[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-013":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-013","fire-109-1-water-chemical-013",109,1,13,"乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",{"A":16,"B":17,"C":18,"D":19},"0.27 公升","0.45 公升","1.85 公升","4.87 公升","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 110 條第二款，乾粉滅火設備啟動用氣體容器之內容積下限。\n【正解理由】乾粉滅火設備使用氣體啟動者，第 110 條第二款明定「啟動用氣體容器之內容積有零點二七公升以上，其所儲存之氣體量在一百四十五公克以上，且其充填比在一點五以上」。同條第一款另要求容器能耐每平方公分二百五十公斤（25MPa）之壓力，第四款規定該容器不得兼供防護區域之自動關閉裝置使用。與二氧化碳滅火設備第 88 條第二款所定「內容積應有一公升以上、所儲存之二氧化碳重量在零點六公斤以上」相比，乾粉之啟動用氣體容器明顯較小。條文所定內容積下限即 0.27 公升，故選 A。\n【逐項排除】\n(A) 0.27 公升與第 110 條第二款完全相符，為正解。\n(B) 0.45 公升非本條所定之值，屬把 0.27 憑印象放大之誘答。\n(C) 1.85 公升同樣未見於本條，數值明顯偏大。\n(D) 4.87 公升與規定相去更遠，本條並無此數值。\n【記憶點】乾粉啟動用氣體容器：0.27 公升、145 公克、充填比 1.5 以上。","啟動用氣體容器屬於啟動系統而非滅火藥劑本身，功能是以高壓氣體推動容器閥開放裝置與選擇閥。乾粉與二氧化碳兩套規格必須分開記：第 110 條乾粉為內容積零點二七公升以上、氣體量一百四十五公克以上、充填比一點五以上；第 88 條二氧化碳為內容積一公升以上、二氧化碳重量零點六公斤以上、充填比一點五以上。兩條的共通點是容器均須能耐每平方公分二百五十公斤（25MPa）之壓力、安全裝置及容器閥符合 CNS 一一一七六規定，且不得兼供防護區域之自動關閉裝置使用；後者是為避免啟動氣體被分流，導致自動關閉裝置與容器閥都動作不確實。\n充填比＝容器內容積（公升）÷ 所充填氣體重量（公斤），值愈小代表灌得愈滿。以乾粉為例，0.27 ÷ 0.145 ≈ 1.86，確實在一點五以上；二氧化碳為 1 ÷ 0.6 ≈ 1.67，同樣符合。規定充填比下限，用意是保留氣相空間，避免溫度上升時液面膨脹造成容器超壓。\n乾粉系統其他常考數值可一併整理：第 100 條乾粉噴頭放射壓力在每平方公分一公斤（0.1MPa）以上，且所核算之滅火藥劑量須於三十秒內放射完畢；第 105 條配管最低與最高配管間落差在五十公尺以下，蓄壓式壓力在每平方公分二十五公斤以上、四十二公斤以下者，應使用符合 CNS 四六二六之無縫鋼管管號 Sch40 以上厚度；第 106 條自儲存容器起，配管任一部分與彎曲部分之距離應為管徑二十倍以上，以免乾粉藥劑與加壓或蓄壓用氣體分離；第 109 條蓄壓式應設置以綠色表示使用壓力範圍之指示壓力表。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-012","消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",12,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-014","測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",14,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-011","乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",11,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-015","公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",15,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-010","全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",10,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-016","製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",16,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-013",113,"水道連結型自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-013",112,"依據各類場所消防安全設備設置標準規定，加氣站之滅火器設置，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-013",111,"有關自動撒水設備末端查驗閥之敘述，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-013",110,"使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-013",108,"依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",1785129972654]