[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-028","fire-108-1-water-chemical-028",108,1,28,"依法令規定在應設水霧、泡沫、乾粉、二氧化碳滅火設備之場所，但外牆開口面積（常時開放部分）達該層樓地板面積百分之多少以上者，上列滅火設備得採移動式設置？",{"A":16,"B":17,"C":18,"D":19},"15","20","25","30","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 18 條但書，外牆常時開放開口達多少比例時得改採移動式設置。\n【正解理由】第 18 條本文列出應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置之場所，但書明定「但外牆開口面積（常時開放部分）達該層樓地板面積百分之十五以上者，上列滅火設備得採移動式設置」。題目問的正是這個門檻，答案為 15，故選 A。\n【逐項排除】\n(A) 百分之十五與第 18 條但書逐字相符，為本題應選者：開口大到這個程度，藥劑已難以在區域內滯留，全區放射失去意義。\n(B) 20 並非第 18 條但書之數值；考生常把它與其他百分比規定混記，但但書只有十五這一個門檻。\n(C) 25 高於條文所定比例；若採此標準，開口達 15% 至 25% 的場所將被迫維持全區放射方式，與條文放寬的立法方向不符。\n(D) 30 更明顯偏離條文，且此數值在第 18 條全條並無出處，屬純誘答項。\n【記憶點】常時開放開口達樓地板面積 15% 以上，全區改移動式，記「一五改移動」。","第 18 條但書背後是滅火機制問題。水霧以外的泡沫、乾粉、二氧化碳等設備採全區放射時，必須在區劃內建立並維持一定的藥劑濃度或覆蓋，開口若常時開放且面積達該層樓地板面積百分之十五以上，藥劑會迅速逸散，全區放射不但無效還浪費藥劑，因此條文允許改採移動式，由人員持皮管接近火點放射。這也解釋了為什麼是「常時開放部分」才計入——設有自動關閉裝置、放射前會關上的開口不算。\n第 18 條本文的應設場所表值得整理成清單記憶：屋頂直昇機停機場（坪）；飛機修理廠、飛機庫樓地板面積在二百平方公尺以上者；汽車修理廠、室內停車空間在第一層樓地板面積五百平方公尺以上者，在地下層或第二層以上樓地板面積在二百平方公尺以上者，在屋頂設有停車場樓地板面積在三百平方公尺以上者；昇降機械式停車場可容納十輛以上者；發電機室、變壓器室及其他類似之電器設備場所樓地板面積在二百平方公尺以上者；鍋爐房、廚房等大量使用火源之場所二百平方公尺以上者；電信機械室、電腦室或總機室二百平方公尺以上者；引擎試驗室、石油試驗室、印刷機房等危險工作場所二百平方公尺以上者。可以記成「二百平方公尺是主旋律，室內停車空間第一層才放寬到五百」。\n易混淆的百分比對照：第 18 條但書的百分之十五講的是「外牆常時開放開口占該層樓地板面積」的比例，決定放射方式；第 86 條講的是全區放射方式防護區域「未設自動關閉裝置之開口部總面積」的上限，供電信機械室使用時應在圍壁面積百分之一以下，其他處所則應在防護區域體積值或圍壁面積值二者中較小數值百分之十以下，決定的是能不能維持全區放射的有效性。兩者一個是十五、一個是十與一，分母也不同，務必分開記。放射方式的三種型態則見第 82 條：全區放射、局部放射，以及移動放射方式（皮管接頭至防護對象任一部分之水平距離在十五公尺以下）。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-027","依各類場所消防安全設備設置標準之規定，室外消防栓於其 I 公尺範圍內附設水帶箱，在 J 公尺以內，保持空曠，不得堆放物品或種植花木。下列 I，J 何者正確？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-029","有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-026","依各類場所消防安全設備設置標準之規定，建築物高度超過 60 公尺者，連結送水管應採用濕式，其中繼幫浦設置規定之敘述何者錯誤？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-030","依滅火器設置規定，下列何者錯誤？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-025","下列何者不屬於各類場所消防安全設備設置標準第 8 條所規定的滅火設備？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-031","第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-028",113,"下列場所之消防安全設備設置何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-028",112,"有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-028",111,"依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-028",110,"消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-028",109,"水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",1785129973009]