[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-fire-law-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-消防法規概要-029","fire-109-1-fire-law-029",109,1,29,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，全閉揚程應為性能曲線上全揚程之多少以下？",{"A":16,"B":17,"C":18,"D":19},"65%","110%","140%","150%","C",null,[],false,"本題考點：《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》所定幫浦性能，其中全閉揚程對性能曲線上全揚程之比值上限。\n【正解理由】該基準之授權依據為《各類場所消防安全設備設置標準》第 234 條，室內消防栓、自動撒水、水霧滅火、泡沫滅火及連結送水管等設備之消防幫浦、電動機、附屬裝置及配管摩擦損失計算，由中央消防機關另定之。依該基準幫浦性能一節，全閉揚程（出水量為零時之揚程）應在性能曲線上全揚程之百分之一百四十以下，用以抑制關閉出水閥時之壓力上衝，故選 C。\n【逐項排除】\n(A) 65%：百分之六十五是性能曲線另一端的下限要求，用於大出水量時全揚程不得衰減過多，方向與本題所問之上限相反。\n(B) 110%：並非該基準就全閉揚程所定之比值；若以此為限，一般離心式消防幫浦幾乎都會被判不合格，與性能曲線之實態不符。\n(C) 140%：與該基準「全閉揚程應為性能曲線上全揚程之百分之一百四十以下」相符，為本題應選者。\n(D) 150%：屬性能試驗取樣時所採的出水量倍數，是流量側的條件，不是揚程比值。\n【記憶點】性能曲線兩端各有一把尺：全閉揚程管上限、大流量時全揚程管下限。","限制全閉揚程的用意在保護下游管路。幫浦在出水量為零時揚程最高，性能曲線若過陡，關斷壓力會把配管、閥件與末端出水口撐在異常高壓下，因此基準以額定出水量時之全揚程為基準值，限制全閉點不得超過其百分之一百四十。《設置標準》裡也看得到同一套壓力上限思維的末端呈現：第 58 條第 2 項要求自動撒水設備之撒水頭放水壓力應在每平方公分十公斤或 1MPa 以下；第 37 條第 2 項第 4 款要求室內消防栓瞄子放水壓力超過每平方公分七公斤時應採取有效之減壓措施；第 42 條則對室外消防栓定為每平方公分六公斤或 0.6MPa。第 183 條更直接用到全閉揚程概念：連結送水管之中繼幫浦，其全閉揚程與押入揚程合計在一百七十公尺以上時，應增設幫浦使串聯運轉。\n全揚程本身的計算式各設備不同，末項常數即該設備要求之放水壓力換算水頭，最好整理成表一起背：室內消防栓依第 37 條為 H＝h1＋h2＋h3＋17m，壓力水箱必要壓力加 1.7 kgf／cm²；室外消防栓依第 42 條加 25m，必要壓力加 2.5 kgf／cm²，幫浦出水量一支在每分鐘四百公升以上；自動撒水設備依第 58 條為 H＝h1＋h2＋10m，必要壓力加 1 kgf／cm²；連結送水管中繼幫浦依第 183 條加 60m，出水量每分鐘二千四百公升以上；消防專用蓄水池依第 186 條加 15m，並依水量四十立方公尺未滿、四十以上一百二十未滿、一百二十以上分別對應出水量一千一百、二千二百、三千三百公升／分鐘與一、二、三個採水口。\n跨設備適用性也是考點：《防火牆及防火水幕設置基準》第 11 點明定防火水幕設備之緊急電源、幫浦加壓送水裝置及配管摩擦損失，本基準未規定者準用「緊急電源容量計算基準」及本計算基準，可見它是共同底層規範。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-fire-law-028","依各類場所消防安全設備設置標準，有關裝設瓦斯漏氣火警自動警報設備之規定，下列敘述何者錯誤？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-fire-law-030","依各類場所消防安全設備檢修及申報作業基準，有關避難器具外觀檢查之規定，緩降機下降空間之判定，在無其他突出物干擾的情境下，以器具中心半徑多少公分的圓柱形範圍內，為緩降機的下降空間？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-fire-law-027","有一 500 平方公尺地下停車場，採水霧滅火設備，依各類場所消防安全設備設置標準，其水源容量應保持多少立方公尺以上？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-fire-law-031","依各類場所消防安全設備設置標準，有關泡沫原液儲存量、泡沫原液與水混合使用濃度之規定，下列敘述何者正確？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-fire-law-026","原有照護思覺失調患者的康復之家想增設自動滅火設備，如採用小區劃型撒水頭（以第一種感度為限），依各類場所消防安全設備設置標準，其撒水頭間距要在多少公尺以上？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-fire-law-032","依各類場所消防安全設備檢修及申報作業基準，有關滅火器外觀檢查之規定，滅火器本體上端與樓地板面之距離，18 公斤以上者不得超過 a 公尺，未滿 18 公斤者不得超過 b 公尺。a、b 值各為下列何者？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-029",114,"依各類場所消防安全設備設置標準規定，下列何處所得免設排煙設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-029",113,"有關消防安全設備檢修申報之相關規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-029",112,"依消防安全設備及必要檢修項目檢修基準之規定，使用加瓦斯試驗器對瓦斯漏氣火警自動警報設備的檢知器進行加瓦斯測試，若某一回路之檢知器數量為 24 個，有關該回路應選取之檢知器檢查數量，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-029",111,"依各類場所消防安全設備設置標準規定，下列何場所之樓地板面積合計未達 1 千平方公尺，得設置水道連結型自動撒水設備或與現行法令同等以上效能之滅火設備？①產後護理之家 ②團體家屋 ③精神護理之家 ④兒童及少年福利機構",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-029",110,"有一室外儲槽，其容量為 9000 公秉，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，設有防火水幕，下列敘述何者正確？",1785129970065]