[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-036","fire-108-1-water-chemical-036",108,1,36,"依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",{"A":16,"B":17,"C":18,"D":19},"100 平方公尺","300 平方公尺","500 平方公尺","1,000 平方公尺","C",null,[],false,"本題考點：高發泡放出口在全區放射時的配置密度與泡沫放出停止裝置。\n【正解理由】依《各類場所消防安全設備設置標準》第七十三條，高發泡放出口分全區放射與局部放射兩種情形配置；全區放射時，防護區域開口部應能在泡沫水溶液放射前自動關閉(能有效補充開口部洩漏者得免設自動關閉裝置),放出口則按防護區域樓地板面積每五百平方公尺至少設置一個，且能有效放射至該區域，並附設泡沫放出停止裝置，四個選項中與該條相符者為五百平方公尺，故選 C。\n【逐項排除】\n(A) 100 平方公尺：配置密度遠高於該條所採的面積級距；一百平方公尺是第二十八條居室應設排煙設備的樓地板面積門檻，與泡沫放出口無關。\n(B) 300 平方公尺：並非該條的配置基準，依此設置會使放出口數量比法定要求多出六成以上。\n(C) 500 平方公尺：與第七十三條全區放射的配置規定相符，為正確答案。\n(D) 1,000 平方公尺：單一放出口的分擔面積成為法定值的兩倍，泡沫難以有效充滿冠泡體積；一千平方公尺是第十三條增建改建部分樓地板面積合計的門檻，不是放出口配置基準。\n【記憶點】高發泡全區放射，每五百平方公尺一個並附放出停止裝置。","高發泡與低發泡的分野在膨脹比。第七十三條把高發泡分成三種：八十以上二百五十未滿為第一種，二百五十以上五百未滿為第二種，五百以上一千未滿為第三種。全區放射的泡沫水溶液放射量依防護對象查表，單位是每分鐘每立方公尺冠泡體積的公升數：飛機庫第一種二公升、第二種零點五公升、第三種零點二九公升；室內停車空間或汽車修護廠第一種一點一一公升、第二種零點二八公升、第三種零點一六公升；第十八條表第八項所列場所第一種一點二五公升、第二種零點三一公升、第三種零點一八公升。膨脹比愈大、泡沫愈輕，單位時間所需水溶液量愈少，這正是表中數值隨種別遞減的原因。\n水源另走第七十六條：全區放射時以最大樓地板面積的防護區域，依冠泡體積每一立方公尺的泡沫水溶液量核算，第一種零點零四立方公尺、第二種零點零一三立方公尺、第三種零點零零八立方公尺；防護區域開口部未設閉鎖裝置者，還要加算開口洩漏的泡沫水溶液量，且各款計算後應加算充滿配管所需量，再加算總泡沫水溶液量的百分之二十。局部放射則依第七十三條核算的放射量，在樓地板面積最大區域能繼續放射二十分鐘以上；移動式泡沫滅火設備的水源容量，為二具泡沫瞄子同時放水十五分鐘的水量以上。\n冠泡體積是高發泡計算題的共同起點，考題常一次要求算冠泡體積、查放射量表、查水源表，最後再加配管量與百分之二十的安全量，把順序記熟就不會漏步驟；而放出口個數則是另一條獨立的計算線，以樓地板面積除以五百取整計算，兩條線不要混在一起。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-035","依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備呼水裝置之減水警報裝置，當水量減少至多少前應發出警報？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-037","進行滅火器之檢查時，有關一般注意事項，下列何者錯誤？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-034","依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-038","依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-033","某百貨商場（10 樓以下）內設有一般反應型撒水頭 15 個，試問其消防幫浦最低出水量應為何？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-039","依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-036",113,"有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-036",112,"乾粉滅火設備採全區或局部之噴頭，下列設置規定何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-036",111,"二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-036",110,"依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-036",109,"任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",1785129973068]