[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-026","fire-108-1-water-chemical-026",108,1,26,"依各類場所消防安全設備設置標準之規定，建築物高度超過 60 公尺者，連結送水管應採用濕式，其中繼幫浦設置規定之敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"中繼幫浦出水量在每分鐘 2,400 公升以上","屋頂水箱有 0.5 立方公尺以上容量，中繼水箱有 2.0 立方公尺以上","全閉揚程與押入揚程合計在 170 公尺以上時，增設幫浦使串聯運轉","設置中繼幫浦之機械室及連結送水管送水口處，設有能與防災中心通話之裝置","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 183 條，建築物高度超過六十公尺者連結送水管中繼幫浦之各項數值。\n【正解理由】第 183 條第五款明定「屋頂水箱有零點五立方公尺以上容量，中繼水箱有二點五立方公尺以上」。選項所寫中繼水箱 2.0 立方公尺，與條文的二點五立方公尺不符，是四個敘述中唯一與條文牴觸者；題目要找錯誤敘述，故選 B。\n【逐項排除】\n(A) 與第 183 條第二款「中繼幫浦出水量在每分鐘二千四百公升以上」相符，敘述正確，不是本題應選者。\n(B) 屋頂水箱 0.5 立方公尺以上固然正確，但中繼水箱應為二點五立方公尺以上，選項寫成 2.0 立方公尺，為本題應選之錯誤敘述。\n(C) 與第七款「全閉揚程與押入揚程合計在一百七十公尺以上時，增設幫浦使串聯運轉」完全一致，敘述正確。\n(D) 與第八款「設置中繼幫浦之機械室及連結送水管送水口處，設有能與防災中心通話之裝置」一致，敘述正確。\n【記憶點】中繼幫浦四個數字：出水 2400、屋頂水箱 0.5、中繼水箱 2.5、串聯 170。","連結送水管是供消防人員搶救使用的設備，平時由消防車自一樓送水口加壓送水。但送水壓力有物理極限，建築物高度超過六十公尺時，單靠地面加壓已無法把水送到頂層並維持有效放水壓力，因此第 183 條要求採用濕式並設中繼幫浦，在中間樓層接力加壓。條文第一款把這件事寫成公式：全揚程＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋放水壓力（H＝h1＋h2＋h3＋60m），末項六十公尺就是為了確保頂層仍有足夠放水壓力而預留的水頭。\n第 183 條的數值可整理成一張表：中繼幫浦出水量每分鐘二千四百公升以上；屋頂水箱 0.5 m³ 以上、中繼水箱 2.5 m³ 以上；全閉揚程與押入揚程合計一百七十公尺以上時增設幫浦串聯運轉；放水測試時應從送水口以送水設計壓力送水，並以口徑二十一毫米瞄子在最頂層測試，放水壓力在每平方公分六公斤以上或 0.6 MPa 以上，且放水量在每分鐘六百公升以上。第三款另規定送水口附近設手動啟動裝置及紅色啟動表示燈，但設有能由防災中心遙控啟動且送水口與防災中心間設有通話裝置者得免設；第四款則是一次側設出水口、止水閥及壓力調整閥並附設旁通管，二次側設逆止閥、止水閥及送水口或出水口。\n易混淆對照：屋頂水箱與中繼水箱是兩個不同的水箱，前者維持配管充水、後者供中繼幫浦吸水，數值一個 0.5 一個 2.5，最常被對調。配管規定在第 181 條：立管應為專用且管徑一百毫米以上，但建築物高度在五十公尺以下時得與室內消防栓共用立管，支管管徑在六十五毫米以上；配管並應能承受送水設計壓力一點五倍以上之水壓且持續三十分鐘，設有中繼幫浦者，幫浦二次側配管應能承受全閉揚程一點五倍以上之水壓。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-025","下列何者不屬於各類場所消防安全設備設置標準第 8 條所規定的滅火設備？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-027","依各類場所消防安全設備設置標準之規定，室外消防栓於其 I 公尺範圍內附設水帶箱，在 J 公尺以內，保持空曠，不得堆放物品或種植花木。下列 I，J 何者正確？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-024","某一 15 樓層之建築物，其消防安全設備同時設有第一種室內消防栓及自動撒水設備，其屋頂水箱容量至少應為下列何者？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-028","依法令規定在應設水霧、泡沫、乾粉、二氧化碳滅火設備之場所，但外牆開口面積（常時開放部分）達該層樓地板面積百分之多少以上者，上列滅火設備得採移動式設置？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-023","依各類場所消防安全設備設置標準之規定，有關應設置室外消防栓設備之場所，下列敘述何者正確？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-029","有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-026",113,"設於外浮頂式儲槽之泡沫放出口為？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-026",112,"依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-026",111,"壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-026",110,"固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-026",109,"密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",1785129972993]