[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-033","fire-108-1-fire-law-033",108,1,33,"依各類場所消防安全設備檢修及申報作業基準規定，有關配線絕緣阻抗試驗合格之判定，若電壓超過 300 V 者，其絕緣電阻值至少應為多少以上？",{"A":16,"B":17,"C":18,"D":19},"0.1 MΩ","0.2 MΩ","0.4 MΩ","3 MΩ","C",null,[],false,"本題考點：配線絕緣阻抗試驗的合格判定值，依《消防安全設備及必要檢修項目檢修基準》第二十七章配線之性能檢查，判定方法為「測定值應符合表 27-3 所列之數值以上」，該表是依電壓分列的判定值表。\n【正解理由】表 27-3 分列各級距之絕緣電阻值：300V 以下而對地電壓為 150V 以下者 0.1MΩ、300V 以下其他情形 0.2MΩ、超過 300V 者 0.4MΩ、3,000V 高壓電路 3MΩ、6,000V 高壓電路 6MΩ。本題問的是「超過 300V」該列，對應值為 0.4MΩ，故選 C。\n【逐項排除】\n(A) 0.1MΩ 是表 27-3 最低一列的值，適用於 300V 以下且對地電壓在 150V 以下者，非本題所問級距。\n(B) 0.2MΩ 同屬 300V 以下該區，適用對地電壓超過 150V 的「其他情形」，仍不是超過 300V 者的值。\n(C) 表 27-3 明列「超過 300V 者 0.4MΩ」，與題目給定的電壓條件完全對應，為應選者。\n(D) 3MΩ 確實列在表 27-3 中，但屬「3,000V 高壓電路」那一列；高壓回路須改用 1,000V、2,000V 或 5,000V 絕緣電阻計測量，與本題低壓級距不同。\n【記憶點】以 300V 畫線：150V 以下 0.1、其他 0.2、超過 300V 0.4；3,000V 配 3MΩ、6,000V 配 6MΩ。","絕緣阻抗試驗量的是配線相互間與配線對大地間的絕緣還撐不撐得住。消防安全設備的配線多處於常時通電或監視狀態，一旦受潮、老化、鼠咬或壓損而絕緣劣化，輕則受信總機誤報，重則火災時該動作的回路不動作，因此檢修基準把它列為配線的性能檢查項目。\n檢查方法有幾個要件常被拆開來單獨命題：其一，須先切斷電壓電路之電源，並以電壓（流）計等確認已無充電情形後才測定；其二，測定對象為電源回路、操作回路、表示燈回路、警報回路等之電壓電路，量配線間及配線與大地間；其三，低壓回路開關器或斷路器之每一分岐回路，使用 500 伏特以下之絕緣電阻計；其四，高壓回路則使用 1,000 伏特、2,000 伏特或 5,000 伏特之絕緣電阻計；其五，使用因絕緣阻抗試驗會有妨礙之虞的電子零件回路，以及配線相互間難以測定之回路，得予省略。\n判定側則是一句話加一張表：測定值應在表 27-3 所列數值以上。0.1／0.2／0.4MΩ 這一組與國內低壓用電設備所採的絕緣電阻分級同屬一套數值體系，3MΩ、6MΩ 則是分別對應 3,000V 與 6,000V 高壓電路，級距與量測用電壓都不同，把高壓那兩格的數值拿來回答低壓題是最典型的陷阱。\n易混淆的還有絕緣電阻與接地電阻：前者單位為 MΩ，數值越大越好，判定寫「以上」；後者單位為 Ω，數值越小越好，判定寫「以下」。看到判定句用「以上」或「以下」，就能先分辨題目問的是哪一種電阻。\n配線這一章的其他考點也常與本題交錯：絕緣阻抗屬性能檢查，而配線的外觀檢查另看接續狀況、標示與耐燃耐熱配線之區分，兩者分屬不同檢查層次，作答時先看題目問的是外觀檢查還是性能檢查，再找對應的判定方法。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-032","依各類場所消防安全設備檢修及申報作業基準規定，有關避難器具開口部大小之檢查，下列何者正確？",32,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-034","依消防法施行細則，有關消防安全設備之設計、監造、裝置及檢修工作項目之規定，下列何者正確？",34,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-031","依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",31,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-035","依建築技術規則建築設計施工編規定，女兒牆之高度應在多少公尺以內？",35,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-030","依各類場所消防安全設備設置標準規定，下列何種處所得免設排煙設備？",30,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-036","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，下列何者不符合呼水裝置之規定？",36,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-033",114,"依六類公共危險物品製造儲存及處理場所標示板規格及設置要點規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-033",113,"依建築技術規則建築設計施工編規定，下列何者不視為居室？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-033",112,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-033",111,"依消防法施行細則規定，供公眾使用建築物應遴選防火管理人並制定消防防護計畫，其相關規定下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-033",110,"依消防安全設備及必要檢修項目檢修基準規定，有關固定式泡沫滅火設備（低發泡）綜合檢查之檢查方法，下列敘述何者正確？",1785129970373]