[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-109-1-警報與避難系統消防安全設備概要-001","fire-109-1-alarm-evacuation-001",109,1,"常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"A":15,"B":16,"C":17,"D":18},"短路測試","斷線測試","電量測試","電壓測試","B",null,[],false,"本題考點：火警自動警報設備配線中終端電阻的功能，出自《設置標準》的配線規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 127 條第一款，「常開式之探測器信號回路，其配線採用串接式，並加設終端電阻，以便藉由火警受信總機作回路斷線自動檢出用」。常開式接點平時開路，若不串接一個已知電阻，總機無從分辨線路是完好或已斷；加設終端電阻後，總機可持續以微小監視電流確認回路導通，故選 B。\n【逐項排除】\n(A) 短路測試不是終端電阻的目的；回路短路時受信總機呈現與火災信號相同之狀態，並非靠終端電阻辨識。\n(B) 斷線測試即條文所稱之「回路斷線自動檢出用」，為本題應選者。\n(C) 電量測試並非第 127 條所定機能，該條五款中並無此項目。\n(D) 電壓測試指向的是同條第四款的絕緣電阻測定，係以直流二百五十伏特額定之絕緣電阻計為之，屬絕緣性能查核，與終端電阻無涉。\n【記憶點】常開式回路＋串接式配線＋終端電阻，等於斷線自動檢出。","終端電阻的原理是把「常開接點的火災信號」與「線路本身的健全性」拆成兩種可辨識的電氣狀態：平時回路串著終端電阻，監視電流是一個固定的小值；探測器動作使接點閉合、電阻被短路，電流變大即判為火警；線路斷了電流歸零，即判為斷線。三種狀態互不混淆，這就是第 127 條第一款要求「串接式」而非並接式的理由。\n瓦斯漏氣火警自動警報設備採同一套設計：第 144 條第二款規定常開式檢知器信號回路之配線採用串接式，並加設終端電阻，以便藉由瓦斯漏氣受信總機作斷線自動檢出用；同條第三款並要求檢知器回路不得與該設備以外之設備回路共用。兩者的差別在絕緣電阻計的額定電壓——火警用直流二百五十伏特（第 127 條第四款），瓦斯漏氣用直流五百伏特（第 144 條第一款），判定值同為對地電壓一百五十伏特以下者零點一 MΩ 以上、超過者零點二 MΩ 以上，回路每一分區零點一 MΩ 以上，這一組對照極常出題。\n第 127 條其餘各款也要一併掌握：P 型受信總機採數個分區共用一公用線方式配線時，該公用線供應之分區數不得超過七個；探測器回路電阻在五十Ω以下；埋設於屋外或有浸水之虞之配線採電纜並穿於金屬管或塑膠導線管，與電力線保持三十公分以上間距。\n在檢修端，終端電阻的效果由《各類場所消防安全設備檢修及申報作業基準》火警自動警報設備之性能檢查中的回路導通項目驗證：將回路斷線試驗開關開到試驗側，依序旋轉回路選擇開關，各回路由試驗用計器之指示值確認是否在所定範圍，或由斷線表示燈確認之；具自動斷線監視方式者，應將回路作成斷線狀態確認其性能。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-108-1-alarm-evacuation-040","依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",40,108,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-002","使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-108-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，下列何種場所不須設置緊急電源插座？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-003","瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-108-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-004","某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",4,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":12},"fire-113-1-alarm-evacuation-001",113,"為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":12},"fire-112-1-alarm-evacuation-001",112,"依據配線檢修基準性能檢查之檢查方法，有關高壓回路電源回路間及電源回路與大地間之絕緣電阻值測定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":12},"fire-111-1-alarm-evacuation-001",111,"依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":66,"year":67,"stem":68,"number":12},"fire-110-1-alarm-evacuation-001",110,"下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":70,"year":31,"stem":71,"number":12},"fire-108-1-alarm-evacuation-001","某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",1785129964181]