[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-015","fire-108-1-water-chemical-015",108,1,15,"依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",{"A":16,"B":17,"C":18,"D":19},"3","5","10","15","C",null,[],false,"本題考點：蓄壓式滅火器性能檢查中，二氧化碳滅火器與海龍滅火器以重量法判定汰換的門檻。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第一章滅火器「三、性能檢查」各加壓方式檢查之順序，蓄壓式滅火器之注意事項明定：「對二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過 10％以上或壓力表示值在綠色範圍外時，應予以更新。」判定採失重比例與壓力表指示位置雙軌，任一不合即應更新，故選 C。\n【逐項排除】\n(A) 3：該注意事項未以百分之三為門檻；本基準中的 3 出現在鈷 60 有效使用年限約為 3 年，是年限而非失重比例。\n(B) 5：同樣非該注意事項所列比例，易與泡沫滅火設備綜合檢查「發泡倍率應在 5 倍以上」的判定值混淆。\n(C) 10：與原文「失重超過 10％以上」相符；氣體系滅火藥劑量與重量表核對之差值亦以充填值 10％以下為界，門檻一致，為本題正解。\n(D) 15：基準未列此比例；滅火藥劑的重量誤差另以表 1-3 依標示重量分級、以公克表示容許範圍，不用百分比表達。\n【記憶點】二氧化碳與海龍滅火器不排氣、直接秤重，失重超過一成或指針跑出綠色範圍就更新。","滅火器性能檢查依加壓方式分三類，檢查順序不同正是命題重點。化學反應式先打開護蓋，取出內筒、支撐架及活動蓋，確認滅火藥劑量是否達液面標示之定量位置後取出藥劑，再以清水洗滌本體容器內外、護蓋、噴射皮管、噴嘴、虹吸管、內筒及支撐架。加壓式先以磅秤確認滅火藥劑之總重量，有排氣閥者先打開使容器內壓完全排出，再卸下護蓋取出加壓用氣體容器及其支撐裝置。蓄壓式則先秤重確認藥劑量、再確認壓力指示計之指針位置，有排氣閥者先打開、無排氣閥者倒置按下壓把使內壓完全排出——但二氧化碳滅火器及海龍滅火器除外，因藥劑本身即為高壓液化氣體，不能以排氣方式處理，只能靠秤重判定，這正是該注意事項要獨立列出的原因。\n清理方式也分兩路：水系滅火器以清水洗滌本體容器內外、護蓋、噴射皮管、噴嘴、虹吸管；鹵化物滅火器與乾粉滅火器屬嚴禁水分之物質，應以乾燥之壓縮空氣清理同樣的部位。這組「水洗與乾燥壓縮空氣」的對比是常見的是非題素材。\n與重量有關的另一組數值是滅火藥劑的總重量容許範圍表：標示重量 1 公斤未滿者為＋100 公克至－80 公克，1 至 2 公斤為＋200 公克至－80 公克，2 至 5 公斤為＋300 公克至－100 公克，級距愈重容許範圍愈寬，至 100 公斤以上為＋2,400 公克至－1,000 公克。要注意這張表以公克分級，而二氧化碳與海龍的汰換判定用的是百分比失重，兩套判定不可互套。\n藥劑品質面另有規定：新更換及充填之滅火藥劑應為經內政部登錄機構認可之產品，充填完成時其噴射性能須能噴射所充填藥劑容量或重量 90％以上之量，使用期限內須達 80％以上；二氧化碳滅火器所充藥劑應採一般工業用之液體二氧化碳，純度應為 99％以上並有相關證明文件。外觀檢查則另以壓力指示計為判定對象，壓力指示值應在綠色範圍內，與性能檢查的失重判定形成雙重把關。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-014","依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-016","依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-013","依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-017","依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-012","主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-018","依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-015",113,"有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-015",112,"有關滅火設備之緊急電源供電容量規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-015",111,"採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-015",110,"公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-015",109,"公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",1785129972932]