[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-015","fire-109-1-water-chemical-015",109,1,15,"公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",{"A":16,"B":17,"C":18,"D":19},"1.7 kgf\u002Fcm²","2.5 kgf\u002Fcm²","2.7 kgf\u002Fcm²","3.5 kgf\u002Fcm²","D",null,[],false,"本題考點：公共危險物品等場所射水設備綜合檢查之放水壓力判定值。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》射水設備之綜合檢查，其檢查方法為以全部射水設備（超過二具時選最遠最高處之二具）做放水試驗，將壓力表進水口置於瞄子前端口徑二分之一距離處讀值，判定方法明定「放水壓力應在 3.5kgf\u002Fcm2 以上」，放水量每具應在 450l\u002Fmin 以上。射水設備係為公共危險物品、可燃性高壓氣體等高危險場所而設，壓力門檻高於一般場所之水系統，故選 D。\n【逐項排除】\n(A) 1.7 kgf\u002Fcm² 未達判定值，實測若為此值即應判不合格，該數值屬室內消防栓瞄子放水壓力的常見下限，非射水設備。\n(B) 2.5 kgf\u002Fcm² 是室外消防栓綜合檢查放水壓力的一般下限（判定為 2.5 至 6 kgf\u002Fcm²），亦為《設置標準》第 40 條室外消防栓瞄子出水壓力值，設備別不同。\n(C) 2.7 kgf\u002Fcm² 是《設置標準》第 65 條水霧滅火設備防護一般對象之出水壓力，與射水設備無涉。\n(D) 與射水設備綜合檢查判定方法所載「3.5kgf\u002Fcm2 以上」逐字相符，為應選者。\n【記憶點】射水設備壓力 3.5、水量 450，比室外消防栓的 2.5／350 各高一級。","射水設備是專為公共危險物品場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽等高風險場所設計的水系統，特色是「壓力高、水量大、可遠距射水」，因此檢修判定值明顯高於一般場所。設置端可對照《各類場所消防安全設備設置標準》第 231 條（屬第四編公共危險物品等場所）：室外消防栓應設置於屋外且具備消防水帶箱，箱內配置瞄子、開關把手及口徑六十三毫米、長度二十公尺消防水帶二條；全部射水設備同時使用時，各射水設備放水壓力在每平方公分三點五公斤以上或 0.35MPa 以上，放水量在每分鐘四百五十公升以上，但全部射水設備數量超過二支時以同時使用二支計算；水源容量在二具射水設備同時放水三十分鐘之水量以上。可見設置端與檢修端數值完全同步，這是命題者最愛的「設置—檢修對照」考法。\n同屬公共危險物品室外儲槽場所的冷卻撒水設備，其綜合檢查判定另有一組數值：實際測得放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在 2 l\u002Fmin m2 以上；可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽場所則為 5 l\u002Fmin m2 以上，若以厚度 25mm 以上岩棉等隔熱材被覆並以鋅鐵板等被覆者，為 2.5 l\u002Fmin m2 以上。兩套設備常被混題並列，須以「防護對象是槽壁面積或防護面積」區辨。\n單位換算：3.5 kgf\u002Fcm² ≈ 0.35 MPa ≈ 35 公尺水頭。放水壓力數值鏈記憶：室內消防栓第一種 1.7、室外消防栓 2.5、水霧防護一般對象 2.7、水霧防護電氣設備與射水設備 3.5。延伸考點：室外消防栓在公共危險物品等場所達顯著滅火困難者、爆竹煙火場所時，其綜合檢查放水壓力亦提高至 3.5 kgf\u002Fcm² 以上、放水量 450 l\u002Fmin 以上，與射水設備同級，可一併記憶。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-014","測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-016","製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-013","乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-017","某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-012","消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-018","移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-015",113,"有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-015",112,"有關滅火設備之緊急電源供電容量規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-015",111,"採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-015",110,"公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-015",108,"依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",1785129972666]