性能檢查之消防栓箱等，第一種消防栓水帶「製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機……施以 7kgf\u002Fcm2 以上水壓試驗 5 分鐘合格，始得繼續使用。但已經水壓試驗合格未達 3 年者，不在此限」。原文所定之加壓時間為 5 分鐘，故選 B。\n【逐項排除】\n(A) 3 分鐘：原文中的「3」是但書「已經水壓試驗合格未達 3 年」之年限，屬免試期間而非加壓時間。\n(B) 5 分鐘與原文「水壓試驗 5 分鐘合格」一致，為應選者。\n(C) 7 分鐘：7 是試驗壓力 7kgf\u002Fcm² 的數值，把壓力值誤植為時間是本題主要陷阱。\n(D) 10 分鐘：10 是題幹「製造年份超過 10 年」的年數門檻，用以決定要不要做這項試驗，不是試驗時間。\n【記憶點】水帶耐壓「7 壓 5 分鐘」，滿 10 年才要試、合格未滿 3 年免再試。","水帶耐水壓試驗的壓力值會隨設備章別不同，這是本考點最容易失分之處。依《各類場所消防安全設備檢修及申報作業基準》，室內消防栓設備、連結送水管之水帶箱等、泡沫滅火設備之泡沫消防栓箱等，均為施以 7kgf\u002Fcm2 以上水壓試驗 5 分鐘合格；而室外消防栓設備之室外消防栓箱等與射水設備之室外消防栓箱等，則為施以 6kgf\u002Fcm2 以上水壓試驗 5 分鐘合格。整理成「室內系 7、室外系 6，時間一律 5 分鐘」即可一次記住四個章別。四者的但書相同：已經水壓試驗合格未達 3 年者，不在此限。\n此一設計的邏輯是水帶橡膠內襯與織布會隨使用與存放年限老化，10 年是啟動定期耐壓驗證的門檻，3 年則是驗證後的有效期間，避免每年重複破壞性試驗。判定方法為應無損傷、腐蝕，且應能容易拆接，水帶應無破裂、漏水或與消防水帶用接頭脫落之情形。\n易混淆對照一：第一種消防栓與第二種消防栓的檢查方法不同。第一種消防栓需目視確認腐蝕損傷、確認是否容易拆接，並做上述耐水壓試驗；第二種消防栓則是以目視確認有無腐蝕、損傷及瞄子開閉裝置操作是否容易，判定為開關裝置應能容易操作，並無水帶耐壓試驗。\n易混淆對照二：竣工試驗與檢修試驗。《各類場所消防安全設備設置標準》第 33 條規定，室內消防栓設備之消防立管管系竣工時應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓，並以繼續維持二小時無漏水現象為合格。前者測的是配管、時間二小時；後者測的是水帶、時間五分鐘，數字與對象皆不同。單位換算：7 kgf\u002Fcm² ≈ 0.7 MPa ≈ 70 公尺水頭。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-015","公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-017","某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-014","測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-018","移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-013","乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-019","某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-016",113,"有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-016",112,"有關二氧化碳滅火設備構件之安全措施規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-016",111,"乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-016",110,"某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-016",108,"依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",1785129972670]