[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-009","fire-108-1-alarm-evacuation-009",108,1,9,"緩降機固定架或支固器具使用錨定螺栓固定時，選用螺紋標稱為 M12×1.75 之螺栓，試問其螺栓埋入混凝土內不含灰漿部分之深度（mm）及轉矩值須為多少（kgf-cm）？",{"A":16,"B":17,"C":18,"D":19},"埋入深度 60（mm）以上，轉矩值 300～450（kgf-cm）","埋入深度 45（mm）以上，轉矩值 150～250（kgf-cm）","埋入深度 70（mm）以上，轉矩值 600～850（kgf-cm）","埋入深度 50（mm）以上，轉矩值 195～300（kgf-cm）","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 174 條，固定架或支固器具使用錨定螺栓時，螺紋標稱對應之埋入深度與轉矩值表，題示規格為 M12×1.75，須逐列比對。\n【正解理由】第 174 條第一款規定使用錨定螺栓，第二款以表定明螺栓埋入混凝土內不含灰漿部分之深度及轉矩值：M10×1.5 為四十五毫米以上、一百五十至二百五十；M12×1.75 為六十毫米以上、三百至四百五十；M16×2 為七十毫米以上、六百至八百五十。本題螺紋標稱為 M12×1.75，對應之數值即六十毫米以上與三百至四百五十，故選 A。條文特別排除灰漿部分，係因表面粉刷層不具結構強度，不得列入計深。\n【逐項排除】\n(A) 埋入深度六十毫米以上、轉矩值三百至四百五十，與表列 M12×1.75 該列完全相符，為本題應選者。\n(B) 四十五毫米、一百五十至二百五十是 M10×1.5 那一列的數值，螺紋標稱較小，套用於本題規格將使鎖固力不足。\n(C) 七十毫米、六百至八百五十是 M16×2 那一列的數值，屬更大螺紋標稱之要求，過度鎖緊反有使錨體周圍混凝土開裂之虞。\n(D) 五十毫米與一百九十五至三百在該表三列中均不存在，埋入深度與轉矩值兩項同時不符。\n【記憶點】M10 抓四十五、M12 抓六十、M16 抓七十；轉矩則由一百五十、三百、六百依序起跳。","避難器具的固定強度是人命直接懸掛其上的部分，因此設置標準對材料、裝置方法與鎖固力三層都設有規定。第 173 條要求供緩降機或救助袋使用之支固器具，及供懸吊型梯、滑杆或避難繩索使用之固定架，應使用符合 CNS 二四七三、四四三五規定或具有同等以上強度及耐久性之材料，並應施予耐腐蝕加工處理；第 167 條規定緩降機下降時所使用繩子應避免與使用場所牆面或突出物接觸，繩長以裝置位置至地面或其他下降地點之等距離長度為準，支固器具應設在使用場所之柱、地板、樑或其他構造上較堅固及容易裝設之場所，並以螺栓、熔接或其他堅固方法裝置。第 174 條的表，正是「以螺栓裝置」時的量化標準。\n埋入深度與轉矩值是一組互補要求。埋入深度決定錨定螺栓與混凝土之間的握裹長度，深度不足時混凝土會先於螺栓破壞，形成拔出型破壞；轉矩值則決定螺栓的預拉力，鎖得太鬆在反覆荷重下容易鬆脫，鎖得太緊則可能使螺栓降伏或使錨體周圍混凝土開裂，因此條文給的是上下限區間而非單一數值，且區間隨螺紋標稱等比放大。條文特別排除「灰漿部分」，是因為表面粉刷層不具結構強度，計算深度時不得列入，這一句也是選項常被動手腳的地方。\n檢修端可與設置端對照成閉環。檢修基準避難器具一章之性能檢查中，固定部係以目視及扭力扳手確認，判定事項包含螺栓、螺帽應無鬆動或脫落，固定基礎應無因龜裂而引起之破損，固定安裝部分應無明顯腐蝕、生鏽、變形、龜裂等對強度有影響之異常，而穿孔錨栓工法之錨栓所使用螺帽之栓緊，其表列轉矩值同為一百五十至二百五十、三百至四百五十、六百至八百五十，與第 174 條完全一致。記憶時把三種螺紋標稱由小到大排列，深度四十五、六十、七十，轉矩起點一百五十、三百、六百，級距關係便一目瞭然。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-008","感熱式局限型探測器使用加熱試驗器對探測器加熱，依動作時間方法判斷，下列何者符合動作時間之規定？（標稱動作溫度與周圍溫度之差低於 50 度）",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-010","某一廣播區域面積為 150 平方公尺，設有揚聲器，請問距所設揚聲器 1 m 處所測得之音壓須達多少以上才符合規定？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-007","有關無線電通信輔助設備設置規定，下列何者正確？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-011","為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-006","探測器應依裝置場所高度選擇探測器種類裝設，下列何者錯誤？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-012","有關依各類場所消防安全設備設置標準規定設置之耐燃保護、耐熱保護措施，室內消防栓、室外消防栓、自動撒水、水霧、泡沫、乾粉、二氧化碳滅火設備、連結送水管設備等之配管，於實施施工、加壓試驗及配合建築物樓地板、樑、柱、牆施工須預埋消防管線時，消防專技人員何人應一併拍照建檔存證以供消防機關查核，消防機關並得視需要隨時派員前往查驗？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-009",113,"出口標示燈及避難方向指示燈之緊急電源應使用蓄電池設備，其容量應能使其有效動作 20 分鐘以上。但設於下列場所之主要避難路徑，該容量應在 60 分鐘以上，並得採蓄電池設備及緊急發電機併設方式，以下場所何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-009",112,"依據緊急廣播設備用揚聲器認可基準，有關頻率特性試驗，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-009",111,"一非防火構造建築物，某層高度 5.2 公尺供辦公室使用，其探測區域為 310 平方公尺，若裝設補償式局限型 1 種探測器，最少設置數量應為多少個？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-009",110,"瓦斯漏氣火警自動警報設備之性能試驗中，下列有關串接配線試驗之測試及判定，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-009",109,"有關避難方向指示燈裝設之敘述，下列何者錯誤？",1785129964670]