[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-005","fire-109-1-water-chemical-005",109,1,5,"某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",{"A":16,"B":17,"C":18,"D":19},"60 秒","180 秒","210 秒","300 秒","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 84 條第三款，全區放射方式二氧化碳滅火設備依場所別所定之藥劑放射完畢時間。\n【正解理由】第 84 條第三款明定，全區放射方式依第 83 條第一款所核算之滅火藥劑量，應「依下表所列場所，於規定時間內全部放射完畢」，該表僅分兩欄：電信機械室、總機室為 3.5 分，其他場所為 1 分。電信機械室單獨列一欄，是因第 83 條表中該場所每立方公尺所需藥劑量達 1.2 公斤、開口部追加量 10 公斤／平方公尺，均為表中最高，屬以較長時間浸潤、抑制電氣設備深層火災之設計。3.5 分×60 秒／分＝210 秒，故選 C。\n【逐項排除】\n(A) 60 秒即 1 分，是表中「其他」場所欄之放射時間，用於一般防護區域，套用於電信機械室會短於規定時間。\n(B) 180 秒即 3 分，表列並無此格，是把 3.5 分誤記為 3 分之典型誘答。\n(C) 210 秒即 3.5 分，與表列電信機械室、總機室之規定時間逐字相符，為正解。\n(D) 300 秒即 5 分，同樣非表列數值，與第 84 條第五款局部放射方式須於 30 秒內放射完畢之體例亦明顯不合。\n【記憶點】全區放射：電信機械室、總機室三分半（210 秒），其他場所一分鐘。","第 83 條第一款的全區放射藥劑量表，把場所分成「電信機械室、總機室」與「其他」兩大類：前者每立方公尺一點二公斤、開口部每平方公尺追加十公斤；後者依防護區域體積分為五十立方公尺未滿一點○、五十以上一百五十未滿零點九、一百五十以上一千五百未滿零點八、一千五百以上零點七五公斤／立方公尺，開口部一律追加五公斤／平方公尺，並分別定有五十、一百三十五、一千二百公斤之基本需要量。第 84 條第三款的放射時間表正與這張藥劑量表配套：電信機械室單位藥劑量最高，若比照其他場所一分鐘放完，瞬間流量與配管口徑都會失衡，故放寬到三點五分。\n第 86 條第三款從另一端把關：不設自動關閉裝置之開口部總面積，供電信機械室使用時應在圍壁面積百分之一以下，其他處所則在防護區域體積值或圍壁面積值二者中較小數值之百分之十以下；所稱圍壁面積指防護區域內牆壁、樓地板及天花板等面積之合計。電信機械室門檻嚴格十倍，理由同樣是它採較長時間放射，濃度不能因洩漏而掉下來。\n數值可整組對照記憶：第 84 條第二款放射壓力，常溫儲存之高壓式為每平方公分十四公斤（1.4MPa）以上，儲存於攝氏零下十八度以下之低壓式為每平方公分九公斤（0.9MPa）以上；第 84 條第五款局部放射方式，藥劑量須於三十秒內放射完畢；第 93 條第一款要求啟動裝置動作至容器閥開啟設二十秒以上之遲延裝置。時間軸串起來即「遲延二十秒 → 全區電信機械室二百一十秒／其他六十秒、局部三十秒」。第 82 條的移動放射方式則另定皮管接頭至防護對象任一部分之水平距離在十五公尺以下，是同一組條文的另一個常考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-004","供集會堂使用之舞臺，應設置何種自動撒水設備？",4,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-006","消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",6,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-003","某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",3,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-007","下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",7,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-002","某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",2,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-008","預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",8,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-005",113,"廚房設置簡易自動滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-005",112,"有關補助撒水栓與第二種室內消防栓之比較，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-005",111,"有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-005",110,"消防幫浦加壓送水裝置之啟動用水壓開關裝置，下列規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-005",108,"開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",1785129972595]