[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-025","fire-107-1-water-chemical-025",107,1,25,"泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"合成界面活性劑：30 秒","蛋白泡沫滅火藥劑：45 秒","水成膜泡沫滅火藥劑：30 秒","水成膜泡沫滅火藥劑：45 秒","A",null,[],false,"本題考點：泡沫滅火設備綜合檢查中，各類泡沫滅火藥劑的 25% 還原時間標準值。\n【正解理由】依《消防安全設備檢修及申報作業基準》泡沫滅火設備綜合檢查之判定要領，發泡倍率應在五倍以上;25% 還原時間則依藥劑種類分別判定：合成界面活性泡沫滅火藥劑在 30 秒以上，蛋白泡沫滅火藥劑與水成膜泡沫滅火藥劑均在 60 秒以上。選項 A 所列合成界面活性劑 30 秒與判定值相符，故選 A。\n【逐項排除】\n(A) 合成界面活性泡沫的標準值即 30 秒以上，為正解；此類藥劑發泡快、泡沫含水量與安定性較低，故門檻訂得最低。\n(B) 蛋白泡沫滅火藥劑係以水解蛋白質加金屬鹽安定劑製成，泡膜厚實、含水量高而排液慢，判定值與水成膜同為 60 秒以上;45 秒僅及門檻的四分之三，綜合檢查時應判定為不良，不因接近而通過。\n(C) 水成膜泡沫滅火藥劑之標準值為 60 秒以上,30 秒是合成界面活性劑的門檻，兩者張冠李戴。\n(D) 水成膜泡沫滅火藥劑同樣須 60 秒以上,45 秒仍不足；本項與 (B) 同屬「把秒數調到逼近門檻」的誘答，只要記住 60 秒是蛋白與水成膜共用的判定值，兩項可一併排除。\n【記憶點】25% 還原時間「合成三十、蛋白與水成膜六十」;時間越長代表泡沫越安定、越耐燒。","25% 還原時間的定義是：採集發泡後的泡沫試樣，量測其中所含泡沫水溶液還原(排液)達全部水溶液量四分之一所需的時間。排液越慢，泡沫層越能持久覆蓋在油面上隔絕氧氣與可燃蒸氣，所以這個時間是「泡沫安定性」的直接指標，與發泡倍率(發泡後體積除以原泡沫水溶液體積)一起構成綜合檢查的兩大判定項目。合成界面活性泡沫發泡容易、倍率高，但泡膜含水少而排液快，標準值自然訂得比蛋白與水成膜低。\n藥劑種類與濃度是同組必背：第 79 條規定泡沫原液與水混合使用之濃度，蛋白質泡沫液為百分之三或百分之六，合成界面活性泡沫液為百分之一或百分之三，水成膜泡沫液為百分之三或百分之六。放射量則見第 72 條：泡水噴頭放射量在每分鐘七十五公升以上；泡沫噴頭依原液種類，樓地板面積每平方公尺之放射量，蛋白質泡沫液六點五公升以上、合成界面活性泡沫液八公升以上、水成膜泡沫液三點七公升以上。可以看出水成膜因兼具水膜封閉效果，單位放射量要求最低，合成界面活性則最高。\n放射區域與移動式規定也常一併命題：第 75 條規定使用泡沫噴頭時，每一放射區域在樓地板面積五十平方公尺以上一百平方公尺以下；使用泡水噴頭時，放射區域占其樓地板面積三分之一以上且至少二百平方公尺，樓地板面積未達二百平方公尺者依實際面積計。第 219 條則規定移動式泡沫滅火設備之泡沫瞄子放射壓力在每平方公分三點五公斤以上或 0.35MPa 以上。\n易混淆對照：蛋白泡沫耐熱、耐燒回性佳但發泡較慢；水成膜(AFFF)在油面形成水膜、滅火速度最快；合成界面活性泡沫發泡倍率可調範圍最大，高發泡場合多用之。把「安定性排序(蛋白、水成膜高於合成界面活性)」與「還原時間門檻」對應起來，就不必死記數字。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-024","竣工查驗時，於屋頂使用口徑 16 mm 瞄子實施第一種室內消防栓綜合檢查，測得放水壓力為 4 kgf\u002Fcm2，所計算之每分鐘放水量約為：",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-026","室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-023","有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-022","可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽設置滅火器，其設置規定，下列敘述何者正確？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-028","有關滅火器性能檢查頻率之規定，下列敘述何者正確？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-025",113,"有一建築物樓高 40 m，總樓地板面積 30000 m2，其消防專用蓄水池之有效水量規定要多少立方公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-025",112,"有關公共危險物品場所設置室外消防栓之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-025",111,"泡沫試料淨重為 200 g，還原數值如下，則 25%還原時間為何？時間（分） 0 0.5 1 1.5 2 2.5 3 還原量（ml） 0 10 20 30 40 50 60",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-025",110,"自動撒水設備之水源容量規定，若使用側壁型或小區劃型撒水頭時，十層以下樓層在 X 個撒水頭、十一層以上樓層在 Y 個撒水頭繼續放水 20 分鐘之水量以上。X、Y 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-025",109,"高架倉庫內所設置之撒水頭，其放水量每分鐘應在多少公升以上？",1785129973241]