[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-028","fire-107-1-water-chemical-028",107,1,28,"有關滅火器性能檢查頻率之規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"化學泡沫滅火器應每年實施一次性能檢查","機械泡沫滅火器應每年實施一次性能檢查","二氧化碳滅火器應每二年實施一次性能檢查","蓄壓式乾粉滅火器應每二年實施一次性能檢查","A",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》滅火器篇中，性能檢查的實施對象與實施頻率。\n【正解理由】依《消防安全設備檢修及申報作業基準》滅火器之檢查方法，外觀檢查對全部滅火器實施，性能檢查則採兩種門檻：化學泡沫滅火器因藥劑係 A 劑與 B 劑水溶液，長期存放會變質、沉澱而失去反應能力，規定每年實施一次性能檢查並更換藥劑；其餘型式之滅火器則以「製造年份是否屆滿一定年限」為實施門檻，而非固定每年或每二年一次。選項 A 與此相符，故選 A。\n【逐項排除】\n(A) 化學泡沫滅火器每年實施一次性能檢查，是基準中唯一以「每年」為週期者，為正解。\n(B) 機械泡沫滅火器之藥劑安定性較高，不採每年實施，而是製造年份屆滿門檻後才實施性能檢查。\n(C) 二氧化碳滅火器為蓄壓式高壓容器，性能檢查並非每二年一次，同樣依製造年份門檻判定。\n(D) 蓄壓式乾粉滅火器亦非每二年一次，其是否須實施性能檢查同樣看製造年份是否屆滿門檻。\n【記憶點】滅火器性能檢查只有化學泡沫是「每年一次」,其餘一律看製造年份，不是每年、也不是每二年。","滅火器的檢查分三個層次，分清楚就不會被選項混淆。外觀檢查是每次檢修都做，查看設置狀況、標示、安全插梢、壓力指示值、瓶體有無變形鏽蝕；性能檢查是拆解檢視藥劑、放射性能與容器內部，對設備負擔較大，因此只對「藥劑會變質」或「使用年限已久」者實施——化學泡沫滅火器屬前者，故每年一次；其餘型式屬後者，以製造年份屆滿門檻(加壓式較短、蓄壓式較長，一般記為加壓式屆滿三年、蓄壓式屆滿五年)為實施條件；第三層是耐壓性能試驗，針對容器本體在達一定年限後施以水壓，確認耐壓強度。\n化學泡沫之所以特別，在於它的滅火機制是化學反應:A 劑碳酸氫鈉水溶液與 B 劑硫酸鋁水溶液在倒轉混合時反應產生二氧化碳，把泡沫推出。兩種水溶液長期靜置會沉澱、結晶或濃度改變，反應一旦不完全，泡沫量與射程立刻不足，這是它必須逐年檢查並更換藥劑的物理化學理由。相對地，乾粉與二氧化碳屬物理性儲壓，只要容器密封良好、壓力維持在使用範圍內，藥劑不會自行劣化，因此改以年限為門檻。\n判讀壓力是同組常考觀念：蓄壓式以指示壓力表的綠色範圍代表正常使用壓力，指針落在綠色範圍外即代表洩壓或超壓。相同觀念也出現在滅火設備端——《各類場所消防安全設備設置標準》第 109 條規定，蓄壓式乾粉滅火設備應設置以綠色表示使用壓力範圍之指示壓力表；第 107 條規定加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至每平方公分二十五公斤以下或 2.5MPa 以下。注意這兩條規範的是滅火「設備」,與滅火「器」分屬不同章節，考題常刻意混用兩者的名詞，看到「蓄壓式」時先確認題目問的是滅火器還是滅火設備。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-029","全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-026","室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-025","泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-028",113,"下列場所之消防安全設備設置何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-028",112,"有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-028",111,"依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-028",110,"消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-028",109,"水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",1785129973265]