[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-024","fire-107-1-water-chemical-024",107,1,24,"竣工查驗時，於屋頂使用口徑 16 mm 瞄子實施第一種室內消防栓綜合檢查，測得放水壓力為 4 kgf\u002Fcm2，所計算之每分鐘放水量約為：",{"A":16,"B":17,"C":18,"D":19},"134 公升","234 公升","334 公升","434 公升","C",null,[],false,"本題考點：以瞄子放水壓力推算室內消防栓放水量的實測公式 Q＝0.653d²√P。\n【正解理由】竣工查驗與綜合檢查係以皮托管量測瞄子前端之放水壓力，再代入放水量公式 Q＝0.653d²√P(Q 為每分鐘放水量，單位 L\u002Fmin;d 為瞄子口徑，單位 mm;P 為放水壓力，單位 kgf\u002Fcm²)。以口徑 16 mm、放水壓力 4 kgf\u002Fcm² 代入，得約 334 L\u002Fmin,四個選項中僅 C 相符，故選 C。\n【逐項排除】\n(A) 134 公升須 P 約 0.64 kgf\u002Fcm²(134÷167.2＝0.80,平方得 0.64),與題給 4 kgf\u002Fcm² 不符。\n(B) 234 公升須 P 約 1.96 kgf\u002Fcm²,是把放水壓力誤取為 2 kgf\u002Fcm² 所得的結果。\n(C) 334 公升即 0.653×256×2 之計算值，與題給條件完全相符，為正解。\n(D) 434 公升須 P 約 6.7 kgf\u002Fcm²,遠高於題給壓力，非本題條件。\n【演算步驟】公式:Q＝0.653×d²×√P;代入 d＝16 mm → d²＝256 mm²;代入 P＝4 kgf\u002Fcm² → √P＝2;Q＝0.653×256 mm²×2＝334.3 L\u002Fmin,約 334 公升\u002F分。\n【記憶點】口徑平方乘壓力開根號，再乘 0.653;16 mm 配 4 kgf\u002Fcm² 就記成 334 公升。","Q＝0.653d²√P 不是憑空來的常數，而是托里切利定理與流量公式的合併結果。水自瞄子噴出的流速 v＝√(2gh),其中 h 為壓力換算的水頭;1 kgf\u002Fcm² 約等於 10 公尺水頭，故 h＝10P(公尺),代入得 v＝√(2×9.8×10P)≒14√P(公尺／秒)。瞄子出口斷面積 A＝πd²／4,d 以毫米計時 A＝(π／4)d²×10⁻⁶(平方公尺)。理論流量 Q＝CAv,C 為流量係數，直線瞄子約 0.98 至 0.99。把單位由立方公尺／秒換成公升／分(乘 1000 再乘 60)即得 Q≒0.65d²√P,取係數約 0.99 時常數恰為 0.653。理解推導的好處是：若題目改給 MPa,只要先把 1MPa＝10.2 kgf\u002Fcm² 換回來即可，不必另記一條公式。\n這條公式也常以 K 值型式出現:Q＝K√P,對同一支瞄子而言 K＝0.653d² 為定值，口徑 13 mm 時 K≒110、16 mm 時 K≒167、19 mm 時 K≒236。把這三個 K 值記起來，考場上只要乘以壓力的平方根就能秒算:16 mm 配 1 kgf\u002Fcm² 為 167 L\u002Fmin、配 4 kgf\u002Fcm² 為 334 L\u002Fmin、配 9 kgf\u002Fcm² 為 501 L\u002Fmin。壓力與流量是平方根關係，壓力變成四倍，流量只變成二倍，這一點常被拿來出觀念題。\n相關考點連結：一般場所第一種室內消防栓的放水量門檻與本公式互為表裡——量到的壓力換算出的流量須達標準值，竣工查驗才算合格；公共危險物品等場所則另有較嚴規定，第 209 條即要求任一樓層內全部室內消防栓同時使用時，各消防栓瞄子放水壓力在每平方公分三點五公斤以上或 0.35MPa 以上、放水量在每分鐘二百六十公升以上，全部消防栓數量超過五支時以同時使用五支計算，水源容量在最多樓層全部消防栓繼續放水三十分鐘之水量以上。相同的公式，套進不同場所的門檻值，就是本科計算題最常見的變化方式。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-023","有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-025","泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-022","可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽設置滅火器，其設置規定，下列敘述何者正確？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-026","室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-021","有關乾粉滅火設備配管設置規定，下列敘述何者正確？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-024",113,"若同一樓層設 2 個泡沫消防栓箱時，消防幫浦出水量應在每分鐘多少公升以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-024",112,"依各類場所消防安全設備設置標準規定，下列何種場所需設置室外消防栓設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-024",111,"十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-024",110,"需設置自動撒水設備之場所中，下列何者應設開放式？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-024",109,"室外消防栓設備之水帶箱設置，箱內應配置口徑 63 毫米及長多少公尺之水帶 2 條？",1785129973235]