[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-010","fire-109-1-water-chemical-010",109,1,10,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",{"A":16,"B":17,"C":18,"D":19},"20 秒","30 秒","60 秒","90 秒","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 93 條第一款，全區放射方式二氧化碳滅火設備之遲延裝置時間。\n【正解理由】第 93 條第一款明定，全區放射方式之安全裝置應自「啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有二十秒以上之遲延裝置」。二氧化碳靠稀釋氧濃度滅火，濃度一旦建立即對人體構成窒息危險，遲延的用意是給防護區域內人員撤離的時間，並讓第 92 條之音響警報先行報知；同條第二款另要求於防護區域出入口等易於辨認處所設置放射表示燈。條文所定為二十秒以上，故選 A。\n【逐項排除】\n(A) 20 秒與條文「二十秒以上」相符，為正解。\n(B) 30 秒是第 84 條第五款局部放射方式藥劑量須放射完畢之時間，並非遲延裝置之法定值。\n(C) 60 秒即一分，是第 84 條第三款「其他」場所之全區放射完畢時間，同樣不是遲延時間。\n(D) 90 秒未見於本設備各條，且遲延過久將延誤滅火時機，不符條文。\n【記憶點】遲延「二十秒以上」＋放射表示燈，是全區放射的兩道安全裝置。","二氧化碳全區放射的安全設計是一組連鎖。第 92 條音響警報裝置規定：手動或自動裝置動作後應自動發出警報，且藥劑未全部放射前不得中斷；音響警報應有效報知防護區域或防護對象內所有人員；設於全區放射方式者採用人語發音，但平時無人駐守者不在此限。第 93 條接手，要求啟動至容器閥開啟間設二十秒以上之遲延，並於出入口等易於辨認處所設放射表示燈。前者叫人走，後者給時間走，並警告外面的人不要進入。\n與這組安全裝置配套的是開口部管制。第 86 條規定全區放射方式防護區域之開口部不得設於面對安全梯間、特別安全梯間、緊急昇降機間或其他類似場所；位於距樓地板面高度三分之二以下部分之開口部，應在滅火藥劑放射前自動關閉；不設自動關閉裝置之開口部總面積，供電信機械室使用時應在圍壁面積百分之一以下，其他處所則在防護區域體積值或圍壁面積值二者中較小數值之百分之十以下。所稱圍壁面積，指防護區域內牆壁、樓地板及天花板等面積之合計。\n放射方式之分類見第 82 條：全區放射須以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，且開口部設有自動關閉裝置，但能有效補充開口部洩漏量者得免設；局部放射視防護對象之形狀、構造、數量及性質配置噴頭；移動放射方式則要求皮管接頭至防護對象任一部分之水平距離在十五公尺以下。時間數值可以一次背齊：遲延二十秒以上、局部放射三十秒內放射完畢、全區其他場所一分鐘、電信機械室與總機室三點五分；再加上第 95 條緊急電源須能有效動作一小時以上，整套氣體系統的時間軸就完整了。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-009","進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-011","乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-008","預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-012","消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-007","下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-013","乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-010",113,"有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-010",112,"水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-010",111,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-010",110,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-010",108,"有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",1785129972621]