[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-017","fire-108-1-water-chemical-017",108,1,17,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",{"A":16,"B":17,"C":18,"D":19},"9","11","12","17","C",null,[],false,"本題考點：老舊消防水帶續用前的耐水壓試驗條件，第一種室內消防栓為 7kgf\u002Fcm² 以上、5 分鐘。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第二章室內消防栓設備「二、性能檢查」消防栓箱等之第一種消防栓檢查方法：製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，並利用相關器具夾住水帶兩末端處，確認快速接頭已確實連接及水帶內無殘留空氣後，「施以 7kgf\u002Fcm² 以上水壓試驗 5 分鐘合格，始得繼續使用」。X 為 7、Y 為 5，相加為 12，故選 C。\n【逐項排除】\n(A) 9：本項無此組合；若把室外消防栓的 6kgf\u002Fcm² 與但書「已經水壓試驗合格未達 3 年者不在此限」的 3 相加即得 9，惟 3 是免再試驗的期間，不是試驗分鐘數。\n(B) 11：為 6 與 5 之和，6kgf\u002Fcm² 是室外消防栓箱及射水設備室外消防栓箱水帶的試驗壓力，適用設備與本題不同。\n(C) 12：即 7 與 5 之和；泡沫消防栓箱與連結送水管水帶箱同樣採 7kgf\u002Fcm² 以上、5 分鐘，為本題正解。\n(D) 17：係誤將 7 與題幹的製造年份 10 年相加，10 年是啟動本項試驗的年限門檻，並非試驗時間。\n【記憶點】水帶試驗「室內、泡沫、連結送水管記 7，室外、射水記 6」，時間一律 5 分鐘、3 年內免再試。","消防水帶會因反覆折疊、日照與潮濕而劣化，基準因此把「製造年份超過 10 年或無法辨識製造年份」設為啟動耐水壓試驗的門檻，並以「已經水壓試驗合格未達 3 年者，不在此限」作為免試期間，形成十年起驗、三年內免重驗的循環。試驗程序本身也是考點：兩端快速接頭連接於耐水壓試驗機，並利用相關器具夾住消防水帶兩末端處，經確認快速接頭已確實連接、且快速接頭至被器具夾住處之間的水帶內無殘留空氣後，才可加壓。排除殘留空氣的用意在於空氣可壓縮，殘留空氣會使壓力讀值失真，也會在水帶破裂時因氣體急速膨脹而增加危險。\n試驗壓力依設備別分兩級，可橫向整理：室內消防栓第一種、泡沫消防栓箱、連結送水管水帶箱均為 7kgf\u002Fcm² 以上；室外消防栓箱與射水設備之室外消防栓箱為 6kgf\u002Fcm² 以上；試驗時間則一律 5 分鐘。記法是「屋內壓力高記七、屋外記六，時間都是五分鐘」。\n第一種與第二種室內消防栓的檢查方法也不同：第一種以目視確認有無腐蝕、損傷，並用手操作確認是否容易拆接，另有前述耐水壓試驗；第二種則以目視確認有無腐蝕、損傷及瞄子開閉裝置操作是否容易，判定為開關裝置應能容易操作，不涉及拆接與水壓試驗。這組差異常與放水量 130 與 80 公升／分的對比一併命題。\n判定方法方面，水帶及瞄子應無損傷、腐蝕，應能容易拆、接，水帶應無破裂、漏水或與消防水帶用接頭脫落之情形；消防栓及測試出水口則以手操作確認開、關是否容易，判定為開關操作應能容易進行。相關考點會延伸到連結送水管第二十章、泡沫滅火設備第七章、室外消防栓第三章的水帶箱檢查，四處條文文字幾乎相同，只有壓力值有別，複習時用同一張表比對，最能避免把 6 與 7 記混。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-016","依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-018","依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-015","依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-019","依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-014","依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-020","公共危險物品等場所之滅火設備分類，下列敘述何者錯誤？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-017",113,"有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-017",112,"有關室內消防栓之水平距離、瞄子放水壓力、消防栓及位置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-017",111,"惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-017",110,"密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-017",109,"某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",1785129972938]