[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-010","fire-108-1-water-chemical-010",108,1,10,"有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",{"A":16,"B":17,"C":18,"D":19},"30","60","90","210","D",null,[],false,"本題考點：二氧化碳滅火設備全區放射方式，電信機械室所核算之滅火藥劑量必須在多少時間內放射完畢。\n【正解理由】依《各類場所消防安全設備設置標準》關於二氧化碳滅火設備噴頭與滅火藥劑放射時間之規定，全區放射方式所核算之滅火藥劑量，應依場所別於表列時間內全部放射完畢；電信機械室、總機室這類電氣場所的表列放射時間為三點五分鐘，換算為二百一十秒，故選 D。\n【逐項排除】\n(A) 三十秒是乾粉滅火設備依第 100 條第三款所核算藥劑量的放射時間，與二氧化碳於電氣場所的表列時間無關。\n(B) 六十秒僅一分鐘，對電氣場所的陰燃與深層火災而言過短，並非電信機械室的表列放射時間。\n(C) 九十秒同樣不是表列值，一分半難以讓藥劑滲入機房夾層與高架地板下方並維持設計濃度。\n(D) 三點五分鐘即二百一十秒，與電信機械室之表列放射時間相符，為正確答案。\n【記憶點】電信機械室記「三點五分鐘等於二百一十秒」，三十秒是乾粉的數字。","為什麼電氣場所的放射時間拉長：一般可燃物火災講求「短時間內建立滅火濃度」，故放射時間短；但電信機械室、總機室的火災多為纜線絕緣材與電子元件的陰燃、深層火災，火點常藏在機櫃內部、高架地板下方或線槽之中。二氧化碳必須有足夠時間滲入這些夾層，並在整個防護區域維持設計濃度一段時間，才能真正熄滅，因此表列放射時間放寬到三點五分鐘。放射時間拉長的代價是藥劑更容易從開口與縫隙散失，故條文另以開口部與自動關閉裝置的規定加以節制。\n配套規定：第 85 條明定全區或局部放射方式防護區域內之通風換氣裝置，應在滅火藥劑放射前停止運轉。放射時間長達三點五分鐘的場所若空調仍在運轉，藥劑會被持續抽離，設計濃度無從建立，因此「先停風、再放藥」是全區放射方式成立的前提。\n與其他滅火設備的放射時間對照：依第 100 條第三款，乾粉滅火設備依核算之滅火藥劑量須於三十秒內全部放射完畢。乾粉靠負觸媒作用抑制燃燒連鎖反應，講求瞬間覆蓋火焰，故時間極短；二氧化碳靠稀釋氧濃度並維持一段時間才生效，才會出現分鐘級的放射時間。把「乾粉三十秒、二氧化碳分鐘級」的物理理由記起來，遠比死背數字牢固。\n單位換算陷阱：條文以「分」為單位，題目卻常改用「秒」發問。三點五分鐘等於二百一十秒、二分鐘等於一百二十秒、一分鐘等於六十秒。當選項同時出現 30、60、90、210 時，只有 210 能由分鐘制的半分倍數換算而來，其餘三者都是整十秒的湊數值，這也是考場上快速篩選的實用技巧。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-009","有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-011","二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-008","移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-012","主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-007","有關水霧滅火設備，下列設置規定何者錯誤？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-013","依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-010",113,"有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-010",112,"水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-010",111,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-010",110,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-010",109,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",1785129972892]