[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-030","fire-108-1-fire-law-030",108,1,30,"依各類場所消防安全設備設置標準規定，下列何種處所得免設排煙設備？",{"A":16,"B":17,"C":18,"D":19},"建築物在第十層以下之各樓層（地下層除外），其非居室部分，天花板及室內牆面，以耐燃一級材料裝修，且除面向室外之開口外，以半小時以上防火時效之防火門窗等防火設備區劃者","建築物在第十層以下之各樓層（地下層除外），其非居室部分，樓地板面積每 200 平方公尺以下，以防煙壁區劃者","建築物在第十層以下之各樓層（地下層除外），其居室部分，樓地板面積在 200 平方公尺以下，天花板及室內牆面，且包括其底材，均以耐燃一級材料裝修者","設有室內消防栓等滅火設備之場所","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》就得免設排煙設備之處所所定的裝修材料、區劃面積與替代設備三組條件。\n【正解理由】依《各類場所消防安全設備設置標準》第五編消防搶救上之必要設備中關於得免設排煙設備處所之規定，建築物在第十層以下之各樓層(地下層除外)之非居室部分，天花板及室內牆面以耐燃一級材料裝修，且除面向室外之開口外，以半小時以上防火時效之防火門窗等防火設備區劃者，即在免設之列,(A) 與此完全相符，故選 A。\n【逐項排除】\n(A) 正確。非居室既以耐燃一級材料裝修、又以防火設備區劃，發煙量與煙的擴散範圍雙重受控，排煙的必要性已消失。\n(B) 錯在面積。非居室以防煙壁區劃而得免設者，規定為樓地板面積每一百平方公尺以下，二百平方公尺已超出容許值。\n(C) 錯在面積。居室部分連底材都以耐燃一級材料裝修者，面積門檻同樣是一百平方公尺以下，並非二百平方公尺。\n(D) 錯在設備種類。得以滅火設備替代而免設者，限二氧化碳、乾粉等以窒息方式滅火、放射時須維持防護區劃密閉的設備；室內消防栓屬水系滅火設備，不在免設之列。\n【記憶點】免設排煙記「十層以下、每一百平方公尺、耐燃一級、半小時防火設備」。","要判斷得否免設，先要知道為什麼要設。依《各類場所消防安全設備設置標準》第 28 條，應設排煙設備者包括：供甲類場所使用樓地板面積合計在五百平方公尺以上者；樓地板面積在一百平方公尺以上之居室，其天花板下方八十公分範圍內之有效通風面積未達該居室樓地板面積百分之二者；樓地板面積在一千平方公尺以上之無開口樓層；戲院、電影院等場所之舞臺部分樓地板面積在五百平方公尺以上者；以及依建築技術規則應設置之特別安全梯或緊急昇降機間。免設規定就是這張清單的例外出口。\n\n排煙的目的是維持避難路徑的能見度與可呼吸環境，並為消防人員保留搶救空間。免設條件因此對應三種「排煙已無實益」的情形：其一，空間本身不發煙——天花板與室內牆面以耐燃一級材料裝修，可燃裝修物大幅減少；其二，煙被關住——以防火設備或防煙壁把空間切成小面積區劃，煙層不會蔓延到其他部分；其三，該空間本來就要密閉——設有二氧化碳、乾粉等滅火設備之場所，放射時必須維持氣密才能達到滅火濃度，若同時排煙反而會把藥劑抽走。\n\n居室與非居室的門檻寬嚴不同也要記牢：非居室(走廊、機房、倉庫等非供起居使用之部分)因無人長時間停留，條件較寬；居室因有人停留，要求裝修連底材都須為耐燃一級，或另以具一小時以上防火時效之牆壁與防火門窗形成區劃。此外，同樣是「得免設」的條文，第 49 條列的是得免裝撒水頭之處所，例如洗手間、浴室或廁所、電信機械室或電腦室、發電機與變壓器等電氣設備室、手術室與加護病房等，兩張清單常被交叉命題，答題時務必看清楚問的是排煙設備還是撒水頭。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-029","依各類場所消防安全設備設置標準，下列有關室內消防栓箱的規定何者錯誤？",29,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-031","依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",31,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-028","依可燃性高壓氣體儲存場所防爆牆設置基準規定，防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，其強度應能承受可能預料之氣體爆炸衝擊。下列有關其構造規定何者錯誤？",28,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-032","依各類場所消防安全設備檢修及申報作業基準規定，有關避難器具開口部大小之檢查，下列何者正確？",32,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-027","下列有關二氧化碳滅火設備各種標示規格規定之敘述，何者錯誤？",27,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-033","依各類場所消防安全設備檢修及申報作業基準規定，有關配線絕緣阻抗試驗合格之判定，若電壓超過 300 V 者，其絕緣電阻值至少應為多少以上？",33,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-030",114,"下列何者非屬各類場所消防安全設備設置標準之警報設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-030",113,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準規定，對於電動機之構造與機能，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-030",112,"依消防安全設備及必要檢修項目檢修基準之規定，有關惰性氣體滅火設備之綜合檢查，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-030",111,"依各類場所消防安全設備設置標準規定，某樓層高度超過 10 公尺且樓地板面積在 700 平方公尺以上之高架儲存倉庫，其撒水頭設置應符合之規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-030",110,"可燃性高壓氣體儲存場所防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，強度應能承受可能預料之氣體爆炸衝擊，有關混凝土空心磚製防爆牆之規定，下列敘述何者正確？",1785129970348]