[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-026","fire-108-1-fire-law-026",108,1,26,"依防火牆及防火水幕設置基準規定，若防火水幕之防護高度為 12 公尺，請問其每公尺水幕長度放水量應在每分鐘多少公升以上？",{"A":16,"B":17,"C":18,"D":19},"90","100","110","120","D",null,[],false,"本題考點：《防火牆及防火水幕設置基準》所定防火水幕放水量與防護高度之間的正比關係。\n【正解理由】依內政部函頒《防火牆及防火水幕設置基準》關於防火水幕之規定，每一公尺水幕長度之放水量，應在每分鐘十公升乘以防護高度(以公尺計)所得之值以上。防護高度為十二公尺時，即為每分鐘一百二十公升以上，故選 D。\n【逐項排除】\n(A) 90 對應的防護高度為九公尺，比題目所給的十二公尺少了三公尺，水幕上緣的水膜將無法完整覆蓋受熱面。\n(B) 100 對應的防護高度為十公尺，是把防護高度誤看成十公尺再乘以係數十所得，屬讀題不慎的陷阱值。\n(C) 110 對應的防護高度為十一公尺，與正解僅差一公尺，是最容易誤選的干擾項，代入時務必逐位核對。\n(D) 正確。防護高度十二公尺乘以每分鐘十公升，得每分鐘一百二十公升，與基準所定下限相符。\n【演算步驟】公式:q ＝ 10 L\u002F(min·m) × H;代入 H ＝ 12 m:q ＝ 10 L\u002F(min·m) × 12 m ＝ 120 L\u002Fmin;結果：每公尺水幕長度之放水量應在 120 L\u002Fmin 以上。\n【記憶點】防火水幕「一公尺高配十公升」,防護高度乘十就是每公尺水幕長度的每分鐘放水量。","防火水幕的作用機制與滅火設備不同：它不是要撲滅儲槽火，而是在火源與受體之間拉起一道連續水膜，靠水的吸熱與蒸發把穿透的輻射熱衰減到受體可承受的程度，同時阻擋火焰直接接觸。既然要遮蔽的是一個面，水量自然與「要遮多高」成正比——防護高度愈高，單位長度水幕需要維持的水膜面積愈大，故基準採每公尺水幕長度每分鐘十公升乘以防護高度的線性公式，而不是給一個固定值。\n\n這題與假想火面高度是同一串考點：先以儲槽水平剖面最大直徑乘閃火點係數求出假想火面高度，再定防火水幕的防護高度，最後乘以十得放水量。若題目給的是儲槽直徑而不是防護高度，就必須先做第一步再做第二步，漏掉係數是最常見的失分點。單位換算方面，每分鐘一百二十公升等於零點一二立方公尺每分鐘、七點二立方公尺每小時；若水幕長度為二十公尺，總放水量即為每分鐘二千四百公升，水源容量與加壓送水裝置都要據此核算。\n\n放水量本來就是設備類科的高頻數值考點，可以整批對照記憶：依《各類場所消防安全設備設置標準》第 34 條，第一種室內消防栓在全部同時使用時，各瞄子放水量在每分鐘一百三十公升以上，第二種則在每分鐘八十公升以上。依同標準第 50 條，撒水頭之放水量每分鐘應在八十公升以上，設於高架倉庫者為一百十四公升，小區劃型撒水頭則為五十公升以上。把這些數值與防火水幕的一百二十公升並列，就不容易張冠李戴。另一個延伸方向是水源與加壓送水裝置：防火水幕的水源容量必須能支持水幕在規定時間內持續放水，一旦防護高度提高使放水量增加，水源容量與幫浦的出水量、揚程都要同步放大，這常是計算題的第二段設問。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-025","依防火牆及防火水幕設置基準規定，假想火面高度為將儲槽水平剖面最大直徑乘以規定之數值。當公共危險物品之閃火點未達攝氏 70 度時，應乘以之數值為何？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-027","下列有關二氧化碳滅火設備各種標示規格規定之敘述，何者錯誤？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-024","依消防法第 6 條及其相關規定，有關住宅用火災警報器下列何者正確？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-028","依可燃性高壓氣體儲存場所防爆牆設置基準規定，防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，其強度應能承受可能預料之氣體爆炸衝擊。下列有關其構造規定何者錯誤？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-023","依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列有關「擋牆」之敘述，何者錯誤？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-029","依各類場所消防安全設備設置標準，下列有關室內消防栓箱的規定何者錯誤？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-026",114,"依據消防法、公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關公共危險物品管制量規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-026",113,"依消防安全設備檢修專業機構管理辦法規定，檢修機構自行停業、受停業處分或逾多久不辦理檢修業務時，應報中央主管機關備查，並將原領證書送中央主管機關註記後發還之？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-026",112,"有關得免設排煙設備之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-026",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，液化石油氣備用量，供營業使用者，不得超過 X 公斤；供家庭使用者，不得超過 Y 公斤，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-026",110,"依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",1785129970319]