[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-033","fire-107-1-water-chemical-033",107,1,33,"自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"密閉乾式管系應併行空氣壓試驗，應使空氣壓力達到 0.28 MPa 之標準","密閉乾式管系應併行空氣壓試驗，壓力持續 24 小時，漏氣減壓量應在 0.01 MPa 以下","試驗壓力以繼續維持 1.5 小時無漏水現象為合格","試驗壓力不得小於加壓送水裝置全閉揚程 1.5 倍以上之水壓","C",null,[],false,"本題考點：自動撒水設備竣工加壓試驗的水壓倍數與維持時間，以及密閉乾式管系併行空氣壓試驗的壓力與漏氣減壓量。\n【正解理由】依《各類場所消防安全設備設置標準》第四十五條，自動撒水設備竣工時應做加壓試驗，其測試方法準用第三十三條規定；第三十三條明定「試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓。試驗壓力以繼續維持二小時無漏水現象為合格」。故正確的維持時間為二小時，(C) 所寫一點五小時與條文不符，本題問的是錯誤者，故選 C。\n【逐項排除】\n(A) 正確：第四十五條明定密閉乾式管系應併行空氣壓試驗，應使空氣壓力達到每平方公分二點八公斤或 0.28MPa 之標準。\n(B) 正確：同條規定該空氣壓力持續二十四小時，漏氣減壓量應在每平方公分零點一公斤以下或 0.01MPa 以下為合格。\n(C) 錯誤：條文為繼續維持二小時，一點五是水壓的「倍數」，在此被移花接木成試驗時間。\n(D) 正確：準用第三十三條，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓。\n【記憶點】一點五倍水壓撐二小時；乾式再加空氣壓 0.28 撐二十四小時、漏氣不逾 0.01。","第三十三條原本是室內消防栓設備消防立管管系的竣工加壓試驗規定，第四十五條以「準用」把同一套方法搬到自動撒水設備，因此只要記住一組數值就能涵蓋兩種設備：一點五倍全閉揚程、維持二小時。所謂全閉揚程，是幫浦在出水量為零時所能產生的最大揚程；以它的一點五倍加壓，等於讓管系承受運轉中不可能出現的最嚴苛壓力，藉此驗證接頭、法蘭與管件的耐壓能力。\n密閉乾式管系為何要多做一道空氣壓試驗？因為它的流水檢知裝置二次側平時不充水而充壓縮空氣，撒水頭動作後必須先排掉這些空氣，二次側壓力下降才會使流水檢知裝置開啟並送水。管系若有微小漏氣，空氣壓縮機將反覆啟動，嚴重時造成誤動作或延遲放水，故以二十四小時的漏氣減壓量作為氣密性的判準。\n與此配套的是第五十五條：密閉乾式或預動式之空氣壓縮機應為專用，並能在三十分鐘內加壓達流水檢知裝置二次側配管之設定壓力值；二次側之減壓警報設於平時有人處；撒水頭動作後，流水檢知裝置應在一分鐘內使撒水頭放水；撒水頭並使用向上型，以免管內殘水積存。\n易混淆的數值是「同為一點五倍，時間卻不同」：連結送水管之配管依第一百八十一條，須能承受送水設計壓力一點五倍以上之水壓且持續三十分鐘，基準壓力與持續時間都與撒水設備不同，命題者極愛互換這兩組。\n最後要區分層次：加壓試驗屬竣工時的一次性驗證，用來確認管系施作品質；設備啟用後的機能確認，則改由流水檢知裝置的動作試驗與末端查驗閥的放水試驗擔任。兩者目的與方法都不同，不可互相取代，這也是本題把「竣工時」四個字寫進題幹的用意。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-032","泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",32,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-034","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",34,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-036","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",36,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-033",113,"某加油站附設加氣站，其滅火器設置應符合之規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-033",112,"二氧化碳滅火設備滅火藥劑量，下列設置規定何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-033",111,"二氧化碳滅火設備配管，下列設置規定何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-033",110,"依消防安全設備及必要檢修項目檢修基準，滅火器設置間距規定，下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-033",109,"加壓式乾粉滅火設備應設壓力調整裝置，其可調整壓力至每平方公分多少公斤以下？",1785129973295]