[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-035","fire-108-1-alarm-evacuation-035",108,1,35,"依各類場所消防安全設備設置標準規定，在應設排煙設備之場所，有關其排煙設備設置之描述，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"防煙區劃之範圍內，任一位置至排煙口之水平距離在 30 公尺以下","地下建築物之地下通道，其排煙機之總排煙量應在每分鐘 600 立方公尺以上","室內排煙規定排煙機之排煙量應在每分鐘 300 立方公尺以上","地下建築物之地下通道每 300 平方公尺應以防煙壁區劃","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 188 條排煙設備之設置規定，尤其是排煙機排煙量與防煙區劃面積這幾組數值。\n【正解理由】依《各類場所消防安全設備設置標準》第 188 條第八款，排煙機之排煙量在每分鐘一百二十立方公尺以上；且在一防煙區劃時，在該防煙區劃面積每平方公尺每分鐘一立方公尺以上；在二區以上之防煙區劃時，在最大防煙區劃面積每平方公尺每分鐘二立方公尺以上。條文所定的基本門檻是每分鐘一百二十立方公尺，選項所稱三百立方公尺並非本款所列數值，敘述錯誤，為本題應選者，故選 C。\n【逐項排除】\n(A) 同條第三款明定「防煙區劃之範圍內，任一位置至排煙口之水平距離在三十公尺以下」，敘述與條文相符，正確。\n(B) 同條第八款但書：「但地下建築物之地下通道，其總排煙量應在每分鐘六百立方公尺以上」，敘述正確。\n(C) 室內排煙之排煙機排煙量法定下限為每分鐘一百二十立方公尺，敘述將其抬高為三百立方公尺，與條文不符。\n(D) 同條第二款「地下建築物之地下通道每三百平方公尺應以防煙壁區劃」，敘述正確；一般樓層則依第一款為每五百平方公尺區劃，兩者不可互換。\n【記憶點】排煙機基本量一二〇、地下通道總量六〇〇（每分鐘立方公尺）；防煙壁區劃一般五百平方公尺、地下通道三百平方公尺。","《各類場所消防安全設備設置標準》第 188 條規範的是第 28 條第一項第一款至第四款排煙設備要「怎麼設」，全條十款依序處理防煙區劃、排煙口位置、材料、防火閘門、開關裝置、開口面積、排煙機能力與緊急電源，是本科數值最密集的條文之一。把數值抽出來排列：每層樓地板面積每五百平方公尺內以防煙壁區劃（戲院、電影院、歌廳、集會堂等場所觀眾席及工廠等類似建築物，天花板高度在五公尺以上且天花板與室內牆面以耐燃一級材料裝修者除外）；地下建築物之地下通道每三百平方公尺區劃；任一位置至排煙口之水平距離在三十公尺以下；排煙口設於天花板或其下方八十公分範圍內；排煙口之開口面積在防煙區劃面積之百分之二以上且以自然方式直接排至戶外，無法自然排出時應設排煙機；排煙機排煙量每分鐘一百二十立方公尺以上，一防煙區劃時每平方公尺每分鐘一立方公尺以上，二區以上時以最大防煙區劃面積每平方公尺每分鐘二立方公尺計；地下建築物之地下通道總排煙量每分鐘六百立方公尺以上；連接緊急電源並能有效動作三十分鐘以上。同條第二項另定防煙壁指以不燃材料建造、自天花板下垂五十公分以上之垂壁，但地下建築物之地下通道應下垂八十公分以上。\n最容易失分的是單位陷阱。第 188 條的排煙量一律以「每分鐘立方公尺」表示，而第 189 條特別安全梯或緊急昇降機間排煙室的排煙機、進風機則以「每秒立方公尺」表示，為每秒四立方公尺（兼用時每秒六立方公尺）以上。若把兩者混用，會算出相差六十倍的答案。換算後每秒六立方公尺相當於每分鐘三百六十立方公尺，遠高於室內排煙的一百二十，理由是排煙室屬避難最後據點，必須維持無煙。\n此外，第 190 條列有得免設排煙設備之八款處所，例如十層以下各樓層之非居室以耐燃一級材料裝修並以半小時以上防火時效之防火門窗等防火設備區劃者、樓梯間與昇降機昇降路與管道間與洗手間廁所、設有二氧化碳或乾粉等自動滅火設備之場所、集合住宅與學校教室與體育館與室內游泳池等。「應設—如何設—免設」三層次併讀，才是本主題的完整地圖。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-034","依各類場所消防安全設備設置標準之規定，下列何種避難器具的開口面積應為高 60 公分以上，寬 60 公分以上？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-036","依各類場所消防安全設備設置標準第 28 條應設置排煙設備之規定，下列何者錯誤？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-033","有關 B 級出口標示燈（顯示避難方向符號者）及 B 級避難方向指示燈有效範圍的規定，下列何者正確？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-037","某機場候機室樓地板面積 300 m2，自然排煙設備其窗戶都在天花板或其下方 80 公分範圍內，共有 10 扇窗，採正向由上往外推可達 90°，請問每一扇窗面積多大才合格？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-032","下列出口標示燈及避難方向指示燈之緊急電源描述何者正確？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-035",113,"某揚聲器額定輸出功率 10 W，量測其額定功率之音響功率位準為 98 dB，試問依緊急廣播設備用揚聲器認可基準規定，採性能設計之緊急廣播設備揚聲器，於該揚聲器上所標示之音響功率位準（1 W）應為多少 dB？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-035",112,"有關緊急電源插座保護箱之外觀試驗，依據緊急電源插座測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-035",110,"依各類場所消防安全設備設置標準規定，避難指標設於走廊或通道時，自走廊或通道任一點至指標之步行距離在多少公尺以下？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-035",109,"有關避難器具開口部周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-alarm-evacuation-035",107,"依各類場所消防安全設備檢修及申報作業基準規定，緊急電源插座為單相交流 110 V 者，應用額定 150 V， X 安培之接地型插座。三相交流 220 V 者則適用額定 250 V，Y 安培接地型插座，並確認應無變形、損傷、顯著腐蝕或異物阻塞等，下列何者正確？",1785129964927]