[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-038","fire-107-1-water-chemical-038",107,1,38,"依各類場所消防安全設備設置標準之規定，下列何種場所不需設置室外消防栓設備？",{"A":16,"B":17,"C":18,"D":19},"建築物及儲存總面積在 3,500 平方公尺之可燃性高壓氣體處理場所","建築物及儲存總面積在 6,000 平方公尺之輕工業場所","建築物及儲存總面積在 8,000 平方公尺有可燃性物質存在，但量少之工作場所","建築物及儲存總面積在 3,500 平方公尺之石化作業場所","C",null,[],false,"本題考點：室外消防栓設備的設置門檻，須先把工作場所依危險程度分成高度、中度、低度三級，再各自對應面積數值。\n【正解理由】依《各類場所消防安全設備設置標準》關於用語定義與應設置室外消防栓設備場所之規定，可燃性高壓氣體製造儲存處理場所與石化作業場所屬高度危險工作場所，其建築物及儲存場所第一層與第二層樓地板面積合計達三千平方公尺以上者應設置；輕工業場所屬中度危險工作場所，門檻為五千平方公尺以上；有可燃性物質存在但存量少、延燒範圍小、延燒速度慢，僅形成小型火災者屬低度危險工作場所，門檻為一萬平方公尺以上。(C) 屬低度危險工作場所而面積僅八千平方公尺，未達一萬平方公尺，故選 C。\n【逐項排除】\n(A) 可燃性高壓氣體處理場所為高度危險工作場所，三千五百平方公尺已逾三千平方公尺門檻，應設置。\n(B) 輕工業場所為中度危險工作場所，六千平方公尺已逾五千平方公尺門檻，應設置。\n(C) 低度危險工作場所門檻為一萬平方公尺，八千平方公尺尚未達到，為本題所求。\n(D) 石化作業場所不是靠倉庫堆高或閃火點量測歸級，而是與可燃性高壓氣體場所、木材加工業、油漆作業場所一同被用語定義列名為高度危險工作場所，同樣適用三千平方公尺門檻；三千五百平方公尺已逾門檻，應設置。\n【記憶點】高三、中五、低十（千平方公尺）；先分級，再比面積。","危險程度分級才是這一題的真正考點，面積數字只是分級之後的查表動作。分級判準環繞「可燃物有多少、燒起來有多快」：儲存一般可燃性固體物質的倉庫，堆高超過一定高度者，因垂直延燒快、射水難以到達深層，列為高度危險；易燃性液體物質則以閃火點與特定溫度下的蒸氣壓為門檻，愈易揮發、愈易點燃者愈危險；可燃性高壓氣體的製造、儲存、處理場所與石化作業場所，因具洩漏後迅速擴散並可能爆炸的特性，直接明定為高度危險工作場所，木材加工業與油漆作業場所亦同。中度危險涵蓋倉庫堆高未超過該高度者、閃火點較高的液體作業場所以及輕工業場所。低度危險的定義最容易被忽略：它不是「沒有可燃物」，而是「有可燃性物質存在，但存量少、延燒範圍小、延燒速度慢，僅形成小型火災者」，本題 (C) 的敘述正是照抄這個定義。\n另有兩個常被拿來出題的補充規則。其一是比例合計法：同一基地存在不同危險程度的工作場所而各自都未達門檻時，應以各該場所實際面積為分子、各級規定面積為分母分別計算，比例總和大於一者仍應設置，避免以切割用途規避設置義務。其二是免設規定：應設室外消防栓設備之場所，若已依本標準設置自動撒水、水霧、泡沫、二氧化碳或乾粉等滅火設備，在該有效範圍內得免設。\n體系上要分清楚：室外消防栓是自建築物外部包圍射水，任務在阻止延燒並支援搶救；室內消防栓則供初期滅火。這也是為什麼門檻以第一層及第二層樓地板面積合計計算——它防護的正是最可能向外延燒的低層部分。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-037","有關撒水頭設置之敘述，下列何者正確？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-036","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-040","進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",108,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-038",113,"依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-038",112,"依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-038",111,"一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-038",110,"依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-038",109,"消防專用蓄水池之設置規定，下列何者正確？",1785129973338]