[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-040","fire-107-1-water-chemical-040",107,1,40,"進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",{"A":16,"B":17,"C":18,"D":19},"65%","55%","45%","35%","A",null,[],false,"本題考點：消防幫浦性能試驗中，出水量為額定出水量一點五倍時的全揚程判定基準。\n【正解理由】依《消防幫浦加壓送水裝置及配管摩擦損失計算基準》關於幫浦性能曲線之規範，幫浦在額定出水量百分之一百五十的出水量下，其全揚程應在額定出水量於性能曲線上全揚程之百分之六十五以上；同一套判定另要求全閉揚程在額定點全揚程百分之一百四十以下。前者的用意是確保大流量放水時揚程不致急遽下墜，末端瞄子或噴頭仍保有足夠放水壓力，故選 A。\n【逐項排除】\n(A) 百分之六十五即一點五倍出水量時的全揚程下限，與性能曲線判定基準相符，為正確數值。\n(B) 百分之五十五已低於判定下限，幫浦落在此值代表大流量時揚程衰減過度，應判定性能不良。\n(C) 百分之四十五更低，揚程隨流量急遽衰減，最遠端的放水壓力將無法維持在規定值。\n(D) 百分之三十五為四者中最低，與判定基準差距最大，明顯不符性能曲線的容許範圍。\n【演算步驟】設額定出水量為 Q₀、額定點全揚程 H₀ ＝ 100 公尺（示例值）。試驗點出水量 Q ＝ 1.5 × Q₀。判定式 H ≥ 0.65 × H₀ ＝ 0.65 × 100 公尺 ＝ 65 公尺，即實測全揚程須在 65 公尺以上，占額定點全揚程 65 公尺 ÷ 100 公尺 ＝ 65%。\n【記憶點】幫浦性能三個數字：全閉一百四十以下、額定一百、一點五倍流量六十五以上。","幫浦全揚程並非單一數值，而是隨出水量變化的性能曲線：流量愈大、揚程愈低。性能試驗之所以取全閉點、額定點與一點五倍額定點三個位置，就是用三個點把整條曲線框住——全閉點設上限，避免關閉出水閥時壓力過高而損及配管與閥件；額定點是設計依據；一點五倍額定點設下限，確保火災時多支瞄子或多顆撒水頭同時放水、實際流量遠超額定時，末端仍有足夠壓力。百分之六十五就是這條曲線所容許的衰減底線。\n單位換算是本類題的基本功：一公斤／平方公分約等於十公尺水頭，約等於 0.098 MPa，故放水壓力每平方公分一公斤即約相當於十公尺揚程。設計端的揚程公式可對照《各類場所消防安全設備設置標準》第 58 條，自動撒水設備幫浦全揚程＝配管摩擦損失水頭＋落差＋十公尺；第 42 條室外消防栓幫浦全揚程＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋二十五公尺。式尾的常數即該設備所需放水壓力換算成的水頭，這些是額定點的設計值，而性能試驗驗的是實機曲線能否包住設計需求。\n試驗要能成立，幫浦本身也須具備量測條件：性能試驗裝置可在不影響滅火機能的前提下測定額定出水量時的出水壓力，防止水溫上升用排放裝置避免全閉運轉時水溫升高，啟動用水壓開關裝置則在配管壓力下降時使幫浦啟動；這幾組附屬裝置正是三個試驗點得以逐一量測的前提。\n易混淆對照：一點五倍講的是橫軸的流量倍數，百分之六十五講的是縱軸的揚程比例，兩者不可互換；且全閉揚程的一百四十是上限、一點五倍點的六十五是下限，方向相反。相關考點常延伸到出水量核算，例如第 42 條規定一支室外消防栓在每分鐘四百公升以上、全部消防栓數量超過二支時以二支計算，第 58 條規定幫浦出水量以撒水頭數量乘以每分鐘九十公升，設於高架儲存倉庫者為一百三十公升，使用小區劃型撒水頭者則乘以每分鐘六十公升。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",108,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何種場所不需設置室外消防栓設備？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-108-1-water-chemical-002","自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-037","有關撒水頭設置之敘述，下列何者正確？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-108-1-water-chemical-003","中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",3,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-040",113,"有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-040",112,"有關公共危險物品場所設置自動撒水設備規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-040",111,"二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-040",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-040",109,"儲槽規定設置補助泡沫消防栓時，下列敘述何者錯誤？",1785129973357]