[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-029","fire-109-1-alarm-evacuation-029",109,1,29,"有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"A":16,"B":17,"C":18,"D":19},"一回路之檢知器數量 6～10 個，撰取檢查數量 2 個","一回路之檢知器數量 16～20 個，撰取檢查數量 4 個","一回路之檢知器數量 26～30 個，撰取檢查數量 6 個","一回路之檢知器數量 30 個以上，撰取檢查數量 15%","D",null,[],false,"本題考點：《各類場所消防安全設備檢修及申報作業基準》瓦斯漏氣火警自動警報設備檢知器之選取檢查數量表。\n【正解理由】依該基準瓦斯漏氣火警自動警報設備檢知器之檢查規定，檢知器應按檢知器選取檢查數量表選取檢查數量，表列各級距為：一回路之檢知器數量 1～5 個選取 1 個、6～10 個選取 2 個、11～15 個選取 3 個、16～20 個選取 4 個、21～25 個選取 5 個、26～30 個選取 6 個、30 個以上選取 20%。表列最末一級為 20% 而非 15%。選項 D 將 30 個以上之選取比例寫成 15%，與表列不同，故選 D。\n【逐項排除】\n(A) 6～10 個對應選取 2 個，與表列相符。\n(B) 16～20 個對應選取 4 個，與表列相符。\n(C) 26～30 個對應選取 6 個，與表列相符。\n(D) 30 個以上之選取檢查數量，表列為 20%，本項寫 15%，為本題應選者。\n【記憶點】每多五個檢知器就多抽一個，抽到六個為止；超過三十個改抽 20%。","這張表把「回路內檢知器愈多、抽驗數量遞增，但不必全查」的抽樣邏輯法制化：五個一階，每多五個就多抽一個，到三十個時為六個；超過三十個改以百分比抽驗，避免大型場所抽驗數量無限膨脹。要特別留意這是級距表而不是比例公式，二十個抽四個並不代表「每五個抽一個」可以無限外推，過了三十個以後計算方式就換成百分比。\n檢知器性能檢查的方法同樣常考：使用加瓦斯試驗器進行加瓦斯測試，對空氣之比重未滿一者使用甲烷、比重大於一者使用異丁烷，測定檢知器動作及至受信總機瓦斯漏氣燈亮燈之時間，並確認中斷器、瓦斯漏氣表示燈及檢知區域警報裝置之動作狀況。判定上，所測得之時間扣除介入中繼器之五秒、採第三種測定方式之二十秒後，應在六十秒內。檢知區域警報裝置之音壓應在七十分貝以上，且音色有別於其他機械噪音。注意事項並規定檢知器每次測試時應輪流選取，選取之檢知器中若發現不良品，該回路之全部檢知器均應實施檢查。\n設置端可對照《各類場所消防安全設備設置標準》第 141 條：瓦斯對空氣之比重未滿一時，設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離八公尺以內，檢知器下端裝設在天花板下方三十公分範圍內；比重大於一時，水平距離四公尺以內，檢知器上端裝設在距樓地板面三十公分範圍內。第 140 條並定義本設備所稱瓦斯為天然氣、液化石油氣及其他經中央主管機關指定者；第 145 條規定其緊急電源應使用蓄電池設備，容量應能使二回路有效動作十分鐘以上，其他回路能監視十分鐘以上；水平距離之起算點，瓦斯燃燒器具為燃燒器中心點，瓦斯導管貫穿牆壁處則為面向室內牆壁處之瓦斯配管中心處。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-028","有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-030","有關緊急廣播設備標示燈外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準規定相同？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-027","有關緩降機支固器具之裝置，下列何者與各類場所消防安全設備設置標準之規定不同？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-031","有關緊急照明設備性能檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-026","有關緊急廣播設備配線之設置，除依屋內線路裝置規則外，下列何者與各類場所消防安全設備設置標準之規定不同？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-032","有關無線電通信輔助設備保護箱標示之外觀檢查的判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-029",113,"有關特別安全梯與緊急昇降機間排煙室兼用時，其排煙設備採機械排煙、自然進風方式，則排煙機之排煙量應在 X m3\u002Fsec 以上；直接面向戶外之進風口開口面積應在 Y m2 以上則 X、Y 各為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-029",112,"某建築物總樓地板面積在 5 萬平方公尺以上其主要避難路徑的地方，該出口標示燈及避難方向指示燈之緊急電源容量應在 60 分鐘以上，下列場所何者不是主要避難路徑？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-029",111,"緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-029",110,"有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-029",108,"消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",1785129964447]