[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-026","fire-107-1-water-chemical-026",107,1,26,"室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",{"A":16,"B":17,"C":18,"D":19},"A=1；B=1","A=1.5；B=1","A=1；B=2","A=1.5；B=2","D",null,[],false,"本題考點：室內消防栓設備之消防立管管系竣工加壓試驗的試驗壓力倍數與維持時間。\n【正解理由】依《各類場所消防安全設備設置標準》第 33 條，條文明定「室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓。試驗壓力以繼續維持二小時無漏水現象為合格」,故 A 為 1.5、B 為 2,故選 D。\n【逐項排除】\n(A) A＝1、B＝1 兩個數值都低於條文要求；試驗壓力若僅取全閉揚程一倍，無法檢出接頭與焊道在異常高壓下的滲漏。\n(B) A＝1.5 倍正確，但 B＝1 小時不足，條文要求繼續維持二小時，加壓時間過短會使緩慢滲漏來不及顯現。\n(C) B＝2 小時正確，但 A＝1 倍不足，未達一點五倍之試驗壓力，等於只用運轉時的最高靜壓試壓。\n(D) A＝1.5、B＝2 與第 33 條逐字相符，為正解。\n【記憶點】室內消防栓立管試壓記「一點五倍、二小時」;倍數與時數各設一個誘答，錯一個就整題錯。","全閉揚程(又稱締切揚程)是消防幫浦在出水量為零時所能產生的最大揚程，也是系統可能承受的最高靜壓。竣工加壓試驗以全閉揚程的一點五倍為試驗壓力，用意是把配管、接頭、閥件推到遠高於運轉工況的壓力下，提早暴露潛在缺陷；維持二小時則是為了讓微量滲漏有時間顯現，短時間加壓往往看不出接頭的緩慢滲水。\n這一條是「準用中樞」,許多設備的試壓規定都指回它，把準用關係記熟，一條可抵好幾條：第 45 條規定自動撒水設備竣工時應做加壓試驗，其測試方法準用第三十三條規定，但密閉乾式管系應併行空氣壓試驗，試驗時應使空氣壓力達到每平方公分二點八公斤或 0.28MPa 之標準，壓力持續二十四小時，漏氣減壓量應在每平方公分零點一公斤以下或 0.01MPa 以下為合格；第 74 條規定泡沫滅火設備竣工時之加壓試驗準用第四十五條等規定；第 209 條規定公共危險物品等場所之室內消防栓設備，其配管、試壓等準用第三十二條、第三十三條等規定。\n易混淆對照是連結送水管：第 181 條規定其配管應能承受送水設計壓力一點五倍以上之水壓，且持續三十分鐘；設有中繼幫浦時，幫浦二次側配管應能承受幫浦全閉揚程一點五倍以上之水壓。倍數同樣是一點五倍，但基準值(送水設計壓力)與持續時間(三十分鐘)都不同。因此正確的記法是「倍數都是一點五，時間各不同——室內消防栓立管二小時、連結送水管三十分鐘、密閉乾式管系空氣壓試驗二十四小時」,把時間當作辨識鍵，才不會在選項互換時被騙。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-025","泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-024","竣工查驗時，於屋頂使用口徑 16 mm 瞄子實施第一種室內消防栓綜合檢查，測得放水壓力為 4 kgf\u002Fcm2，所計算之每分鐘放水量約為：",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-028","有關滅火器性能檢查頻率之規定，下列敘述何者正確？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-023","有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-029","全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-026",113,"設於外浮頂式儲槽之泡沫放出口為？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-026",112,"依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-026",111,"壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-026",110,"固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-026",109,"密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",1785129973244]