[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-037","fire-108-1-water-chemical-037",108,1,37,"進行滅火器之檢查時，有關一般注意事項，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"塑膠製容器或構件，不得以辛那（二甲苯）或汽油等有機溶劑加以清理","護蓋之開關緊閉時，應使用適當之拆卸扳手或鐵鎚執行","乾粉滅火器本體容器內壁及構件之清理及保養時，應充分注意防潮","開啟護蓋或栓塞時，應注意容器內殘壓之排除","B",null,[],false,"本題考點：滅火器檢查的一般注意事項，特別是開啟護蓋所准用的工具。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》滅火器章一般注意事項,「護蓋之開關，應使用適當之拆卸扳手，不得以鐵鎚或以鑿刀敲擊」;基準是把鐵鎚列為禁止使用的工具，本選項卻寫成拆卸扳手「或鐵鎚」均可執行，與規定相反，故選 B。\n【逐項排除】\n(A) 敘述正確。基準明定合成樹脂製容器或構件，不得以辛那(二甲苯)或汽油等有機溶劑加以清理，以免容器材質受侵蝕劣化。\n(B) 敘述錯誤，為本題應選者。護蓋緊閉時仍只能使用適當的拆卸扳手，以鐵鎚敲擊會使容器或護蓋變形、螺牙受損，基準明文排除鐵鎚與鑿刀。\n(C) 敘述正確。基準指出乾粉藥劑極易因受潮而影響滅火之動作及效能，故本體容器內壁及構件之清理及保養時應充分注意。\n(D) 敘述正確。基準規定開啟護蓋或栓塞時應注意容器內殘壓，須排出容器內殘壓後始得開啟，以免殘壓將護蓋彈出。\n【記憶點】護蓋只認拆卸扳手，鐵鎚鑿刀一律不得敲。","滅火器的性能檢查依加壓方式分三種順序。化學反應式：打開護蓋，取出內筒、支撐架及活動蓋，確認滅火藥劑量是否達到液面標示的定量位置，將藥劑移置另一容器，再以清水洗滌本體容器內外、護蓋、噴射皮管、噴嘴、虹吸管、內筒及支撐架，最後確認各部構件。加壓式：藥劑量以重量表示者先以磅秤確認總重量，有排氣閥者先打開使容器內壓完全排出，再卸下護蓋取出加壓用氣體容器及其支撐裝置，藥劑量以容量表示者確認是否達液面標示的定量位置，取出藥劑後清理並確認各構件。蓄壓式：先秤重確認藥劑量、確認壓力指示計的指針位置，有排氣閥者打開排壓，無排氣閥者倒置按下壓把使容器內壓完全排出(二氧化碳滅火器及海龍滅火器除外),再自容器本體取下護蓋或栓塞。\n清理方式依藥劑性質分流：水系滅火器以清水洗滌；鹵化物滅火器與乾粉滅火器屬嚴禁水分之物質，應以乾燥之壓縮空氣清理，這正是選項(C)強調防潮的延伸。二氧化碳滅火器及海龍滅火器進行重量檢查時，失重超過百分之十以上或壓力表示值在綠色範圍外者應予以更新，是常考的判定數值。壓力調整器的判定方法則為壓力指針動作應正常、調整壓力值應在綠色範圍內，無法正常動作或超出綠色範圍者應修復或更換；其檢查方法是先關閉本體容器連接閥門，打開加壓用氣體容器閥觀察壓力計指度與指針動作，再關閉容器閥觀察高壓側壓力表指度是否下降以判斷有無洩漏。\n這類題目的解題訣竅是抓「工具、材質、殘壓、水分」四個關鍵詞：工具只認拆卸扳手，合成樹脂件忌有機溶劑，開蓋前先排殘壓，乾粉與鹵化物忌水，四句話就能覆蓋一般注意事項的大半考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-036","依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-038","依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-035","依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備呼水裝置之減水警報裝置，當水量減少至多少前應發出警報？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-039","依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-034","依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-040","電動機之使用應符合之相關規定，下列何者錯誤？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-037",113,"加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-037",112,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-037",111,"依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-037",110,"依消防安全設備及必要檢修項目檢修基準，水道連結型自動撒水設備之末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-037",109,"連結送水管之配管設置規定，應能承受送水設計壓力 1.5 倍以上之水壓，且能持續多少時間才合格？",1785129973076]