[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-021","fire-108-1-alarm-evacuation-021",108,1,21,"依各類場所消防安全設備設置標準規定，下列危險物品場所何者不須設置火警自動警報設備？",{"A":16,"B":17,"C":18,"D":19},"室內儲存場所管制量 100 倍以上者","製造場所總樓地板面積 500 m2 以上者","一般處理場所管制量 50 倍以上者","室內儲槽場所達顯著滅火困難者","C",null,[],false,"本題考點：公共危險物品等場所應設火警自動警報設備之門檻，屬《各類場所消防安全設備設置標準》第四編的專章規定，數值與一般場所完全不同。\n【正解理由】依第 205 條第 1 項，製造場所及一般處理場所之門檻為「總樓地板面積在五百平方公尺以上」或「室內儲存或處理公共危險物品數量達管制量一百倍以上」；室內儲存場所為「數量達管制量一百倍以上」或「總樓地板面積在一百五十平方公尺以上」；室內儲槽場所則以「達顯著滅火困難」為門檻。一般處理場所的管制量門檻既然是一百倍，題目所稱的五十倍尚未達到，即不在應設之列，故選 C。\n【逐項排除】\n(A) 室內儲存場所管制量一百倍以上，正落在第 205 條第 1 項第 2 款第 1 目，屬應設置之場所。\n(B) 製造場所總樓地板面積五百平方公尺以上，符合同項第 1 款第 1 目，屬應設置之場所。\n(C) 一般處理場所之管制量門檻為一百倍，五十倍未達門檻，不須設置火警自動警報設備，為本題應選者。\n(D) 室內儲槽場所達顯著滅火困難者，明列於同項第 3 款，屬應設置之場所。\n【記憶點】公危場所火警自動警報：製造與一般處理看五百平方公尺或一百倍；室內儲存看一百五十平方公尺或一百倍；室內儲槽看「顯著滅火困難」。","第 205 條還有一個常被忽略的第 2 項：前項以外之公共危險物品製造、儲存或處理場所，儲存、處理公共危險物品數量達管制量十倍以上者，應設置手動報警設備或具同等功能之緊急通報裝置，但平日無作業人員者不在此限。因此「管制量五十倍的一般處理場所」並非什麼都不用設——它免的是火警自動警報設備，仍落在手動報警設備或緊急通報裝置的範圍內。命題者常把「不須設置火警自動警報設備」與「不須設置任何警報設備」混為一談，作答時要看清楚問的是哪一種設備。\n判斷公危場所的規範強度，核心是第 194 條的「顯著滅火困難場所」與第 195 條的「一般滅火困難場所」兩組定義。第 194 條就製造場所或一般處理場所列出四種情形：總樓地板面積在一千平方公尺以上、公共危險物品數量達管制量一百倍以上、製造或處理設備高於地面六公尺以上、建築物除供一般處理場所使用外尚有其他用途（各有其但書）；室內儲存場所以管制量一百五十倍以上、特定類別總樓地板面積一百五十平方公尺以上、高度六公尺以上之一層建築物等為準；室內儲槽場所與室外儲槽場所則以儲槽儲存液體表面積四十平方公尺以上或儲槽高度六公尺以上為準。第 195 條的一般滅火困難場所門檻則普遍降一級，例如製造場所或一般處理場所為總樓地板面積六百平方公尺以上未滿一千平方公尺、管制量十倍以上未滿一百倍。第 202 條進一步規定一般滅火困難場所之滅火設備：製造場所、一般處理場所、室內儲存場所、室外儲存場所、第二種販賣場所及室內加油站設置第四種及第五種滅火設備，其第五種滅火設備之滅火效能值在最低滅火效能值五分之一以上；室內及室外儲槽場所則設置第四種及第五種滅火設備各一具以上。\n最後提醒一個結構性陷阱：第四編的規定只適用於公共危險物品及可燃性高壓氣體場所，一般場所（辦公室、百貨、停車場等）的火警自動警報設備要回頭看第 19 條，兩套數值不得互相套用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-020","依消防法令規定，觀光旅館、飯店、旅館、招待所（限有寢室客房者）等場所，採膠囊式經營時，須設置火警自動警報設備者，下列何者錯誤？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-022","依照各類場所消防安全設備檢修及申報作業基準之規定，會結露之場所適用的探測器為下列何者？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-019","應設排煙設備場所之樑為裸露式者，交錯之樑形成之各防煙區劃皆應設置排煙口。但其樓地板面積每 500 平方公尺防煙區劃內，防煙壁及排煙口之設置，符合各類場所消防安全設備設置標準第 188 條第 1 項第 3 款規定，並符合下列何者，不在此限？〔A：大樑深度（cm）；B：中樑深度（cm）；X：大樑下加設之垂壁高度（cm），其值得為 0；A＋X：防煙壁下垂高度（cm）。〕",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-023","偵煙式局限型探測器裝設於防火構造建築物天花板高度 8 公尺之裝置面時，若樓地板面積為 500 平方公尺，且其天花板中間有一下垂 40 公分的樑隔開，試問至少須設置幾個偵煙式局限型 1 種探測器？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-018","利用加瓦斯試驗器對瓦斯漏氣檢知器進行檢測，其性能判定方法下列何者錯誤？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-024","某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-021",113,"一棟防火構造建築物，其中展覽室長 20 公尺、寬 20 公尺、高 6 公尺，天花板具有一個 50 公分的樑，將其平均分為兩個區域，試問使用補償式局限型一種探測器時，最少應設置幾顆探測器於該區域當中？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-021",112,"依各類場所消防安全設備設置標準之規定，裝設於樓梯 L 級揚聲器，距揚聲器 1 公尺處所測得之音壓規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-021",111,"依各類場所消防安全設備設置標準規定，下列有關出口標示燈及避難方向指示燈之敘述，何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-021",110,"下列有關免設火警探測器之場所，何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-021",109,"有關應設置火警自動警報設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",1785129964793]