[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-003":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-003","fire-109-1-alarm-evacuation-003",109,1,3,"瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",{"A":16,"B":17,"C":18,"D":19},"1","4","6","7","B",null,[],false,"本題考點：瓦斯漏氣檢知器的設置位置，依瓦斯對空氣之比重分成兩套水平距離規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 141 條第二款第一目，瓦斯對空氣之比重大於一時，檢知器「設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離四公尺以內」，同款第二目並要求檢知器上端裝設在距樓地板面三十公分範圍內；比重大於一之瓦斯外洩後沉降積聚於地面附近，故水平距離縮短、裝設位置下移，故選 B。\n【逐項排除】\n(A) 1 公尺並非本條之水平距離；一公尺是第 143 條檢知區域警報裝置音壓應在七十分貝以上的測定距離。\n(B) 4 公尺與第 141 條第二款第一目相符，為本題應選者。\n(C) 6 公尺不在第 141 條所列數值之內；該條的六是六十公分，指樑或類似構造體是否形成阻隔的淨高門檻。\n(D) 7 公尺同樣非本條數值；比重未滿一者為八公尺以內，條文並無七公尺之規定。\n【記憶點】輕瓦斯八公尺、天花板下方三十公分內；重瓦斯四公尺、距樓地板面三十公分內。","第 141 條的兩套規定完全由氣體物性推導而來。比重未滿一的天然氣外洩後上浮，故檢知器下端裝設在天花板下方三十公分範圍內，水平距離放寬到八公尺以內；但樓板有淨高六十公分以上之樑或類似構造體時，煙氣被樑阻隔而無法橫向擴散，即應改設於近瓦斯燃燒器具或瓦斯導管貫穿牆壁處。此外，瓦斯燃燒器具室內之天花板附近設有吸氣口時，應設在距器具或導管貫穿處與天花板間、無淨高六十公分以上之樑或類似構造體區隔之吸氣口一點五公尺範圍內——因為氣流會把外洩瓦斯帶往吸氣口，那裡才是最早到達的位置。\n比重大於一的液化石油氣沉降於地面，橫向擴散慢且易被門檻、家具阻擋，故距離收緊為四公尺以內，檢知器上端裝設在距樓地板面三十公分範圍內。第三款並明定水平距離之起算點：瓦斯燃燒器具為燃燒器中心點，瓦斯導管貫穿牆壁處為面向室內牆壁處之瓦斯配管中心處，計算題若從牆面或器具邊緣起算即會失分。\n配套的警報裝置見第 143 條：瓦斯漏氣表示燈於設有檢知器之居室面向通路時，設於該面向通路部分之出入口附近，距樓地板面高度在四點五公尺以下，亮度須在表示燈前方三公尺處能明確識別，並標明瓦斯漏氣表示燈字樣，但一警報分區僅一室時得免設；檢知區域警報裝置於檢知器動作時應發出警報音響，音壓在距一公尺處七十分貝以上，但檢知器具有發出警報功能者，或設於機械室等常時無人場所及瓦斯導管貫穿牆壁處者不在此限。《各類場所消防安全設備檢修及申報作業基準》瓦斯漏氣火警自動警報設備之外觀檢查，即以同一組八公尺、四公尺、三十公分的設置基準逐項判定。",true,[28,32,36,39,43,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-002","使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",2,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-004","某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",4,{"webId":37,"stem":38,"number":12,"year":11,"session":12},"fire-109-1-alarm-evacuation-001","常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-109-1-alarm-evacuation-005","差動式局限型探測器係利用下列何構件，來防止設置場所因正常溫度變化而造成火災誤報？",5,{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-108-1-alarm-evacuation-040","依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",40,108,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-006","差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",6,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-003",113,"下列場所不得免設排煙設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-003",112,"依據標示設備檢修基準，下列何者非性能檢查之檢查項目？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-003",111,"下列場所何者依規定應設置火警自動警報設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-003",110,"建築物有某一樓層樓地板面積 900 平方公尺且設置之避難方向指示燈均為 C 級，該樓層最有可能為下列何種用途？",{"webId":70,"year":47,"stem":71,"number":13},"fire-108-1-alarm-evacuation-003","用途為補習班，居室樓地板面積 300 平方公尺，採用有效通風方式檢討，其排煙口設於天花板下方 80 公分內，試問有效通風面積最少須要多少平方公尺以上方可符合規定？",1785129964206]