[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-019","fire-107-1-water-chemical-019",107,1,19,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",{"A":16,"B":17,"C":18,"D":19},"X＝3；Y＝10","X＝4；Y＝10","X＝5；Y＝16","X＝10；Y＝20","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》公共危險物品等場所編中，第 228 條第六款對高壓氣體類場所滅火器所定的「單具能力」門檻——每一具對普通火災(A 類)與油類火災(B 類)各須具備幾個滅火效能值。\n【正解理由】依《各類場所消防安全設備設置標準》第 228 條第六款，條文明定「每具滅火器對普通火災具有四個以上之滅火效能值，對油類火災具有十個以上之滅火效能值」,X 為 4、Y 為 10,故選 B。\n【逐項排除】\n(A) X＝3 與條文「四個以上」不符;3 個效能值是一般場所小型滅火器常見規格，不足以因應高壓氣體場所的火災規模。\n(B) X＝4、Y＝10 與第 228 條第六款逐字相符，普通火災(A 類)四個以上、油類火災(B 類)十個以上，為正解。\n(C) X＝5、Y＝16 兩個數值都高於條文要求，條文並無 5 與 16 之規定，屬憑印象加碼的誘答。\n(D) X＝10、Y＝20 是把油類的十個誤植到普通火災欄位，再自行加倍成 20,與條文不符。\n【記憶點】高壓氣體場所滅火器「普四油十」:A 類 4 個、B 類 10 個，數字小的在前。","滅火效能值是滅火器的滅火能力單位，以標準模型火(A 類為木材堆、B 類為油盤)實測所能撲滅的規模換算而得，數字越大代表能力越強。法規之所以不寫「幾公斤」而寫「幾個效能值」,是為了讓不同藥劑、不同容量的產品能在同一把尺上比較。可燃性高壓氣體場所一旦洩漏起火，多以噴射火焰或油類火災型態呈現,B 類需求遠高於 A 類——這正是第 228 條第六款把油類火災要求(十個)訂得比普通火災(四個)高出一倍以上的立法理由。\n條文體系上,《各類場所消防安全設備設置標準》第 207 條先規定可燃性高壓氣體製造、儲存或處理場所及加氣站、天然氣儲槽、可燃性高壓氣體儲槽「應設置滅火器」,第 228 條再把具數與效能值一次講完：製造、儲存或處理場所設置二具，樓地板面積二百平方公尺以上者，每五十平方公尺(含未滿)增設一具；儲槽設置三具以上；加氣站部分，儲氣槽區四具以上、加氣機每臺一具以上、用火設備處所一具以上，建築物每層樓地板面積一百平方公尺以下設二具、超過一百平方公尺時每增加(含未滿)一百平方公尺增設一具；儲存場所任一點至滅火器之步行距離在十五公尺以下，且不得妨礙出入作業；設於屋外者，滅火器置於箱內或有不受雨水侵襲之措施。\n同一組考點常往防護設備延伸：第 229 條冷卻撒水設備之撒水量為防護面積每平方公尺每分鐘五公升以上、水源容量在連續撒水三十分鐘之水量以上；第 231 條射水設備放水壓力在每平方公分三點五公斤以上、放水量在每分鐘四百五十公升以上，數量超過二支時以同時使用二支計算。把「滅火器具數與效能值」「冷卻撒水量」「射水設備壓力與流量」三組數字並排記，是本編最有效率的複習方式。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-018","有關大型滅火器之敘述，下列何者正確？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-020","室內消防栓之水源採重力水箱設置，下列何種裝置不屬於該構造應有之裝置？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-017","一電氣設備室長寬高分別為 12 m、8 m 及 4 m，若採二氧化碳全區放射滅火設備防護，藥劑放射後採機械排放，則其排風機之風量應為每分鐘多少立方公尺？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-021","有關乾粉滅火設備配管設置規定，下列敘述何者正確？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-016","有關乾粉滅火系統之放射時間，下列敘述何者正確？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-022","可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽設置滅火器，其設置規定，下列敘述何者正確？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-019",113,"關於水帶試驗，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-019",112,"依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-019",111,"下列有關滅火器性能檢查之敘述，何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-019",109,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",1785129973197]