[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-014","fire-108-1-alarm-evacuation-014",108,1,14,"緊急照明設備性能試驗之水平面照度測試，切換為緊急電源狀態亮燈，經過 A 分鐘後，使用 B 測試，確認緊急照明燈之照度有無達到法規所規定之值。請問前述 A、B 為何？",{"A":16,"B":17,"C":18,"D":19},"A：30、B：低照度測定用光電管照度計","A：30、B：減光罩","A：20、B：低照度測定用光電管照度計","A：20、B：減光罩","A",null,[],false,"本題考點：緊急照明設備的水平面照度測試，究竟要用什麼儀器量、又要在切換緊急電源亮燈多久之後量，屬「器材＋時間」兩個空格的辨識題。\n【正解理由】依《各類場所消防安全設備設置標準》第 178 條，緊急照明燈在地面之水平面照度，係「使用低照度測定用光電管照度計測得之值」，在地下建築物之地下通道應在十勒克司以上，其他場所應在二勒克司以上；條文既已指名量測器材，B 空格只能是低照度測定用光電管照度計。A 空格則對應緊急照明設備之緊急電源須能持續供電三十分鐘之要求——先在緊急電源狀態下亮滿三十分鐘再量照度，才能同時驗證蓄電池容量與供電末期的照度是否仍達標，故選 A。\n【逐項排除】\n(A) 三十分鐘加低照度測定用光電管照度計，器材與第 178 條所定完全一致，時間也對應緊急電源三十分鐘之供電要求，為本題應選者。\n(B) 器材錯誤。減光罩是對光電式分離型探測器做動作與不動作試驗時遮擋光束用的，本身讀不出地面水平面之勒克司值。\n(C) 器材雖對，但只亮二十分鐘就量，測不出緊急電源末期是否仍能維持照度，時間點取得太早。\n(D) 二十分鐘與減光罩兩處皆不符，時間與器材都錯。\n【記憶點】緊急照明「亮滿三十分鐘，再用低照度光電管照度計量：地下通道十勒克司、其他場所二勒克司」。","勒克司（lux）是每平方公尺接受一流明光通量的照度單位。緊急照明的驗收與檢修都以「地面之水平面照度」為量測面，而不是燈具正下方的最大值，這是條文用語刻意寫成「在地面之水平面照度」的原因。《各類場所消防安全設備設置標準》第 178 條把數值分為兩級：地下建築物之地下通道十勒克司以上、其他場所二勒克司以上，並要求走廊曲折點處增設緊急照明燈——地下通道沒有自然採光、避難距離又長，因此門檻訂為其他場所的五倍。可以一併記的是同標準第 146-6 條：觀眾席引導燈之照度，在觀眾席通道地面之水平面上測得之值在零點二勒克司以上。零點二、二、十這三個數字構成「觀眾席引導燈—一般場所—地下通道」的照度階梯，是本科最常被合併命題的一組數值。\n為什麼測試一定要先切到緊急電源？因為緊急照明的價值全在停電之後。第 176 條規定緊急照明設備除內置蓄電池式外，照明器具應直接連接於分路配線，不得裝置插座或開關；緊急照明燈之電源回路配線應施予耐燃保護，但天花板及其底材使用不燃材料時，得施予耐熱保護。條文用「不得裝插座或開關」＋「耐燃保護」把「常用電源中斷後仍會亮」這件事鎖死，測試自然也要在切換緊急電源之後才有意義。\n易混淆的是各種檢查器材與設備的對應：低照度測定用光電管照度計量的是照度；減光罩用於光電式分離型探測器的動作、不動作試驗；加熱試驗器對應差動式與定溫式探測器；加煙試驗器對應偵煙式探測器；加瓦斯試驗器對應瓦斯漏氣檢知器。看到器材名稱就能反推設備，是選擇題最省時的解法。本題時間數值未見於候選條文原文，僅以緊急電源三十分鐘之要求推得，把握度標為中等。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-013","有關避難器具之外觀試驗，下列何者不屬於外觀試驗？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-015","依建築技術規則對緊急用昇降機之相關規定，下列何者正確？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-012","有關依各類場所消防安全設備設置標準規定設置之耐燃保護、耐熱保護措施，室內消防栓、室外消防栓、自動撒水、水霧、泡沫、乾粉、二氧化碳滅火設備、連結送水管設備等之配管，於實施施工、加壓試驗及配合建築物樓地板、樑、柱、牆施工須預埋消防管線時，消防專技人員何人應一併拍照建檔存證以供消防機關查核，消防機關並得視需要隨時派員前往查驗？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-016","依照各類場所消防安全設備檢修及申報作業基準之規定，某燃燒器具的瓦斯，對空氣比重大於 1 時，其檢知器應設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 A 公尺以內；檢知器上端，應裝設在距樓地板面 B 公分範圍內。請問前述 A、B 為何？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-011","為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-017","某商場有一樓層，以防煙垂壁區劃為四區，各區劃樓地板面積分別為 100 平方公尺、300 平方公尺、250 平方公尺、200 平方公尺，採用機械排煙方式，四區劃僅設置 1 台排煙風機，試問該排煙風機之排煙量每分鐘不得小於多少立方公尺？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-014",113,"某社區活動中心位於建築物第 2 層（非避難層），經檢討該活動中心為有開口樓層，依規定自活動中心任一點易於觀察識別其主要出入口，且與主要出入口之步行距離分別在 X 公尺以下，得免設出口標示燈；步行距離在 Y 公尺以下，得免設避難方向指示燈，則 X+Y=？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-014",112,"依各類場所消防安全設備設置標準規定，火警自動警報設備應採分區鳴動，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-014",111,"依各類場所消防安全設備設置標準規定，供失智照顧型長期照顧服務機構、老人福利機構（安養機構）、產後護理機構等避難弱勢場所之樓層，符合規定者得免設避難器具，下列何者非免設之必要條件？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-014",110,"對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-014",109,"某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",1785129964726]