[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-026","fire-108-1-alarm-evacuation-026",108,1,26,"依各類場所消防安全設備設置標準規定，裝置面高度 10 公尺者，不可選擇下列何種探測器設置？",{"A":16,"B":17,"C":18,"D":19},"火焰式探測器","偵煙式局限型 2 種","差動式分布型","定溫式局限型特種","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 114 條「探測器應依裝置場所高度選擇種類」之對照表，10 公尺落在「八公尺以上未滿十五公尺」欄。\n【正解理由】第 114 條之表把裝置場所高度分為未滿四公尺、四公尺以上未滿八公尺、八公尺以上未滿十五公尺、十五公尺以上未滿二十公尺四欄。裝置面高度 10 公尺屬第三欄，該欄所列可設之探測器僅有差動式分佈型、離子式局限型一種或二種、光電式局限型一種或二種、光電式分離型、火焰式。定溫式只出現在第一欄的「定溫式」與第二欄的「定溫式特種或一種」，第三欄完全沒有任何定溫式，故 10 公尺高處不得選用定溫式局限型特種，故選 D。\n【逐項排除】\n(A) 火焰式探測器：明列於第三欄，可設；它偵測火焰輻射之紫外線或紅外線，不受熱氣流在高處被稀釋之影響。\n(B) 偵煙式局限型 2 種：第三欄列有離子式局限型一種或二種、光電式局限型一種或二種，此二者即偵煙式局限型，二種可設。\n(C) 差動式分布型：第三欄首位即為差動式分佈型，可設；它以空氣管或熱電偶分布於整個探測區域感測溫升率，高天花板下仍能取得足夠溫差。\n(D) 定溫式局限型特種：第三欄未列任何定溫式；定溫式須待該點達標稱動作溫度才動作，天花板愈高熱氣流稀釋愈嚴重，八公尺以上即退場，為本題應選者。\n【記憶點】八公尺以上就與差動式局限型、補償式、定溫式告別，只留分布型、偵煙式與火焰式。","高度分欄的物理理由是火羽流的稀釋：燃燒產生的熱氣流上升過程中不斷捲入冷空氣，天花板愈高、抵達裝置面時的溫升與流速愈低，靠單點溫度或溫升率動作的探測器就愈不可靠。因此第 114 條的表由左至右，可用種類逐欄變少，且等級逐欄提高——十五公尺以上未滿二十公尺欄只剩離子式局限型一種、光電式局限型一種、光電式分離型一種、火焰式，連二種都被淘汰。\n這個結論可以用別條交叉驗證。第 120 條差動式局限型、補償式局限型及定溫式局限型的有效探測範圍表，欄位只做到「四公尺以上未滿八公尺」就結束，八公尺以上根本沒有對應數值，等於從另一個角度證明這三類在高處不再適用；表中定溫式局限型二種在四公尺以上欄甚至已標為不適用。第 122 條偵煙式探測器的表則做到「四公尺以上未滿二十公尺」，一種或二種有效探測範圍 75 平方公尺，三種在該欄無值，代表偵煙式三種只能用在未滿四公尺處，這也解釋了為何選項只寫「偵煙式局限型 2 種」而不寫三種。第 123 條再補上光電式分離型的邊界：設在天花板等高度二十公尺以下之場所、光軸高度在天花板等高度百分之八十以上、光軸與警戒區任一點之水平距離在七公尺以下。\n易混淆的是三種構造名詞：局限型是一個點感測一小塊區域；分布型把感測元件（空氣管、熱電偶、熱半導體）鋪滿整個探測區域，取整區的平均變化，因此耐得住高天花板；分離型是送光器與受光器分置兩端，以光軸被煙遮蔽的減光率動作，適合大空間與挑高場所。另可一併記第 119 條：探測區域以淨高四十公分以上之樑區劃，但差動式分布型及偵煙式探測器需六十公分以上，數字剛好與上述兩類「適合大空間」的性格呼應。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-025","依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-027","依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-024","某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-028","有關緊急廣播設備之敘述，下列何者錯誤？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-023","偵煙式局限型探測器裝設於防火構造建築物天花板高度 8 公尺之裝置面時，若樓地板面積為 500 平方公尺，且其天花板中間有一下垂 40 公分的樑隔開，試問至少須設置幾個偵煙式局限型 1 種探測器？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-029","消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-026",113,"依規定出口標示燈及避難方向指示燈，應保持不熄滅。惟為配合政府機關推動節能減碳措施，除上述燈具採用省電產品外，出口標示燈及走廊通道避難方向指示燈，符合下列何者規定，得予減光或消燈？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-026",112,"依各類場所消防安全設備設置標準規定，醫院在第 3 層樓可以使用下列何種避難器具？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-026",111,"因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-026",110,"對於單相交流 110 V 之緊急電源插座進行外觀及性能檢查時，下列何者與消防安全設備及必要檢修項目檢修基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-026",109,"有關緊急廣播設備配線之設置，除依屋內線路裝置規則外，下列何者與各類場所消防安全設備設置標準之規定不同？",1785129964842]