[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-109-1-water-chemical-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-004","fire-109-1-water-chemical-004",109,1,4,"供集會堂使用之舞臺，應設置何種自動撒水設備？",{"A":16,"B":17,"C":18,"D":19},"密閉濕式自動撒水設備","密閉乾式自動撒水設備","開放式自動撒水設備","預動式自動撒水設備","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 43 條但書，舞臺應設開放式自動撒水設備的強制規定。\n【正解理由】第 43 條本文雖允許自動撒水設備「得依實際情況需要就下列各款擇一設置」，但其但書明定「供第十二條第一款第一目所列場所及第二目之集會堂使用之舞臺，應設開放式」。集會堂正列於第 12 條第一款第二目，題示又限定為該場所之舞臺，完全該當但書要件，設置型式不得自由選擇，只能是開放式。故選 C。\n【逐項排除】\n(A) 密閉濕式為第 43 條第一款，平時管內貯滿高壓水、撒水頭動作時即撒水，是一般場所最常見的型式，但舞臺已被但書排除，不得採用。\n(B) 密閉乾式為第二款，平時管內貯滿高壓空氣，撒水頭動作時先排空氣繼而撒水，適用於配管有結凍之虞的處所，並非但書所指定的型式。\n(C) 正確。開放式為第三款，平時管內無水，火災時啟動一齊開放閥使水流入管系撒水，整個放水區域同時放水；舞臺懸掛布幕、道具與燈具，起火後沿垂直可燃物向上延燒極快，須一齊放水才能有效控制，故立法強制。\n(D) 預動式為第四款，平時管內貯滿低壓空氣，須以感知裝置啟動流水檢知裝置且撒水頭動作才撒水，設計目的在避免誤動作造成水損，與舞臺所需的一齊放水方向相反。\n【記憶點】第 12 條第一款第一目所列場所與集會堂的舞臺，撒水設備沒得挑，一律開放式。","第 43 條的結構是原則得選擇、例外強制：本文允許在密閉濕式、密閉乾式、開放式、預動式及其他經中央主管機關認可者之中擇一設置，但書則把第 12 條第一款第一目所列場所，也就是電影片映演場所、歌廳、舞廳、夜總會、俱樂部、理容院、指壓按摩場所、錄影節目帶播映場所、視聽歌唱場所、酒家、酒吧、酒店等，以及第二目集會堂使用之舞臺抽出來，一律要求開放式。理由在於舞臺上方懸吊大量布幕、道具與燈具，起火後沿垂直可燃物迅速向上延燒，密閉式撒水頭逐顆感熱動作的速度追不上火勢蔓延，必須以一齊開放閥讓整個放水區域同時放水。\n配套規定要一起記：第 53 條要求一齊開放閥每一放水區域設置一個，二次側配管裝設試驗用裝置，使在該放水區域不放水的情形下也能測試其動作，且一齊開放閥所承受之壓力在其最高使用壓力以下；第 54 條規定每一舞臺之放水區域在四個以下，放水區域在二個以上時，每一放水區域樓地板面積在一百平方公尺以上，且鄰接之放水區域必須相互重疊，以免留下未被涵蓋的空白。\n四種型式的取捨邏輯可以這樣對照：密閉濕式反應最快但配管有結凍與誤動作水損之虞；密閉乾式二次側充高壓空氣，動作後先排氣再撒水，故第 55 條要求空氣壓縮機為專用並能在三十分鐘內加壓達二次側配管設定壓力值、撒水頭動作後流水檢知裝置應在一分鐘內使撒水頭放水、撒水頭並使用向上型，二次側減壓警報則設於平時有人處；預動式再多一道感知裝置把關，適合怕水損的場所。\n最易混淆之處在放水區域面積：第 211 條屬第四編公共危險物品等場所專用，其開放式撒水設備每一放水區域樓地板面積在一百五十平方公尺以上，但防護對象樓地板面積未滿一百五十平方公尺時以實際樓地板面積計算，與一般場所第 54 條的一百平方公尺分屬兩套規定，不得互相套用。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-003","某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-005","某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-002","某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-006","消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-109-1-water-chemical-001","下列場所何者未達依法應設置滅火器之條件？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-109-1-water-chemical-007","下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-water-chemical-004",114,"依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",{"webId":57,"year":58,"stem":59,"number":13},"fire-113-1-water-chemical-004",113,"有關連結送水管設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":61,"year":62,"stem":63,"number":13},"fire-112-1-water-chemical-004",112,"依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",{"webId":65,"year":66,"stem":67,"number":13},"fire-111-1-water-chemical-004",111,"裝置於舞臺之開放式自動撒水設備，依規定下列何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-110-1-water-chemical-004",110,"下列有關室內消防栓設備之規定，何者錯誤？",1785129972590]