[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-016","fire-108-1-water-chemical-016",108,1,16,"依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",{"A":16,"B":17,"C":18,"D":19},"8.5","8.7","9.5","10.5","D",null,[],false,"本題考點：公共危險物品等場所達顯著滅火困難者所設第一種滅火設備之消防栓，其放水壓力的上下限。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第二章室內消防栓設備「三、綜合檢查」判定方法之放水壓力欄：消防栓放水壓力應在 1.7kgf\u002Fcm² 以上 7kgf\u002Fcm² 以下，「但公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在 3.5kgf\u002Fcm² 以上 7kgf\u002Fcm² 以下」。題目所稱 X 即 3.5、Y 即 7，兩者相加為 10.5，故選 D。\n【逐項排除】\n(A) 8.5：為室外消防栓一般判定值 2.5kgf\u002Fcm² 以上 6kgf\u002Fcm² 以下之和，適用對象是室外消防栓，與題目所問的室內消防栓不同。\n(B) 8.7：為一般場所室內消防栓 1.7 與 7 之和，題目已限定公共危險物品等場所達顯著滅火困難者，應適用但書而非本文。\n(C) 9.5：係把但書的下限 3.5 與室外消防栓的上限 6 拼湊而成，兩者分屬不同章的判定值，不得混用。\n(D) 10.5：即 3.5 與 7 之和，與但書所定範圍完全對應，為本題正解。\n【記憶點】公危顯著滅火困難的室內消防栓：壓力下限抬到 3.5、上限仍是 7，放水量則抬到 260 公升／分。","室內消防栓的綜合檢查，是把設置端規格與檢修端判定合起來考的典型題型。依《消防安全設備及必要檢修項目檢修基準》第二章的綜合檢查，放水試驗應於裝置消防栓最多之最高樓層實施，以該樓層全部消防栓放水為準，消防栓超過二支時以二支同時放水；公共危險物品等場所達顯著滅火困難者設置消防栓之數量超過五支時，則以五支同時放水。壓力量測方式是將壓力表之進水口放置於瞄子前端、距離為瞄子口徑二分之一處讀取指示值。放水量依 Q＝0.653D²√P 計算，Q 為瞄子放水量（公升／分）、D 為瞄子口徑（毫米）、P 為瞄子壓力（kgf\u002Fcm²）。\n判定值可整理成一張表：室內消防栓放水壓力 1.7 至 7kgf\u002Fcm²，公危顯著滅火困難者設置之第一種滅火設備消防栓為 3.5 至 7kgf\u002Fcm²；放水量第一種消防栓 130 公升／分以上、第二種 80 公升／分以上，公危顯著滅火困難者為 260 公升／分以上。室外消防栓另成一組：放水壓力 2.5 至 6kgf\u002Fcm²，公危顯著滅火困難者、爆竹煙火製造場所有火藥區之作業區或庫存區及爆竹煙火儲存場所為 3.5kgf\u002Fcm² 以上；放水量 350 公升／分以上，前述場所為 450 公升／分以上，且放水試驗選擇配管上最遠最高處之二具，前述場所超過四具時選四具。\n對公共危險物品等場所加嚴的理由，在於這類場所的火載量與延燒速度都高於一般場所，需要更大的放水量與更遠的射程，壓力下限自然要抬高；上限仍維持 7kgf\u002Fcm²，則是為限制瞄子反作用力，確保仍在人員可控範圍內。\n減壓措施的性能檢查採用同一組判定值：打開距加壓送水裝置最近及最遠的消防栓開關閥，確認壓力是否在規定範圍，並確認減壓閥等應無洩漏、變形、損傷。綜合檢查另須切換成緊急電源供電狀態實施，惟於檢查類似醫院之場所，因切換緊急電源可能產生困擾時，得使用常用電源檢查——這個但書本身也是常見的考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-015","依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-017","依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-014","依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-018","依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-013","依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-019","依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-016",113,"有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-016",112,"有關二氧化碳滅火設備構件之安全措施規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-016",111,"乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-016",110,"某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-016",109,"製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",1785129972936]