[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-002","fire-109-1-alarm-evacuation-002",109,1,2,"使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",{"A":16,"B":17,"C":18,"D":19},"甲烷","乙烷","丙烷","異丁烷","D",null,[],false,"本題考點：以加瓦斯試驗器檢查瓦斯漏氣檢知器時，試驗氣體須依瓦斯對空氣之比重選用。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》瓦斯漏氣火警自動警報設備之性能檢查，檢知器係「使用『加瓦斯試驗器』進行加瓦斯測試（對空氣之比重未滿一者使用甲烷，對空氣之比重大於一者使用異丁烷）」，並藉以測定檢知器動作及至受信總機動作之時間，同時確認中繼器、瓦斯漏氣表示燈及檢知區域警報裝置之動作狀況。題目所問為比重大於一者，故選 D。\n【逐項排除】\n(A) 甲烷比空氣輕，是該基準指定給比重未滿一（如天然氣）之檢知器使用的試驗氣體，與題目條件相反。\n(B) 乙烷未列於該檢查方法所指定之試驗氣體，屬憑印象填入的選項。\n(C) 丙烷雖為液化石油氣主要成分且比空氣重，但基準括號內指定者為異丁烷，並非丙烷。\n(D) 異丁烷即基準明定用於比重大於一之試驗氣體，為本題應選者。\n【記憶點】輕瓦斯配甲烷、重瓦斯配異丁烷，正好對應檢知器八公尺與四公尺兩套設置位置。","試驗氣體之所以分兩種，是為了讓測試條件貼近該場所實際可能外洩的瓦斯：對空氣比重未滿一的天然氣以甲烷為代表，外洩後上浮並蓄積於天花板附近；對空氣比重大於一的液化石油氣以異丁烷為代表，外洩後沉降並蓄積於地面附近。檢知器的感測元件與設置高度都依此設計，若拿錯氣體，等於在錯誤的高度與濃度條件下驗證，測不出真實性能。\n該基準對檢知器的抽驗數量訂有級距表：一回路之檢知器一至五個選取一個，六至十個選二個，十一至十五個選三個，十六至二十個選四個，二十一至二十五個選五個，二十六至三十個選六個，三十個以上者取百分之二十。判定則規定由確認燈、檢知區域警報裝置或加壓試驗用瓦斯起算所測得之時間，扣除介入中繼器之五秒、採第三種測法之二十秒後，應在六十秒內；且每次測試應輪流選取，選取之檢知器中發現不良品時，該回路全部檢知器均應實施檢查。\n設置面的規定則回到《各類場所消防安全設備設置標準》第 141 條：比重未滿一者設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離八公尺以內，檢知器下端裝設在天花板下方三十公分範圍內；比重大於一者水平距離四公尺以內，檢知器上端裝設在距樓地板面三十公分範圍內。檢修基準的檢知器設置基準表另列不得設置之場所：出入口附近外氣流通之場所、距出風口一點五公尺內之場所、瓦斯燃燒器具之廢氣容易接觸之場所、明顯無法確保檢知器性能之場所——這四款與試驗氣體的選用同屬「確保檢知條件真實」的同一組思維。加瓦斯測試使檢知器動作後，同一次檢查還要接著確認警報裝置：瓦斯漏氣表示燈應無明顯劣化且正常亮燈，動作之檢知器所在位置應能容易辨識；檢知區域警報裝置之音壓應在七十分貝以上，音色須有別於其他機械噪音，且於檢知區域內任一點均能有效聽到。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-109-1-alarm-evacuation-001","常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-109-1-alarm-evacuation-003","瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-108-1-alarm-evacuation-040","依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",40,108,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-004","某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-108-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，下列何種場所不須設置緊急電源插座？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-005","差動式局限型探測器係利用下列何構件，來防止設置場所因正常溫度變化而造成火災誤報？",5,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-002",113,"對於緊急電源插座距離樓地板的裝設高度範圍，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-002",112,"依據緊急電源插座檢修基準，有關性能檢查之判定方法，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-002",111,"平時有人之公共危險物品製造、儲存或處理場所，若未達應設置火警自動警報設備之規定時，其儲存、處理公共危險物品數量達幾倍管制量以上，應設置手動報警設備或具同等功能之緊急通報裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-002",110,"某樓高 12 層觀光旅館於最高樓層開設之餐廳，依各類場所消防安全設備設置標準之規定，其位於同樓層的廚房無須設置下列何種裝置？",{"webId":70,"year":39,"stem":71,"number":13},"fire-108-1-alarm-evacuation-002","特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",1785129964195]